Carlo Gavazzi EM210 (PFA and PFB models) Modbus register map
Three phase DIN rail energy meter with an RS485 Modbus RTU port. The map covers phase and system voltage, current, power, power factor, frequency, import and export energy and the serial and transformer settings.
- Protocol
- Modbus RTU
- Defaults
- Per the protocol document: 9.6 kbps, no parity, one stop bit; the default instrument address is not stated.
- Addresses in the manual
- Modicon style numbers (for example 40001 is holding register 0)
- 32 and 64-bit values
- Low word first (CD AB)
- Registers listed
- 50
- Checked against
- EM210 Communication Protocol, Version 4 Revision 3 (October 30th, 2019)
Address base. Each variable is printed as a 6-digit Modicom number for function 04 (for example 300001) beside the physical word address (0000h). Wire address equals the printed number minus 300001. Function 03 reads the same data with the leading 3 replaced by 4 (p. 3). Writable settings are printed as 3040xx and similar; address them as holding registers. For example 300001 in the manual (Phase 1 line to neutral voltage) is address 0 on the wire.
Word order. 32-bit values are sent least significant word first, with MSB first inside each word (p. 7).
Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.
Downloads
The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.
Registers
| Manual | Wire | Register | Type | Regs | Unit | Scale | Access | Area |
|---|---|---|---|---|---|---|---|---|
| 300001 | 0 | Phase 1 line to neutral voltageVoltage_L1N |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300003 | 2 | Phase 2 line to neutral voltageVoltage_L2N |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300005 | 4 | Phase 3 line to neutral voltageVoltage_L3N |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300007 | 6 | Line 1 to line 2 voltageVoltage_L1L2 |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300009 | 8 | Line 2 to line 3 voltageVoltage_L2L3 |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300011 | 10 | Line 3 to line 1 voltageVoltage_L3L1 |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300013 | 12 | Phase 1 currentCurrent_L1 |
int32 | 2 | A | 0.001 | R | Input (FC04) |
| 300015 | 14 | Phase 2 currentCurrent_L2 |
int32 | 2 | A | 0.001 | R | Input (FC04) |
| 300017 | 16 | Phase 3 currentCurrent_L3 |
int32 | 2 | A | 0.001 | R | Input (FC04) |
| 300019 | 18 | Phase 1 active powerActivePower_L1 |
int32 | 2 | W | 0.1 | R | Input (FC04) |
| 300021 | 20 | Phase 2 active powerActivePower_L2 |
int32 | 2 | W | 0.1 | R | Input (FC04) |
| 300023 | 22 | Phase 3 active powerActivePower_L3 |
int32 | 2 | W | 0.1 | R | Input (FC04) |
| 300025 | 24 | Phase 1 apparent powerApparentPower_L1 |
int32 | 2 | VA | 0.1 | R | Input (FC04) |
| 300027 | 26 | Phase 2 apparent powerApparentPower_L2 |
int32 | 2 | VA | 0.1 | R | Input (FC04) |
| 300029 | 28 | Phase 3 apparent powerApparentPower_L3 |
int32 | 2 | VA | 0.1 | R | Input (FC04) |
| 300031 | 30 | Phase 1 reactive powerReactivePower_L1 |
int32 | 2 | var | 0.1 | R | Input (FC04) |
| 300033 | 32 | Phase 2 reactive powerReactivePower_L2 |
int32 | 2 | var | 0.1 | R | Input (FC04) |
| 300035 | 34 | Phase 3 reactive powerReactivePower_L3 |
int32 | 2 | var | 0.1 | R | Input (FC04) |
| 300037 | 36 | System line to neutral voltageVoltageLN_Sys |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300039 | 38 | System line to line voltageVoltageLL_Sys |
int32 | 2 | V | 0.1 | R | Input (FC04) |
| 300041 | 40 | System active powerActivePower_Sys |
int32 | 2 | W | 0.1 | R | Input (FC04) |
| 300043 | 42 | System apparent powerApparentPower_Sys |
int32 | 2 | VA | 0.1 | R | Input (FC04) |
| 300045 | 44 | System reactive powerReactivePower_Sys |
int32 | 2 | var | 0.1 | R | Input (FC04) |
| 300047 | 46 | Phase 1 power factorPowerFactor_L1 · Negative values mean exported active power, positive values mean imported. |
int16 | 1 | 0.001 | R | Input (FC04) | |
| 300048 | 47 | Phase 2 power factorPowerFactor_L2 |
int16 | 1 | 0.001 | R | Input (FC04) | |
| 300049 | 48 | Phase 3 power factorPowerFactor_L3 |
int16 | 1 | 0.001 | R | Input (FC04) | |
| 300050 | 49 | System power factorPowerFactor_Sys |
int16 | 1 | 0.001 | R | Input (FC04) | |
| 300051 | 50 | Phase sequencePhaseSequence · 0 = L1-L2-L3 order, 1 = L1-L3-L2 order. Meaningful only on 3-phase systems. |
int16 | 1 | 1 | R | Input (FC04) | |
| 300052 | 51 | FrequencyFrequency · Weight is Hz (no decimals) in this table; the by-phase table (300273) is 32-bit and uses the same Hz weight. |
int16 | 1 | Hz | 1 | R | Input (FC04) |
| 300053 | 52 | Total imported active energyEnergyImport_kWh |
int32 | 2 | kWh | 0.1 | R | Input (FC04) |
| 300055 | 54 | Total imported reactive energyEnergyImport_kvarh |
int32 | 2 | kvarh | 0.1 | R | Input (FC04) |
| 300273 | 272 | Frequency (32-bit copy)Frequency32 |
int32 | 2 | Hz | 1 | R | Input (FC04) |
| 300279 | 278 | Total exported active energyEnergyExport_kWh |
int32 | 2 | kWh | 0.1 | R | Input (FC04) |
| 300771 | 770 | Display version codeDisplayVersionCode · 0 = version A, 2 = version C. |
uint16 | 1 | 1 | R | Input (FC04) | |
| 300772 | 771 | Display revision codeDisplayRevisionCode |
uint16 | 1 | 1 | R | Input (FC04) | |
| 300773 | 772 | Programming lock statusProgrammingLock · 1 = programming locked (rear trimmer position), 0 = unlocked. |
uint16 | 1 | 1 | R | Input (FC04) | |
| 300012 | 11 | Carlo Gavazzi identification codeProductCode · 210 for EM210. |
uint16 | 1 | 1 | R | Input (FC04) | |
| 320488 | 20487 | Instrument production yearProductionYear |
uint16 | 1 | 1 | R | Input (FC04) | |
| 320737 | 20736 | Instrument secondary addressSecondaryAddress · Low word at physical address 5100h, high word at 5101h. |
uint32 | 2 | 1 | R | Input (FC04) | |
| 304097 | 4096 | Programming passwordPassword · 0 to 999, default 0. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 304099 | 4098 | Measuring systemMeasuringSystem · 0 = 3Pn (the only value listed), default 3Pn. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 304115 | 4114 | Pulse output on-timePulseDuration · 0 = 30 ms (default), 1 = 100 ms. The manual prints 304129 beside physical address 1012h; 304115 is the number that matches 1012h, so the wire address 0x1012 is used. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 304129 | 4128 | Energy per pulseKWhPerPulse · 1 to 999, where 1 means 0.01 kWh and 999 means 9.99 kWh. Default 1. The manual prints 304866 beside physical address 1020h; 304129 is the number that matches 1020h, so the wire address 0x1020 is used. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 304865 | 4864 | Application typeApplicationType · 0 to 5 selects application A to F. PFA models support A, B, C and F; PFB models support D and E. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 308193 | 8192 | RS485 instrument addressModbusAddress · 1 to 247. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 308194 | 8193 | RS485 baud rateBaudRate · 0 = 9.6 kbps (default), 1 = 19.2, 2 = 38.4, 3 = 57.6, 4 = 115.2 kbps. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 308195 | 8194 | RS485 parityParity · 0 = none (default), 1 = even. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 308196 | 8195 | RS485 stop bitsStopBits · 0 = 1 stop bit (default), 1 = 2 stop bits. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 304100 | 4099 | Current transformer ratioCT_Ratio · Raw 10 to 9990 means CT ratio 1.0 to 999.0. |
uint32 | 2 | 0.1 | RW | Holding (FC03) | |
| 304102 | 4101 | Voltage transformer ratioVT_Ratio · Raw 10 to 9990 means VT ratio 1.0 to 999.0. Fixed at 1.0 on AV5 PFA and PFB models. |
uint32 | 2 | 0.1 | RW | Holding (FC03) |
Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.
Open in Modbus Poll
- Download the Modbus Poll blocks file.
- Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to CD AB.
- In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
- The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.
Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.
Source and accuracy
Manufacturer document: EM210 Communication Protocol, PFA and PFB models (www.gavazziautomation.com)
EM210 Communication Protocol, Version 4 Revision 3 (October 30th, 2019), pp. 3-12. Read on 2026-10-24.
Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.
Found a mistake? Report it by email with the register address and the manual page.