Installation
EtherCAT Explorer is a native macOS app, not on the Mac App Store: it sends raw Ethernet frames, which the App Store sandbox does not allow. Download the notarized DMG, open it, and drag the app to Applications.
Download
- Free download: dl-ethercat-explorer.voltrus.id
- Pro licence: $39.99 one-time from the Voltrus Console. One key activates one Mac and can be moved.
System Requirements
| Requirement | Minimum |
|---|---|
| macOS | 13 Ventura or newer (Apple Silicon and Intel) |
| Network port | A wired Ethernet port: built in, Thunderbolt or USB adapter, or a dock. Wi-Fi does not work. Not needed for the simulator. |
| Access | An administrator password once per restart, to allow raw Ethernet (see below) |
Licence activation needs an internet connection once. Afterwards the app works offline.
Raw Ethernet access
EtherCAT frames are Ethernet frames with EtherType 0x88A4, not IP traffic. macOS sends and receives them through /dev/bpf*, which only root can open by default. When the app shows that it has no access, choose Grant access and enter an administrator password: the app runs chgrp admin /dev/bpf* && chmod g+rw /dev/bpf*, which lasts until the next restart. Wireshark's ChmodBPF helper does the same at every start; if it is installed, the app does not ask.
Quick Start
- Connect the Mac's Ethernet port to the IN port of the first device on the line, usually the coupler.
- Choose Ethernet port, pick the interface, then Connect and scan.
- The device list shows every device in cable order with its station address, name and AL state. Select one to see its identity, ESC type, ports and distributed clock support.
- Use the state buttons to move all devices, or the selected one, to PRE-OP, SAFE-OP or OP (Pro). Process data starts in SAFE-OP.
Without a line
Choose Simulator, pick a simulated machine (Machine, I/O station or Two servo drives) and Start the simulator. Every view works the same on the simulator.
Device views
| View | Shows |
|---|---|
| Overview | Identity (vendor, product code, revision, serial), station address and alias, ESC type and revision, FMMUs and sync managers, process RAM, ports with link and loop state, distributed clocks and propagation delay, mailbox protocols |
| Process data | The PDO mapping (read over CoE, or from the EEPROM when the device has no CoE) and live values of every entry; outputs can be written in OP (Pro). CiA 402 drives get their statusword decoded. |
| CoE objects | The object dictionary with names, read through SDO Information, and every entry's value; SDO read by index, and SDO write (Pro). Long values use segmented transfers. |
| Registers | ESC registers with decoded meanings, sync managers, FMMUs, and the error counters per port (invalid frames, RX errors, forwarded RX errors, lost links). Register writes and counter resets are Pro. |
| EEPROM | The SII contents: general category, strings, mailbox settings, sync manager and FMMU defaults, PDOs, and a header checksum check. Backup to a .bin file is Pro. |
The Frames tab captures frames with their datagrams decoded (command, address, length, working counter). Saving them as .pcap for Wireshark is Pro.
States and AL status codes
Devices start in INIT. Going up, the app steps through each state (INIT, PRE-OP, SAFE-OP, OP) because devices refuse to skip one. When a device refuses, it sets its AL status code, and the app shows the code and its meaning next to the device: for example 0x001D (invalid output configuration) or 0x0011 (invalid requested state change). Output devices drop back to SAFE-OP when the process data cycle stops for about 100 ms (watchdog, 0x001B).
This version does not configure distributed clock sync. Devices that require DC sync mode to reach OP, such as many servo drives in cyclic synchronous modes, will refuse SAFE-OP or OP with their AL status code.
Free and Pro
Free: scanning a line or the simulator, the device list, INIT, PRE-OP and SAFE-OP, the EEPROM view, registers and error counters, CoE objects with SDO reads, the PDO mapping, live inputs, frame capture and the log. Pro adds OP with output writes, SDO writes, register writes and error counter resets, live trends of any process data entry, EEPROM backup to .bin, .pcap export, and the device list as CSV.
Simulator
The simulated machine is an EK1100 coupler with an EL1008 (8 digital inputs), EL2008 (8 digital outputs), EL3102 (2 analog inputs) and EL4102 (2 analog outputs), and two VD400 servo drives with CiA 402. The devices answer frames at register level: mailboxes, the AL state machine and its status codes, the EEPROM, FMMUs and watchdogs work as on real devices. EL2008 outputs 1 to 4 are wired to EL1008 inputs 1 to 4, and EL4102 channel 1 to EL3102 channel 2, so what you write comes back as an input. The Simulator tab can pull the cable after any device or add RX errors on a port. The terminals use Beckhoff's published identities; the drives are made up.
Troubleshooting
- No interface in the list: plug in the adapter or dock and press refresh next to the list. Pick a wired interface; Wi-Fi cannot carry EtherCAT.
- No access to the interface: choose Grant access and enter an administrator password. After a restart macOS resets the permission.
- No devices found: check the cable goes to the IN port of the first device, that the devices have power, and that no other master (a PLC, TwinCAT) is running on the line.
- Devices missing after a certain point: look at the last device that answers: its Registers view shows lost links and RX errors on its ports, which point to the cable or connector after it.
- A device refuses a state: read its AL status code next to the state. See States.
- Licence key rejected: enter it with its dashes, with internet access for the first activation. See Support.
Support
Email [email protected] or see the support page. EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany. EtherCAT Explorer is not affiliated with or endorsed by Beckhoff Automation or the EtherCAT Technology Group.