MC & FINS Explorer Documentation

Installation

MC & FINS Explorer is a native macOS app, not on the Mac App Store. Download the notarized DMG, open it, and drag the app to Applications.

Download

System Requirements

RequirementMinimum
macOS13 Ventura or newer (Apple Silicon and Intel)
NetworkAn Ethernet or Wi-Fi route to the PLC's IP address. Not needed for the built-in simulator.

Mitsubishi: enable MC protocol (SLMP)

The PLC only answers MC protocol on a port that is opened for it. Which CPUs: MELSEC iQ-R, Q series, L series and iQ-F (FX5) with built-in Ethernet, or an Ethernet module (QJ71E71, RJ71EN71 and similar).

  1. GX Works3 (iQ-R, iQ-F): in the module parameters of the Ethernet port, add an SLMP connection in the external device configuration, and set the protocol (TCP or UDP) and the port number.
  2. GX Works2 (Q, L): in the built-in Ethernet port settings, open Open Setting and add a line with protocol TCP or UDP, open system MC Protocol, and a host station port number.
  3. Set the communication data code to binary or ASCII. The client must use the same code.
  4. To write while the CPU is in RUN, enable "Enable online change" (or "Permit writing in RUN") for the port.
  5. Write the parameters to the PLC and reset or power-cycle it.
SettingValues
Frame3E (most drivers) or 4E (adds a serial number to match responses)
CodeBinary or ASCII, as set in the PLC
TransportTCP or UDP, as set in the PLC
PortAs set in the PLC; 5000 is common
Network / station00 / FF for the CPU you are connected to
FX3U-ENET-ADP and FX3U-ENET-L use the older 1E frame, which this version does not support.

Omron: FINS

FINS listens on UDP port 9600 and, on most current units, TCP port 9600. Which PLCs: CJ1, CJ2, CP1L-E, CP1H with an Ethernet option board, CS1 with an Ethernet unit, and NJ/NX with FINS enabled on the built-in EtherNet/IP port.

FieldWhat to enter
DA1 (destination node)The PLC's FINS node number. With automatic address conversion this is the last octet of the PLC's IP address (192.168.250.1 is node 1).
SA1 (source node)A node number for your Mac that no other device on the FINS network uses, for example the last octet of the Mac's IP address.
DNA / SNA0 on a single local network.
FINS/TCPThe PLC assigns the client node during the handshake; you only enter DA1.

On NJ and NX controllers, FINS reaches memory areas (CIO, DM, W, H, EM). Variables must be mapped to an area with an AT specification to be read over FINS.

Address formats

PLCExamples
Mitsubishi wordsD100, W1A (hex), R0, ZR1000, SD0, TN0 (timer value), CN5 (counter value)
Mitsubishi bitsM0, X10 and Y20 (hex on iQ-R and Q; octal on iQ-F), B0, L0, F0, SM400, TS0, CS5
Omron wordsD100 (DM), CIO 100, W10, H5, A0, E0_100 (EM bank 0)
Omron bitsCIO 0.05, D100.03, W10.00

Types for the tag table: Bool, Int16, UInt16, Int32, UInt32, Float32, BCD16 and Hex. 32-bit types use two consecutive words.

Troubleshooting

  • Mitsubishi times out: check the port number, TCP or UDP, and binary or ASCII all match the PLC's open settings, and that the parameters were written and the CPU reset.
  • Mitsubishi end code C059: the command or subcommand is not supported by this CPU or frame. C056: the request goes past the last address of the device.
  • Omron does not answer over UDP: check DA1 matches the PLC's node number and that SA1 is not used by another device. A firewall or a different subnet also stops the reply.
  • Omron response code 1103: the address is out of range for that area. 0401: the command is not supported by this unit.
  • Writes refused: on Mitsubishi, writing in RUN must be allowed for the port; on Omron, some areas are read-only or write-protected in the PLC setup.
Writing to a PLC that runs a machine changes what the machine does. Test writes and RUN/STOP against the simulator or an idle PLC first.

Support