Fronius Smart Meter SunSpec (float) Modbus register map

Modbus map for an energy meter (for example a Fronius Smart Meter) connected to a Fronius Datamanager over Modbus RTU and read over Modbus TCP as SunSpec meter model 211/212/213 (float setting). It lists the common block, AC currents, voltages, power, frequency, power factor and total energy counters. Registers marked not supported in the vendor table are omitted.

Protocol
Modbus TCP via the Fronius Datamanager
Defaults
The meter is read with Modbus device ID 240 for Fronius Smart Meter address 1 (241 for address 2, up to 244 for address 5). Modbus TCP port is preset to 502 on the Datamanager (p. 64, 73, 74, 96).
Addresses in the manual
1-based register numbers (wire address is the number minus 1)
32 and 64-bit values
Not stated in the manual
Registers listed
47
Checked against
Document 42,0410,2049, edition 031-14062024 (English US section). Checked against the copy of that vendor URL archived at web.archive.org on 2024-07-10; the live vendor URL returned HTTP 404 on 2026-10-24, so a newer edition could not be checked.

Address base. Same scheme as the Fronius inverter map: the manual gives register numbers (SunSpec start 40001) and states the address in the Modbus request is one lower, so register 40001 is read with address 40000 (p. 66-67). Addresses here are for the float setting; the integer with scale factor setting (models 201 to 203) uses different addresses. For example 40001 in the manual (SunSpec identifier "SunS") is address 40000 on the wire.

Word order. The manual does not state the word order of 32-bit values or floats. Check a known value (Common_SID should read 0x53756E53) against your master's word order setting.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

47 registers
Manual Wire Register Type Regs Unit Scale Access Area
40001 40000 SunSpec identifier "SunS"Common_SID · Fixed value 0x53756E53 ("SunS"). uint32 2 1 R Holding (FC03)
40003 40002 Model identifierCommon_ID · Fixed value 1. uint16 1 1 R Holding (FC03)
40004 40003 Model lengthCommon_L · Fixed value 65. uint16 1 1 R Holding (FC03)
40005 40004 ManufacturerCommon_Mn · Reads "Fronius". string 16 1 R Holding (FC03)
40021 40020 Device modelCommon_Md string 16 1 R Holding (FC03)
40037 40036 OptionsCommon_Opt string 8 1 R Holding (FC03)
40045 40044 Meter software versionCommon_Vr string 8 1 R Holding (FC03)
40053 40052 Meter serial numberCommon_SN string 16 1 R Holding (FC03)
40069 40068 Modbus device addressCommon_DA · Range 1 to 247. uint16 1 1 R Holding (FC03)
40070 40069 Meter model identifier (211, 212 or 213)Meter_ID · 211 = single phase, 212 = split phase, 213 = three phase. uint16 1 1 R Holding (FC03)
40071 40070 Meter model lengthMeter_L · Fixed value 124. uint16 1 1 R Holding (FC03)
40072 40071 AC total currentMeter_A float32 2 A 1 R Holding (FC03)
40074 40073 AC phase A currentMeter_AphA float32 2 A 1 R Holding (FC03)
40076 40075 AC phase B currentMeter_AphB float32 2 A 1 R Holding (FC03)
40078 40077 AC phase C currentMeter_AphC float32 2 A 1 R Holding (FC03)
40080 40079 AC voltage average, phase to neutralMeter_PhV float32 2 V 1 R Holding (FC03)
40082 40081 AC voltage phase A to neutralMeter_PhVphA float32 2 V 1 R Holding (FC03)
40084 40083 AC voltage phase B to neutralMeter_PhVphB float32 2 V 1 R Holding (FC03)
40086 40085 AC voltage phase C to neutralMeter_PhVphC float32 2 V 1 R Holding (FC03)
40088 40087 AC voltage average, phase to phaseMeter_PPV float32 2 V 1 R Holding (FC03)
40090 40089 AC voltage phase A to BMeter_PPVphAB float32 2 V 1 R Holding (FC03)
40092 40091 AC voltage phase B to CMeter_PPVphBC float32 2 V 1 R Holding (FC03)
40094 40093 AC voltage phase C to AMeter_PPVphCA float32 2 V 1 R Holding (FC03)
40096 40095 AC frequencyMeter_Hz float32 2 Hz 1 R Holding (FC03)
40098 40097 AC powerMeter_W · At meter location 0 (grid), positive means consuming from the grid and negative means feeding in (p. 96). float32 2 W 1 R Holding (FC03)
40100 40099 AC power phase AMeter_WphA float32 2 W 1 R Holding (FC03)
40102 40101 AC power phase BMeter_WphB float32 2 W 1 R Holding (FC03)
40104 40103 AC power phase CMeter_WphC float32 2 W 1 R Holding (FC03)
40106 40105 AC apparent powerMeter_VA float32 2 VA 1 R Holding (FC03)
40108 40107 AC apparent power phase AMeter_VAphA float32 2 VA 1 R Holding (FC03)
40110 40109 AC apparent power phase BMeter_VAphB float32 2 VA 1 R Holding (FC03)
40112 40111 AC apparent power phase CMeter_VAphC float32 2 VA 1 R Holding (FC03)
40114 40113 AC reactive powerMeter_VAR float32 2 VAr 1 R Holding (FC03)
40116 40115 AC reactive power phase AMeter_VARphA float32 2 VAr 1 R Holding (FC03)
40118 40117 AC reactive power phase BMeter_VARphB float32 2 VAr 1 R Holding (FC03)
40120 40119 AC reactive power phase CMeter_VARphC float32 2 VAr 1 R Holding (FC03)
40122 40121 Power factorMeter_PF · Unit cos(). float32 2 1 R Holding (FC03)
40124 40123 Power factor phase AMeter_PFphA float32 2 1 R Holding (FC03)
40126 40125 Power factor phase BMeter_PFphB float32 2 1 R Holding (FC03)
40128 40127 Power factor phase CMeter_PFphC float32 2 1 R Holding (FC03)
40130 40129 Total energy exportedMeter_TotWhExp float32 2 Wh 1 R Holding (FC03)
40138 40137 Total energy importedMeter_TotWhImp float32 2 Wh 1 R Holding (FC03)
40146 40145 Total apparent energy exportedMeter_TotVAhExp float32 2 VAh 1 R Holding (FC03)
40154 40153 Total apparent energy importedMeter_TotVAhImp float32 2 VAh 1 R Holding (FC03)
40194 40193 EventsMeter_Evt · Bit field. uint32 2 1 R Holding (FC03)
40196 40195 End block identifierEnd_ID · Fixed value 0xFFFF. uint16 1 1 R Holding (FC03)
40197 40196 End block lengthEnd_L · Fixed value 0. uint16 1 1 R Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: Fronius Datamanager Modbus TCP & RTU, Operating Instructions (www.fronius.com)

Document 42,0410,2049, edition 031-14062024 (English US section). Checked against the copy of that vendor URL archived at web.archive.org on 2024-07-10; the live vendor URL returned HTTP 404 on 2026-10-24, so a newer edition could not be checked., p. 64, 73, 74, 96-97 (English section, edition 031-14062024). The manual contains no register tables for the meter; the rows come from the Fronius register map archive (Meter float map xlsx, Complete Map sheet).. Read on 2026-10-24.

Also used: Fronius Modbus SunSpec Maps, State Codes and Events (register map archive, version 1.1.7-0) (www.fronius.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.

More from Fronius

All Fronius register maps

Other energy meters