Compare

Voltrus SCADA vs Rapid SCADA

Rapid SCADA is an open-source .NET SCADA with a free Community edition and low-priced paid editions. Voltrus SCADA is one open-source binary with the configuration in the browser. Published prices and limits first, then what we saw building the same plant in both.

Competitor facts are from their own pages, read on 25 November 2026. Numbers in the table link to the sources.

Voltrus SCADA and Rapid SCADA, point by point.

Factor
Voltrus SCADA
Rapid SCADA
Licence and free option
Core: AGPL-3.0, free for commercial use, no device, tag or retention limits.
Source code under Apache-2.0. Rapid SCADA Community is free; add-on modules are paid separately.[1],[2]
Paid editions
Integrator: $249 lifetime per site, or $19 per month. Enterprise: $999 lifetime, or $79 per month.
Standard: USD 490 / 690 / 920 per server for up to 1,000 / 5,000 / 10,000 channels, add-on modules included. Enterprise: price on request. Embedded: USD 95. Licensed per server with unlimited clients and connections.[1],[5]
Add-ons on the free edition
Core has every protocol, the historian, trends and the API.
Chart Pro USD 49, Notification USD 139, Rapid Gate (sync and redundancy) USD 95, HTTP API driver USD 185, Modbus Slave driver USD 280.[1]
What you install
One executable with the web UI inside, on Linux, Windows, macOS or a Raspberry Pi.
Four services (Server, Communicator, Webstation, Agent) on the ASP.NET Core runtime; on Linux with systemd units and Nginx in front.[3],[4]
AI agents
Built-in MCP server with confirmed writes and a read-only switch.
Not covered by the pages we read.[4]

List prices in the vendor's currency, as published (the source says whether tax is included), before any discount a distributor may give. Partner and reseller figures are indications, not vendor quotes. If a number here is out of date, tell us at [email protected] and we will fix it.

What each one costs an engineer's laptop.

The same water-treatment plant (47 Modbus tags polled every second) on five platforms, idle with no client open, on one Linux machine, 24–25 Nov 2026. Tested in our lab, 24–25 Nov 2026

Measured Voltrus SCADA0.52.0FUXA1.3.6Rapid SCADA6.5.1Ignition8.3.10WinCC OA3.21
Download 22.5 MB tarball936 MB image139 MB zip + .NET 10 runtime2.11 GB compressed imageSiemens packages, image built locally
On disk 63 MB binary (web UI and drivers inside)936 MB image616 MB image4.45 GB image + 1.2 GB Designer on the engineer's PC8.02 GB image
Processes 11 (Node.js)4 (.NET services)1 JVM (+ wrapper)13 WinCC OA + 11 PostgreSQL
Idle RAM, no client 14–16 MiB81 MiB191–211 MiB880–890 MiB235–372 MiB
Idle CPU, % of one core 0.3–0.4 %~0.8 %1.7–2.5 %44–59 %15–21 %
Start to usable 0.1–0.6 s10 s~10 s48–75 s20 s to the first value

Three Voltrus plants side by side, each with its own simulator, config, SQLite database and port, from one copy of the binary: 44 MiB of RAM and about 1 % of one core in total; 63 MB binary plus 24.5 MB of data after about 70 minutes.

  • One Ignition gateway can host several projects: devices, tag providers and historians are shared, so three plants in one gateway cost roughly one gateway plus their tags. Separate gateways (other versions, modules or customers) are a JVM each. From the Ignition docs; the per-gateway cost is from our lab.
  • The Ignition and WinCC OA figures were taken before the lab machine started swapping. Ignition's idle CPU was 44–49 % about 15 minutes after start and 59 % after 21 minutes; it may settle lower after longer.
  • Not measured: several copies of FUXA, Rapid SCADA, Ignition or WinCC OA at once, RAM with clients connected, Windows and macOS, battery and fan.
  • Method, caveats and the scripts to repeat it

What Rapid SCADA does better.

We built the same plant in Rapid SCADA 6.5.1 from the official Linux package in a container. The runtime is solid; configuring it on Linux meant writing our own tool, because the configuration app is Windows-only.

  • Any value bound to a channel shows its status colour (orange on High) with no screen work.
    Tested in our lab, 24–25 Nov 2026
  • Modbus device templates are shared by reference: one register map file serves every device that uses it.
    Tested in our lab, 24–25 Nov 2026
  • Click any value on a screen and a trend of it opens.
    Tested in our lab, 24–25 Nov 2026
  • The server log names the user behind every command ("Command to channel 1035 from user with ID 11").
    Tested in our lab, 24–25 Nov 2026
  • Apache-2.0 source, a Standard licence from USD 490 per server with unlimited clients, and an Embedded edition for USD 95.
    From vendor documentation

Lessons we shipped.

Each of these came out of the lab. They shipped in Voltrus SCADA v0.53.0 (25 Nov 2026). Details, commits and tests: lessons implemented.

  • Every bound value now shows its alarm and quality state colour, with no per-screen work.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • Linked Modbus device templates: fix the register map once and every linked device follows, after a preview.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • A trend popup from any value, up to six pens, each with its own autoscaled axis.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • Alarm chatter count per tag and an on-delay suggestion from the tag's own noise, offered in the tag editor.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • Tag-swap faceplates: one pump, motor, valve or analog faceplate definition, opened by many symbols, each with its own tags; commands go through the command queue.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • Every command shows who sent it and through what: user, API key, MCP, flow or recipe.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026

Each one is the right call somewhere.

Pick Voltrus SCADA when

  • You configure on Linux or a Mac, or want the whole setup in the browser.
  • You want alarm on-delays, multi-pen trends and an API in the free edition.
  • You want AI agents to read the plant over MCP.

Pick Rapid SCADA when

  • You want Apache-2.0 terms rather than AGPL.
  • You work on Windows and are happy with its Administrator tool, or need its Embedded edition for USD 95.
  • You want a paid licence per server under USD 1,000 with unlimited clients and channel tiers.

Where each fact comes from.

  1. Rapid SCADA pricing, effective 1 January 2026 (PDF) (read 25 November 2026)
  2. GitHub: RapidScada/scada-v6 (source, Apache-2.0) (read 25 November 2026)
  3. Rapid SCADA docs: installation on Linux (read 25 November 2026)
  4. Voltrus SCADA README: features, project status, Core vs Enterprise (read 25 November 2026)
  5. Voltrus SCADA pricing (read 25 November 2026)

Rapid SCADA is a trademark of its owner. Voltrus is not affiliated with or endorsed by it.

Tell us about your plant

We reply on WhatsApp or email.

Prefer email? [email protected]