Carlo Gavazzi EM24 DIN (PFA, PFB and X models) Modbus register map

Three phase DIN rail energy analyzer with an RS485 Modbus RTU port. The map covers phase and system voltage, current, power, power factor, frequency, four-tariff energy counters, digital input counters, demand values and setup.

Protocol
Modbus RTU
Defaults
The document fixes the serial format at no parity and one stop bit, with 4800 or 9600 baud selectable. It does not state a default address or baud rate.
Addresses in the manual
Modicon style numbers (for example 40001 is holding register 0)
32 and 64-bit values
Low word first (CD AB)
Registers listed
78
Checked against
EM24-DIN PFA, PFB & X models Communication Protocol, Version 4 Revision 0 (December 03, 2012)

Address base. Each variable is printed as a 6-digit Modicom number for function 04 (for example 300001) beside the physical word address (0000h). Wire address equals the printed number minus 300001. Function 03 reads the same data when the leading 3 is replaced by 4 (p. 3). Writable settings are printed as 3043xx and similar; address them as holding registers. For example 300001 in the manual (Phase 1 line to neutral voltage) is address 0 on the wire.

Word order. 32-bit values are sent least significant word first, with MSB first inside each word (p. 7).

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

78 registers
Manual Wire Register Type Regs Unit Scale Access Area
300001 0 Phase 1 line to neutral voltageVoltage_L1N int32 2 V 0.1 R Input (FC04)
300003 2 Phase 2 line to neutral voltageVoltage_L2N int32 2 V 0.1 R Input (FC04)
300005 4 Phase 3 line to neutral voltageVoltage_L3N int32 2 V 0.1 R Input (FC04)
300007 6 Line 1 to line 2 voltageVoltage_L1L2 int32 2 V 0.1 R Input (FC04)
300009 8 Line 2 to line 3 voltageVoltage_L2L3 int32 2 V 0.1 R Input (FC04)
300011 10 Line 3 to line 1 voltageVoltage_L3L1 int32 2 V 0.1 R Input (FC04)
300013 12 Phase 1 currentCurrent_L1 int32 2 A 0.001 R Input (FC04)
300015 14 Phase 2 currentCurrent_L2 int32 2 A 0.001 R Input (FC04)
300017 16 Phase 3 currentCurrent_L3 int32 2 A 0.001 R Input (FC04)
300019 18 Phase 1 active powerActivePower_L1 int32 2 W 0.1 R Input (FC04)
300021 20 Phase 2 active powerActivePower_L2 int32 2 W 0.1 R Input (FC04)
300023 22 Phase 3 active powerActivePower_L3 int32 2 W 0.1 R Input (FC04)
300025 24 Phase 1 apparent powerApparentPower_L1 int32 2 VA 0.1 R Input (FC04)
300027 26 Phase 2 apparent powerApparentPower_L2 int32 2 VA 0.1 R Input (FC04)
300029 28 Phase 3 apparent powerApparentPower_L3 int32 2 VA 0.1 R Input (FC04)
300031 30 Phase 1 reactive powerReactivePower_L1 int32 2 var 0.1 R Input (FC04)
300033 32 Phase 2 reactive powerReactivePower_L2 int32 2 var 0.1 R Input (FC04)
300035 34 Phase 3 reactive powerReactivePower_L3 int32 2 var 0.1 R Input (FC04)
300037 36 System line to neutral voltageVoltageLN_Sys int32 2 V 0.1 R Input (FC04)
300039 38 System line to line voltageVoltageLL_Sys int32 2 V 0.1 R Input (FC04)
300041 40 System active powerActivePower_Sys int32 2 W 0.1 R Input (FC04)
300043 42 System apparent powerApparentPower_Sys int32 2 VA 0.1 R Input (FC04)
300045 44 System reactive powerReactivePower_Sys int32 2 var 0.1 R Input (FC04)
300047 46 System active power demandPowerDemand_Sys int32 2 W 0.1 R Input (FC04)
300049 48 System apparent power demandApparentDemand_Sys int32 2 VA 0.1 R Input (FC04)
300051 50 Phase 1 power factorPowerFactor_L1 · Negative values mean leading (capacitive), positive values mean lagging. int16 1 0.001 R Input (FC04)
300052 51 Phase 2 power factorPowerFactor_L2 int16 1 0.001 R Input (FC04)
300053 52 Phase 3 power factorPowerFactor_L3 int16 1 0.001 R Input (FC04)
300054 53 System power factorPowerFactor_Sys int16 1 0.001 R Input (FC04)
300055 54 Phase sequencePhaseSequence · -1 means L1-L3-L2 order, 0 means L1-L2-L3 order. Meaningful only on 3-phase systems. int16 1 1 R Input (FC04)
300056 55 FrequencyFrequency int16 1 Hz 0.1 R Input (FC04)
300057 56 Maximum system active power demandPowerDemandMax int32 2 W 0.1 R Input (FC04)
300059 58 Maximum system apparent power demandApparentDemandMax int32 2 VA 0.1 R Input (FC04)
300061 60 Maximum current demandCurrentDemandMax int32 2 A 0.001 R Input (FC04)
300063 62 Total imported active energyEnergyImport_kWh int32 2 kWh 0.1 R Input (FC04)
300065 64 Total imported reactive energyEnergyImport_kvarh int32 2 kvarh 0.1 R Input (FC04)
300067 66 Partial imported active energyEnergyImportPartial_kWh int32 2 kWh 0.1 R Input (FC04)
300069 68 Partial imported reactive energyEnergyImportPartial_kvarh int32 2 kvarh 0.1 R Input (FC04)
300071 70 Phase 1 imported active energyEnergyImport_kWh_L1 int32 2 kWh 0.1 R Input (FC04)
300073 72 Phase 2 imported active energyEnergyImport_kWh_L2 int32 2 kWh 0.1 R Input (FC04)
300075 74 Phase 3 imported active energyEnergyImport_kWh_L3 int32 2 kWh 0.1 R Input (FC04)
300077 76 Imported active energy, tariff 1EnergyImport_kWh_T1 int32 2 kWh 0.1 R Input (FC04)
300079 78 Imported active energy, tariff 2EnergyImport_kWh_T2 int32 2 kWh 0.1 R Input (FC04)
300081 80 Imported active energy, tariff 3EnergyImport_kWh_T3 int32 2 kWh 0.1 R Input (FC04)
300083 82 Imported active energy, tariff 4EnergyImport_kWh_T4 int32 2 kWh 0.1 R Input (FC04)
300085 84 Imported reactive energy, tariff 1EnergyImport_kvarh_T1 int32 2 kvarh 0.1 R Input (FC04)
300087 86 Imported reactive energy, tariff 2EnergyImport_kvarh_T2 int32 2 kvarh 0.1 R Input (FC04)
300089 88 Imported reactive energy, tariff 3EnergyImport_kvarh_T3 int32 2 kvarh 0.1 R Input (FC04)
300091 90 Imported reactive energy, tariff 4EnergyImport_kvarh_T4 int32 2 kvarh 0.1 R Input (FC04)
300093 92 Total exported active energyEnergyExport_kWh int32 2 kWh 0.1 R Input (FC04)
300095 94 Total exported reactive energyEnergyExport_kvarh int32 2 kvarh 0.1 R Input (FC04)
300097 96 Hour counterRunHours int32 2 h 0.01 R Input (FC04)
300099 98 Digital input counter 1Counter1 · Weight is 0.1, 0.01 or 0.001 of the engineering unit depending on the digital input format setting (registers 304404 to 304406). int32 2 1 R Input (FC04)
300101 100 Digital input counter 2Counter2 int32 2 1 R Input (FC04)
300103 102 Digital input counter 3Counter3 int32 2 1 R Input (FC04)
300769 768 Digital input statusDigitalInputStatus · Bit 0 to bit 2 give the state of channels 1 to 3. A bit value of 0 means the input is closed and 1 means open. bitfield16 1 1 R Input (FC04)
300770 769 Current tariffCurrentTariff · 0 = tariff 1, 1 = tariff 2, 2 = tariff 3, 3 = tariff 4. uint16 1 1 R Input (FC04)
300771 770 Model version codeVersionCode · The value identifies the exact model variant (PFA, PFB or X, and input option); the mapping is listed in table 2.6-1. uint16 1 1 R Input (FC04)
300772 771 Revision codeRevisionCode uint16 1 1 R Input (FC04)
300773 772 Front selector statusFrontSelector · 3 = keypad locked; 0, 1 or 2 = keypad unlocked. uint16 1 1 R Input (FC04)
300012 11 Carlo Gavazzi identification codeProductCode · 71 for AV9 and AV2 input products, 72 for AV5, 73 for AV6. uint16 1 1 R Input (FC04)
304353 4352 Programming passwordPassword · 0 to 9999; out of range counts as 0. uint16 1 1 RW Holding (FC03)
304354 4353 Application typeApplicationType · 0 to 7 selects application A to H. A, B, C, G are PFA only; E, F, H are PFB only; all are available on X models. uint16 1 1 RW Holding (FC03)
304355 4354 Measuring systemMeasuringSystem · 0 = 3Pn, 1 = 3P1, 2 = 2P, 3 = 1P, 4 = 3P. PFA and PFB models support only 3Pn. uint16 1 1 RW Holding (FC03)
304356 4355 Demand integration timeDemandIntervalTime · 1 to 30. uint16 1 1 RW Holding (FC03)
304361 4360 Filter spanFilterSpan · 0 to 100. uint16 1 1 RW Holding (FC03)
304362 4361 Filter coefficientFilterCoefficient · 1 to 32. uint16 1 1 RW Holding (FC03)
304363 4362 RS485 instrument addressModbusAddress · 1 to 247. uint16 1 1 RW Holding (FC03)
304364 4363 RS485 baud rateBaudRate · 0 = 4800, 1 = 9600. Stop bits fixed at 1 and parity fixed at none. uint16 1 1 RW Holding (FC03)
304397 4396 Current transformer ratioCT_Ratio · Raw 10 to 600000 means CT ratio 1.0 to 60000.0. uint32 2 0.1 RW Holding (FC03)
304399 4398 Voltage transformer ratioVT_Ratio · Raw 10 to 60000 means VT ratio 1.0 to 6000.0. uint32 2 0.1 RW Holding (FC03)
304872 4871 Instrument secondary addressSecondaryAddress uint32 2 1 R Holding (FC03)
312289 12288 Reset all meters (hour counter excluded)ResetAll · Write 1 to execute; any other value has no effect. uint16 1 1 W Holding (FC03)
312290 12289 Reset total meters (hour counter excluded)ResetTotals · Write 1 to execute; any other value has no effect. uint16 1 1 W Holding (FC03)
312291 12290 Reset partial metersResetPartials · Write 1 to execute; any other value has no effect. uint16 1 1 W Holding (FC03)
312292 12291 Reset hour counterResetHourCounter · Write 1 to execute; any other value has no effect. uint16 1 1 W Holding (FC03)
312293 12292 Reset counters 1 to 3ResetCounters · Write 1 to execute; any other value has no effect. uint16 1 1 W Holding (FC03)
312294 12293 Reset maximum demand valuesResetDemandMax · Write 1 to execute; any other value has no effect. uint16 1 1 W Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to CD AB.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: EM24-DIN PFA, PFB and X models Communication Protocol (www.gavazziautomation.com)

EM24-DIN PFA, PFB & X models Communication Protocol, Version 4 Revision 0 (December 03, 2012), pp. 3-13. Read on 2026-10-24.

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.