Fronius Datamanager SunSpec inverter (float) Modbus register map

Modbus map of a Fronius inverter read through the Fronius Datamanager over Modbus TCP or Modbus RTU. It holds the SunSpec common block, inverter model 111/112/113 (float setting), nameplate, basic settings, extended measurements, immediate controls, multiple MPPT and basic storage control models, plus the Fronius specific registers and site totals. Fronius meters on the same Datamanager use a separate map. The tables are the float setting; the integer with scale factor setting uses models 101 to 103 and different addresses.

Protocol
Modbus TCP and Modbus RTU (RS485, Datamanager 2.0 only)
Defaults
Modbus TCP port preset 502 (port 80 cannot be used). Modbus RTU is enabled at the factory on Datamanager 2.0, except on Symo Hybrid; baud rate and parity are selectable and the manual states no default. The inverter Modbus device ID equals the inverter number (inverter number 00 is device ID 100). Use a query timeout of at least 10 seconds (p. 62, 63, 72-75).
Addresses in the manual
1-based register numbers (wire address is the number minus 1)
32 and 64-bit values
Not stated in the manual
Registers listed
161
Checked against
Document 42,0410,2049, edition 031-14062024 (English US section). Checked against the copy of that vendor URL archived at web.archive.org on 2024-07-10; the live vendor URL returned HTTP 404 on 2026-10-24, so a newer edition could not be checked.

Address base. The manual gives register numbers (SunSpec start 40001, Fronius registers from 212) and states that the address in the Modbus request is one lower: register 40001 is read with address 40000 (0x9C40), and its worked example reads register 40005 with address 40004 (p. 66-67). This file lists the register numbers as printed. Register numbers of models after the common block depend on the model type setting and on which models the device has, so find the model by its ID and use offsets (p. 75). Model 124 exists only on inverters with a storage solution. For example 212 in the manual (Delete stored ratings of the current inverter) is address 211 on the wire.

Word order. The manual does not state the word order of 32-bit and 64-bit values or floats. Its string example returns the first character in the high byte of the first register. Check a known value (for example Common_SID, which should read 0x53756E53) against your master's word order setting.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

161 registers
Manual Wire Register Type Regs Unit Scale Access Area
212 211 Delete stored ratings of the current inverterF_Delete_Data · Write 0xFFFF to delete the stored ratings of the inverter currently communicating. uint16 1 1 RW Holding (FC03)
213 212 Store ratings of all inverters persistentlyF_Store_Data · Write 0xFFFF to store the rating data of all inverters on the Datamanager. uint16 1 1 RW Holding (FC03)
214 213 Active inverter state codeF_Active_State_Code · Not supported for Fronius Hybrid inverters, so the reported status may differ at night. uint16 1 1 R Holding (FC03)
215 214 Reset all event flags and active state codeF_Reset_All_Event_Flags · Write 0xFFFF to clear the event flags and the active state code. uint16 1 1 RW Holding (FC03)
216 215 SunSpec model type (float or integer with scale factors)F_ModelType · 1 = floating point (models 111 to 113 and 211 to 213), 2 = integer with scale factors (101 to 103 and 201 to 203). Write 1 or 2, then immediately write 6 to the same register to confirm; otherwise the change reverts after a few seconds. Changing it moves the addresses of all models after the common block. uint16 1 1 RW Holding (FC03)
217 216 Storage restrictions view mode (model 124)F_Storage_Restrictions_View_Mode · 0 = local restrictions (set through the Modbus interface, default), 1 = global restrictions. The table text is cut short after "Global restrictions are those". uint16 1 1 RW Holding (FC03)
500 499 Site power, sum of all connected invertersF_Site_Power · Value is in W and needs no scale factor. uint32 2 W 1 R Holding (FC03)
502 501 Site energy for the current dayF_Site_Energy_Day · Value is in Wh and needs no scale factor. uint64 4 Wh 1 R Holding (FC03)
506 505 Site energy for the last yearF_Site_Energy_Year · Value is in Wh and needs no scale factor. uint64 4 Wh 1 R Holding (FC03)
510 509 Site total energyF_Site_Energy_Total · Value is in Wh and needs no scale factor. uint64 4 Wh 1 R Holding (FC03)
40001 40000 SunSpec identifier "SunS"Common_SID · Fixed value 0x53756E53 ("SunS"). uint32 2 1 R Holding (FC03)
40003 40002 Common model identifierCommon_ID · Fixed value 1. uint16 1 1 R Holding (FC03)
40004 40003 Common model lengthCommon_L · Fixed value 65. uint16 1 1 R Holding (FC03)
40005 40004 ManufacturerCommon_Mn · Reads "Fronius". string 16 1 R Holding (FC03)
40021 40020 Device modelCommon_Md · Device model, for example IG+150V. string 16 1 R Holding (FC03)
40037 40036 Options (Datamanager firmware version)Common_Opt · Contains the firmware version of the Datamanager. string 8 1 R Holding (FC03)
40045 40044 Inverter software versionCommon_Vr string 8 1 R Holding (FC03)
40053 40052 Inverter serial numberCommon_SN · Not supported on all devices; depends on the inverter controller production date. string 16 1 R Holding (FC03)
40069 40068 Modbus device addressCommon_DA · Range 1 to 247. uint16 1 1 R Holding (FC03)
40070 40069 Inverter model identifier (111, 112 or 113)Inv_ID · 111 = single phase, 112 = split phase, 113 = three phase. uint16 1 1 R Holding (FC03)
40071 40070 Inverter model lengthInv_L · Fixed value 60. uint16 1 1 R Holding (FC03)
40072 40071 AC total currentInv_A float32 2 A 1 R Holding (FC03)
40074 40073 AC phase A currentInv_AphA float32 2 A 1 R Holding (FC03)
40076 40075 AC phase B currentInv_AphB float32 2 A 1 R Holding (FC03)
40078 40077 AC phase C currentInv_AphC float32 2 A 1 R Holding (FC03)
40080 40079 AC voltage phase A to BInv_PPVphAB float32 2 V 1 R Holding (FC03)
40082 40081 AC voltage phase B to CInv_PPVphBC float32 2 V 1 R Holding (FC03)
40084 40083 AC voltage phase C to AInv_PPVphCA float32 2 V 1 R Holding (FC03)
40086 40085 AC voltage phase A to neutralInv_PhVphA float32 2 V 1 R Holding (FC03)
40088 40087 AC voltage phase B to neutralInv_PhVphB float32 2 V 1 R Holding (FC03)
40090 40089 AC voltage phase C to neutralInv_PhVphC float32 2 V 1 R Holding (FC03)
40092 40091 AC powerInv_W float32 2 W 1 R Holding (FC03)
40094 40093 AC frequencyInv_Hz float32 2 Hz 1 R Holding (FC03)
40096 40095 AC apparent powerInv_VA float32 2 VA 1 R Holding (FC03)
40098 40097 AC reactive powerInv_VAr float32 2 VAr 1 R Holding (FC03)
40100 40099 AC power factorInv_PF · The table gives the unit as %. float32 2 % 1 R Holding (FC03)
40102 40101 AC lifetime energy productionInv_WH · The table notes the value may be imprecise. float32 2 Wh 1 R Holding (FC03)
40104 40103 DC currentInv_DCA · Not supported if the inverter has multiple DC inputs; use the multiple MPPT model instead. float32 2 A 1 R Holding (FC03)
40106 40105 DC voltageInv_DCV · Not supported if the inverter has multiple DC inputs; use the multiple MPPT model instead. float32 2 V 1 R Holding (FC03)
40108 40107 DC power, total of all DC inputsInv_DCW · Total power of all DC inputs. float32 2 W 1 R Holding (FC03)
40118 40117 Operating stateInv_St · The manual lists SunSpec operating codes: 1 off, 2 sleeping (auto shutdown), 3 starting, 4 MPPT (working normally), 5 throttled (power reduction active), 6 shutting down, 7 fault, 8 standby. uint16 1 1 R Holding (FC03)
40119 40118 Vendor defined operating stateInv_StVnd · The manual lists Fronius operating codes: 1 to 8 as for St, then 9 no SolarNet communication, 10 no communication with inverter, 11 overcurrent on SolarNet plug, 12 bootloader (inverter being updated), 13 AFCI event. uint16 1 1 R Holding (FC03)
40120 40119 Event flags, bits 0 to 31Inv_Evt1 · Bit field; event lists are in the downloadable Fronius state codes and events files. uint32 2 1 R Holding (FC03)
40122 40121 Event flags, bits 32 to 63Inv_Evt2 · Bit field; event lists are in the downloadable Fronius state codes and events files. uint32 2 1 R Holding (FC03)
40124 40123 Vendor defined event flags, bits 0 to 31Inv_EvtVnd1 · Bit field; event lists are in the downloadable Fronius state codes and events files. uint32 2 1 R Holding (FC03)
40126 40125 Vendor defined event flags, bits 32 to 63Inv_EvtVnd2 · Bit field; event lists are in the downloadable Fronius state codes and events files. uint32 2 1 R Holding (FC03)
40128 40127 Vendor defined event flags, bits 64 to 95Inv_EvtVnd3 · Bit field; event lists are in the downloadable Fronius state codes and events files. uint32 2 1 R Holding (FC03)
40130 40129 Vendor defined event flags, bits 96 to 127Inv_EvtVnd4 · Bit field; event lists are in the downloadable Fronius state codes and events files. uint32 2 1 R Holding (FC03)
40132 40131 Nameplate model identifierNameplate_ID · Fixed value 120. uint16 1 1 R Holding (FC03)
40133 40132 Nameplate model lengthNameplate_L · Fixed value 26. uint16 1 1 R Holding (FC03)
40134 40133 DER device typeNameplate_DERTyp · Value 4 means PV device. uint16 1 1 R Holding (FC03)
40135 40134 Rated continuous power outputNameplate_WRtg uint16 1 W 1 R Holding (FC03)
40136 40135 Scale factor WRtg_SFNameplate_WRtg_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40137 40136 Rated continuous apparent powerNameplate_VARtg uint16 1 VA 1 R Holding (FC03)
40138 40137 Scale factor VARtg_SFNameplate_VARtg_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40139 40138 Rated reactive power, quadrant 1Nameplate_VArRtgQ1 · Quadrants 2 and 3 are not supported. int16 1 var 10 R Holding (FC03)
40142 40141 Rated reactive power, quadrant 4Nameplate_VArRtgQ4 · Quadrants 2 and 3 are not supported. int16 1 var 10 R Holding (FC03)
40143 40142 Scale factor VArRtg_SFNameplate_VArRtg_SF · Table gives constant 1; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40144 40143 Rated maximum RMS AC currentNameplate_ARtg uint16 1 A 0.01 R Holding (FC03)
40145 40144 Scale factor ARtg_SFNameplate_ARtg_SF · Table gives constant -2; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40146 40145 Minimum power factor, quadrant 1Nameplate_PFRtgQ1 · Unit cos(). Quadrants 2 and 3 are not supported. int16 1 0.001 R Holding (FC03)
40149 40148 Minimum power factor, quadrant 4Nameplate_PFRtgQ4 · Unit cos(). Quadrants 2 and 3 are not supported. int16 1 0.001 R Holding (FC03)
40150 40149 Scale factor PFRtg_SFNameplate_PFRtg_SF · Table gives constant -3; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40151 40150 Nominal energy rating of storage deviceNameplate_WHRtg uint16 1 Wh 1 R Holding (FC03)
40152 40151 Scale factor WHRtg_SFNameplate_WHRtg_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40155 40154 Maximum charge rate of storage deviceNameplate_MaxChaRte uint16 1 W 1 R Holding (FC03)
40156 40155 Scale factor MaxChaRte_SFNameplate_MaxChaRte_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40157 40156 Maximum discharge rate of storage deviceNameplate_MaxDisChaRte uint16 1 W 1 R Holding (FC03)
40158 40157 Scale factor MaxDisChaRte_SFNameplate_MaxDisChaRte_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40160 40159 Basic settings model identifierSettings_ID · Fixed value 121. uint16 1 1 R Holding (FC03)
40161 40160 Basic settings model lengthSettings_L · Fixed value 30. uint16 1 1 R Holding (FC03)
40162 40161 Maximum power output settingSettings_WMax · Defaults to the rated power WRtg. uint16 1 W 10 RW Holding (FC03)
40163 40162 Reference voltage at the point of common couplingSettings_VRef · Read-only in this table. uint16 1 V 1 R Holding (FC03)
40164 40163 Voltage offset from point of common coupling to inverterSettings_VRefOfs int16 1 V 1 RW Holding (FC03)
40167 40166 Maximum apparent power setpointSettings_VAMax · The table lists this as RW but gives only function code 0x03. uint16 1 VA 10 R Holding (FC03)
40168 40167 Maximum reactive power setting, quadrant 1Settings_VARMaxQ1 · Defaults to VArRtgQ1. int16 1 var 10 R Holding (FC03)
40171 40170 Maximum reactive power setting, quadrant 4Settings_VARMaxQ4 · Defaults to VArRtgQ4. int16 1 var 10 R Holding (FC03)
40173 40172 Minimum power factor setpoint, quadrant 1Settings_PFMinQ1 · Unit cos(). Defaults to PFRtgQ1. int16 1 0.001 R Holding (FC03)
40176 40175 Minimum power factor setpoint, quadrant 4Settings_PFMinQ4 · Unit cos(). Defaults to PFRtgQ4. int16 1 0.001 R Holding (FC03)
40182 40181 Scale factor WMax_SFSettings_WMax_SF · Table gives constant 1; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40183 40182 Scale factor VRef_SFSettings_VRef_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40184 40183 Scale factor VRefOfs_SFSettings_VRefOfs_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40186 40185 Scale factor VAMax_SFSettings_VAMax_SF · Table gives constant 1; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40187 40186 Scale factor VARMax_SFSettings_VARMax_SF · Table gives constant 1; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40189 40188 Scale factor PFMin_SFSettings_PFMin_SF · Table gives constant -3; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40192 40191 Extended measurements model identifierExtMeas_ID · Fixed value 122. uint16 1 1 R Holding (FC03)
40193 40192 Extended measurements model lengthExtMeas_L · Fixed value 44. uint16 1 1 R Holding (FC03)
40194 40193 PV inverter connection statusExtMeas_PVConn · Bit 0 connected, bit 1 available, bit 2 operating, bit 3 test. bitfield16 1 1 R Holding (FC03)
40195 40194 Storage inverter connection statusExtMeas_StorConn · Bit 0 connected, bit 1 available, bit 2 operating, bit 3 test. bitfield16 1 1 R Holding (FC03)
40196 40195 Grid connection statusExtMeas_ECPConn · 0 = disconnected, 1 = connected. bitfield16 1 1 R Holding (FC03)
40197 40196 AC lifetime active energy outputExtMeas_ActWh · Unit Wh. uint64 4 Wh 1 R Holding (FC03)
40227 40226 Active inverter controlsExtMeas_StActCtl · Bit 0 FixedW (power reduction), bit 1 FixedVAR, bit 2 FixedPF. uint32 2 1 R Holding (FC03)
40229 40228 Time synchronization sourceExtMeas_TmSrc · Returns the string "RTC". string 4 1 R Holding (FC03)
40233 40232 Inverter clock, seconds since 2000-01-01 00:00 UTCExtMeas_Tms · Seconds since 2000-01-01 00:00 UTC. uint32 2 s 1 R Holding (FC03)
40238 40237 Immediate controls model identifierCtl_ID · Fixed value 123. uint16 1 1 R Holding (FC03)
40239 40238 Immediate controls model lengthCtl_L · Fixed value 24. uint16 1 1 R Holding (FC03)
40240 40239 Connect or disconnect time windowCtl_Conn_WinTms · Standby control timing; default 0. uint16 1 s 1 RW Holding (FC03)
40241 40240 Connect or disconnect timeoutCtl_Conn_RvrtTms · Standby control timing; default 0. uint16 1 s 1 RW Holding (FC03)
40242 40241 Connection control (standby or grid feed)Ctl_Conn · Write 0 to switch the inverter to standby (no grid feed), write 1 to reactivate. Needs "Inverter control via Modbus" enabled in the Datamanager Modbus settings. bitfield16 1 1 RW Holding (FC03)
40243 40242 Power output limitCtl_WMaxLimPct · Power limit in percent of WMax. The manual says values below 10 may force standby depending on software version. Enter the value, then start the mode with WMaxLim_Ena; to change an active limit, rewrite the value and restart with WMaxLim_Ena. uint16 1 % 0.01 RW Holding (FC03)
40244 40243 Power limit time windowCtl_WMaxLimPct_WinTms · Range 0 to 300 s; default 0. uint16 1 s 1 RW Holding (FC03)
40245 40244 Power limit timeoutCtl_WMaxLimPct_RvrtTms · Range 0 to 28800 s; 0 keeps the mode active until disabled. uint16 1 s 1 RW Holding (FC03)
40246 40245 Power limit ramp timeCtl_WMaxLimPct_RmpTms · The table lists RW with only function code 0x03; the manual says writes to this register are ignored without an exception. Range 0 to 65534 s. uint16 1 s 1 R Holding (FC03)
40247 40246 Power limit enableCtl_WMaxLim_Ena · 0 = disabled, 1 = enabled. uint16 1 1 RW Holding (FC03)
40248 40247 Constant power factor setpointCtl_OutPFSet · Valid range 0.8 to 1.0 and -0.8 to -0.999. Sign convention in the manual: positive is under-excited, negative is over-excited. Enable with OutPFSet_Ena. int16 1 0.001 RW Holding (FC03)
40249 40248 Power factor time windowCtl_OutPFSet_WinTms · Range 0 to 300 s. uint16 1 s 1 RW Holding (FC03)
40250 40249 Power factor timeoutCtl_OutPFSet_RvrtTms · Range 0 to 28800 s. uint16 1 s 1 RW Holding (FC03)
40251 40250 Power factor ramp timeCtl_OutPFSet_RmpTms · Range 0 to 65534 s. uint16 1 s 1 RW Holding (FC03)
40252 40251 Constant power factor enableCtl_OutPFSet_Ena · 0 = disabled, 1 = enabled. uint16 1 1 RW Holding (FC03)
40254 40253 Constant reactive power setpointCtl_VArMaxPct · Reactive power as a percentage of VArMax. Enable with VArPct_Ena. int16 1 % 1 RW Holding (FC03)
40256 40255 Reactive power time windowCtl_VArPct_WinTms · Range 0 to 300 s. uint16 1 s 1 RW Holding (FC03)
40257 40256 Reactive power timeoutCtl_VArPct_RvrtTms · Range 0 to 28800 s. uint16 1 s 1 RW Holding (FC03)
40258 40257 Reactive power ramp timeCtl_VArPct_RmpTms · Range 0 to 65534 s. uint16 1 s 1 RW Holding (FC03)
40259 40258 Reactive power limit modeCtl_VArPct_Mod · Value 2 = VAR limit as a percentage of VArMax. Cannot be changed. uint16 1 1 R Holding (FC03)
40260 40259 Constant reactive power enableCtl_VArPct_Ena · 0 = disabled, 1 = enabled. uint16 1 1 RW Holding (FC03)
40261 40260 Scale factor WMaxLimPct_SFCtl_WMaxLimPct_SF · Table gives constant -2; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40262 40261 Scale factor OutPFSet_SFCtl_OutPFSet_SF · Table gives constant -3; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40263 40262 Scale factor VArPct_SFCtl_VArPct_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40264 40263 Multiple MPPT model identifierMPPT_ID · Fixed value 160. uint16 1 1 R Holding (FC03)
40265 40264 Multiple MPPT model lengthMPPT_L · Fixed value 48. uint16 1 1 R Holding (FC03)
40266 40265 DC current scale factorMPPT_DCA_SF · Apply as 10 to the power of this value to the DC current registers. The table gives no constant. int16 1 1 R Holding (FC03)
40267 40266 DC voltage scale factorMPPT_DCV_SF · Apply as 10 to the power of this value to the DC voltage registers. The table gives no constant. int16 1 1 R Holding (FC03)
40268 40267 DC power scale factorMPPT_DCW_SF · Apply as 10 to the power of this value to the DC power registers. The table gives no constant. int16 1 1 R Holding (FC03)
40269 40268 DC energy scale factorMPPT_DCWH_SF · Not supported for Fronius Hybrid inverters. int16 1 1 R Holding (FC03)
40270 40269 Global eventsMPPT_Evt · Bit field. uint32 2 1 R Holding (FC03)
40272 40271 Number of DC inputsMPPT_N · Table value 2. uint16 1 1 R Holding (FC03)
40274 40273 DC input 1 identifierMPPT_Input1_ID · Table value 1. uint16 1 1 R Holding (FC03)
40275 40274 DC input 1 labelMPPT_Input1_IDStr · Reads "String 1". string 8 1 R Holding (FC03)
40283 40282 DC input 1 currentMPPT_Input1_DCA · Multiply by 10 to the power of DCA_SF (40266). In hybrid systems input 1 is the PV input. uint16 1 A 1 R Holding (FC03)
40284 40283 DC input 1 voltageMPPT_Input1_DCV · Multiply by 10 to the power of DCV_SF (40267). uint16 1 V 1 R Holding (FC03)
40285 40284 DC input 1 powerMPPT_Input1_DCW · Multiply by 10 to the power of DCW_SF (40268). uint16 1 W 1 R Holding (FC03)
40286 40285 DC input 1 lifetime energyMPPT_Input1_DCWH · Multiply by 10 to the power of DCWH_SF (40269). Not supported for Fronius Hybrid inverters. uint32 2 Wh 1 R Holding (FC03)
40288 40287 DC input 1 timestampMPPT_Input1_Tms · Seconds since 2000-01-01 00:00 UTC. uint32 2 s 1 R Holding (FC03)
40291 40290 DC input 1 operating stateMPPT_Input1_DCSt · Operating state of DC input 1. uint16 1 1 R Holding (FC03)
40294 40293 DC input 2 identifierMPPT_Input2_ID · Table value 2. uint16 1 1 R Holding (FC03)
40295 40294 DC input 2 labelMPPT_Input2_IDStr · Reads "String 2", or "Not supported" if there is only one DC input. string 8 1 R Holding (FC03)
40303 40302 DC input 2 currentMPPT_Input2_DCA · Multiply by 10 to the power of DCA_SF (40266). Not supported if only one DC input. In hybrid systems input 2 is the storage; only the absolute value is shown. uint16 1 A 1 R Holding (FC03)
40304 40303 DC input 2 voltageMPPT_Input2_DCV · Multiply by 10 to the power of DCV_SF (40267). Not supported if only one DC input. uint16 1 V 1 R Holding (FC03)
40305 40304 DC input 2 powerMPPT_Input2_DCW · Multiply by 10 to the power of DCW_SF (40268). Not supported if only one DC input. In hybrid systems only the absolute value of the storage power is shown. uint16 1 W 1 R Holding (FC03)
40306 40305 DC input 2 lifetime energyMPPT_Input2_DCWH · Multiply by 10 to the power of DCWH_SF (40269). Not supported if only one DC input or on Fronius Hybrid inverters. uint32 2 Wh 1 R Holding (FC03)
40308 40307 DC input 2 timestampMPPT_Input2_Tms · Seconds since 2000-01-01 00:00 UTC. Not supported if only one DC input. uint32 2 s 1 R Holding (FC03)
40311 40310 DC input 2 operating stateMPPT_Input2_DCSt · Operating state of DC input 2. Not supported if only one DC input. uint16 1 1 R Holding (FC03)
40314 40313 Basic storage controls model identifierStor_ID · Fixed value 124. Model 124 is only available on inverters with a storage solution; without it the end block starts at 40314 (the manual gives 40313 as its start address with offsets from 1). uint16 1 1 R Holding (FC03)
40315 40314 Basic storage controls model lengthStor_L · Fixed value 24. uint16 1 1 R Holding (FC03)
40316 40315 Reference value for maximum charge and discharge powerStor_WchaMax · Reference value for the InWRte and OutWRte percentages: max(MaxChaRte, MaxDisChaRte). Value 0 if there is no storage. uint16 1 W 1 R Holding (FC03)
40317 40316 Maximum charging rate setpointStor_WchaGra · The table range column gives 100. uint16 1 %/s 1 R Holding (FC03)
40318 40317 Maximum discharge rate setpointStor_WdisChaGra · The table range column gives 100. uint16 1 %/s 1 R Holding (FC03)
40319 40318 Storage control modeStor_StorCtl_Mod · Bit 0 activates the charge limit (InWRte), bit 1 activates the discharge limit (OutWRte); value 3 activates both. Needs "Inverter control via Modbus" enabled. bitfield16 1 1 RW Holding (FC03)
40321 40320 Minimum reserve for storageStor_MinRsvPct · Minimum state of charge reserve; setting it can show as "Energy saving mode" in Fronius Solar.web. uint16 1 % 0.01 RW Holding (FC03)
40322 40321 Storage state of chargeStor_ChaState · Storage charge level in percent. Table unit is "% AhrRtg". uint16 1 % 0.01 R Holding (FC03)
40325 40324 Storage charge statusStor_ChaSt · 1 OFF, 2 EMPTY, 3 DISCHARGING, 4 CHARGING, 5 FULL, 6 HOLDING, 7 TESTING (used during calibration or service charge). uint16 1 1 R Holding (FC03)
40326 40325 Discharge rate limitStor_OutWRte · Percent of WChaMax; valid range -100.00 to +100.00 percent (raw -10000 to 10000 at scale factor -2). The manual p. 92-94 gives worked power window examples; StorCtl_Mod = 2 activates this limit. int16 1 % 0.01 RW Holding (FC03)
40327 40326 Charge rate limitStor_InWRte · Percent of WChaMax; valid range -100.00 to +100.00 percent (raw -10000 to 10000 at scale factor -2). The manual p. 92-94 gives worked power window examples; StorCtl_Mod = 1 activates this limit. int16 1 % 0.01 RW Holding (FC03)
40331 40330 Charging from grid setpointStor_ChaGriSet · 0 = PV only (grid charging disabled), 1 = grid charging enabled. Combined with the "battery charging from DNO grid" setting in Fronius system monitoring. uint16 1 1 RW Holding (FC03)
40332 40331 Scale factor WchaMax_SFStor_WchaMax_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40333 40332 Scale factor WchaDisChaGra_SFStor_WchaDisChaGra_SF · Table gives constant 0; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40335 40334 Scale factor MinRsvPct_SFStor_MinRsvPct_SF · Table gives constant -2; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40336 40335 Scale factor ChaState_SFStor_ChaState_SF · Table gives constant -2; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40339 40338 Scale factor InOutWRte_SFStor_InOutWRte_SF · Table gives constant -2; the manual says scale factors can change with firmware, so read it. int16 1 1 R Holding (FC03)
40340 40339 End block identifierEnd_ID · Fixed value 0xFFFF. uint16 1 1 R Holding (FC03)
40341 40340 End block lengthEnd_L · Fixed value 0. uint16 1 1 R Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: Fronius Datamanager Modbus TCP & RTU, Operating Instructions (www.fronius.com)

Document 42,0410,2049, edition 031-14062024 (English US section). Checked against the copy of that vendor URL archived at web.archive.org on 2024-07-10; the live vendor URL returned HTTP 404 on 2026-10-24, so a newer edition could not be checked., p. 62-63, 66-67, 72-75, 77-83, 91-94 (English section, edition 031-14062024). The manual contains no register tables for these models; the rows come from the Fronius register map archive (Inverter float map xlsx, Complete Map sheet).. Read on 2026-10-24.

Also used: Fronius Modbus SunSpec Maps, State Codes and Events (register map archive, version 1.1.7-0) (www.fronius.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.