K3 in Voltrus Genba
Fire extinguisher and K3 checks, recorded at the equipment.
The inspector scans the QR or NFC tag on an extinguisher, hydrant or forklift and answers check items taken from the regulation's own text. Supervisors see what passed, what failed and what was not checked.
The templates and the certificate register are in the Voltrus Genba console today.
Templates
Check items from the regulation text
Every item names its article. Items that are not a legal requirement are marked as common practice, and limits that differ per plant (such as a boiler’s maximum pressure) are yours to enter from the permit or equipment data.
Every 6 and 12 months
Fire extinguishers (APAR)
Two templates, as in Pasal 11: the 6-month inspection, and the 12-month one with the head cap opened.
- Filled, pressure not dropped, seal and pin intact
- CO2 weighed: 10% under weight must be refilled
- Placement: sign at 125 cm, at most 15 m apart, top at 1.2 m
- 12 months: contents, strainer, thread, gasket, powder not lumpy
- Pressure test at most every 5 years, refill schedule per type
Permenakertrans PER.04/MEN/1980 Pasal 4–8, 11–15, 18. Plus a monthly template for buildings (Permen PU 26/PRT/M/2008).
Monthly and weekly
Hydrants and fire pumps
Visual check of the hydrant cabinet, hose, nozzle and valve, and a weekly fire pump run of at least 30 minutes.
- Cabinet and pillar unobstructed
- Hose, nozzle, couplings present
- Pump run ≥ 30 minutes
- Controller back in automatic
Pump run: Permen PU 26/PRT/M/2008 item 5.4.4.1.1. Hydrant hose cabinets / pillars every 3 months, yard hydrants yearly: items 7.4.5.5.11–12. The check items are common practice.
Monthly (suggested)
First-aid boxes A, B, C
The minimum count of 21 supplies per box type. Counts below the minimum are flagged.
- Sterile gauze 20 / 40 / 40
- Plasters 10 / 15 / 20
- Box holds first-aid supplies only
- White box with the green first-aid symbol, easy to reach
Permenakertrans PER.15/MEN/VIII/2008 Pasal 10, Lampiran II and III. The rule sets no inspection interval.
Each shift
Lifting gear, boilers, pressure vessels
Pre-use check for forklifts and cranes, the boiler operator daily logbook (pressure, steam output, feed water, pH, fuel), and a routine air receiver check.
- K3 sticker and certificate still valid
- Operator's Lisensi K3 valid
- Boiler pressure below the Akte Izin limit
- Safety valve not wedged
Permenaker 8/2020 Pasal 162, 176, 182; Peraturan Uap 1930 Pasal 39; Permenaker 37/2016 Pasal 84; Permenaker 4/2025 Pasal 10 and 16(1)d (daily logbook). Other technical items are common practice.
Certificate register
Expiring certificates stop slipping through
K3 certificates for boilers, pressure vessels, storage tanks and lifting equipment, and operator licences, kept in one register. Validity dates are entered from the original documents; the app does not guess them from the regulations.
- Reminders to supervisors 90, 30 and 7 days before expiry, and once after.
- Status per document: valid, expiring soon, expired.
- Register downloads as Excel, CSV or PDF for audits.
- Lifting operator and technician licences are valid 5 years (Permenaker 8/2020 Pasal 162); enter the date from the card.
Status
What works today, and its limits
Works today
- K3 templates in the checkpoint editor: pick one, then adjust its items and limits.
- A QR or NFC checkpoint at each extinguisher, hydrant, boiler or forklift; the checklist is filled in after the scan, even with no signal.
- Failed items tell the site's supervisors, or open an incident straight away.
- A K3 certificate register with reminders 90, 30 and 7 days before expiry, and once after.
- The register downloads as CSV, Excel or PDF; the per-item check report as CSV.
Its limits
- Validity is not worked out from the regulations: the date is taken from the original document.
- Limits that differ per unit, such as a boiler's maximum pressure, are entered from the permit or equipment data.
- Reminders arrive as Voltrus Genba app notifications on the supervisors' phones, not by email or WhatsApp.
- It does not replace the periodic inspections and their certificates.
Start in the console: add checkpoints, pick templates and fill in the register. Want help setting it up? Ask on WhatsApp.
Sources
What we based it on
We read the official texts on JDIH Kemnaker, the TemanK3 portal, JDIH PU and peraturan.bpk.go.id. Anything we could not find in an official text is not presented as a legal duty.
-
Permenakertrans PER.04/MEN/1980Official text
Installing and maintaining fire extinguishers: 6- and 12-month inspections (Pasal 11–13), pressure test at most every 5 years (Pasal 15), refills (Pasal 18), placement (Pasal 4–10). -
Permenakertrans PER.15/MEN/VIII/2008Official text
Workplace first aid: box types A, B, C and their contents (Lampiran II and III). Official text -
Permen PU 26/PRT/M/2008Official text
Fire protection in buildings: extinguisher check about every 30 days, fire pump run at least 30 minutes a week, hydrant hose cabinets / pillars inspected every 3 months, yard hydrants yearly and after each use, water flow test every 5 years. Official text -
Permenaker 8/2020Official text
Lifting and conveying equipment: periodic inspection at most 2 years after the first, then yearly; lifting accessories yearly; Lisensi K3 valid 5 years. Official text -
Permenaker 37/2016 and Peraturan Uap 1930Official text
Pressure vessels other than steam equipment, and storage tanks (inspection at most every 2 years, testing at most every 5). Boilers fall under Peraturan Uap 1930; we have not found a boiler hydrotest interval in an official text. Official text -
Permenaker 4/2025Official text
Steam equipment operators: class I and II Lisensi K3 valid 5 years (Pasal 10); the operator keeps a daily logbook of working pressure, steam output, feed-water flow, water pH, fuel and the actions taken (Pasal 16(1)d). Official text -
Permenaker 12/2015 and 33/2015Official text
Electrical safety: installations are inspected before handover, after a change or repair, and periodically, at least once a year, with testing at least every 5 years (Pasal 10–11). No template yet; the certificates can go in the register. Official text -
Permenaker 11/2026Official text
Since July 2026 the labour inspection unit issues the certificate stating whether equipment meets K3 requirements. Inspection intervals are unchanged. Official text -
Other technical check itemsCommon practice
Daily forklift, boiler, air receiver and hydrant items not taken from the articles above are common practice, and marked that way in the template.
Voltrus Genba helps record and remind. It does not replace the periodic inspections and tests by labour inspectors or K3 testers, and it does not guarantee compliance.
FAQ
Questions from HSE teams
Start with the extinguishers in one building
Add checkpoints for the extinguishers in one building, pick the 6-month template, print the labels, and enter your certified equipment in the register.
See also: wastewater and B3 waste logbooks → · Voltrus Genba → · Send an email