Carlo Gavazzi EM340 Modbus register map

Three phase DIN rail energy meter from the EM300 family with an optional RS485 Modbus RTU port. The map covers phase and system voltage, current, power, power factor, frequency, import and export energy, tariffs and meter setup.

Protocol
Modbus RTU
Defaults
Per the protocol document: address 1, 9.6 kbps, no parity, one stop bit. Function codes 03 and 04 read the same data.
Addresses in the manual
Modicon style numbers (for example 40001 is holding register 0)
32 and 64-bit values
Low word first (CD AB)
Registers listed
65
Checked against
EM300 Series and ET300 Series Communication Protocol, Version 2 Revision 17 (July 05, 2021)

Address base. The document gives each variable as a 6-digit Modicon number for function 04 (for example 300001) beside the physical word address (0000h). Wire address equals the printed number minus 300001. Function 03 reads the same values with the leading 3 replaced by 4 (pp. 3, 9). Writable settings are printed in the same 3xxxxx form; address them as holding registers. For example 300001 in the manual (Phase 1 line to neutral voltage) is address 0 on the wire.

Word order. INT32, UINT32 and INT64 values are sent least significant word first, with MSB first inside each word (p. 7). The document also mentions an engineering-sample EM340 with the opposite word order (p. 14).

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

65 registers
Manual Wire Register Type Regs Unit Scale Access Area
300001 0 Phase 1 line to neutral voltageVoltage_L1N int32 2 V 0.1 R Input (FC04)
300003 2 Phase 2 line to neutral voltageVoltage_L2N int32 2 V 0.1 R Input (FC04)
300005 4 Phase 3 line to neutral voltageVoltage_L3N int32 2 V 0.1 R Input (FC04)
300007 6 Line 1 to line 2 voltageVoltage_L1L2 int32 2 V 0.1 R Input (FC04)
300009 8 Line 2 to line 3 voltageVoltage_L2L3 int32 2 V 0.1 R Input (FC04)
300011 10 Line 3 to line 1 voltageVoltage_L3L1 int32 2 V 0.1 R Input (FC04)
300013 12 Phase 1 currentCurrent_L1 · Signed; negative in bidirectional mode when power flows in reverse. int32 2 A 0.001 R Input (FC04)
300015 14 Phase 2 currentCurrent_L2 int32 2 A 0.001 R Input (FC04)
300017 16 Phase 3 currentCurrent_L3 int32 2 A 0.001 R Input (FC04)
300019 18 Phase 1 active powerActivePower_L1 int32 2 W 0.1 R Input (FC04)
300021 20 Phase 2 active powerActivePower_L2 int32 2 W 0.1 R Input (FC04)
300023 22 Phase 3 active powerActivePower_L3 int32 2 W 0.1 R Input (FC04)
300025 24 Phase 1 apparent powerApparentPower_L1 int32 2 VA 0.1 R Input (FC04)
300027 26 Phase 2 apparent powerApparentPower_L2 int32 2 VA 0.1 R Input (FC04)
300029 28 Phase 3 apparent powerApparentPower_L3 int32 2 VA 0.1 R Input (FC04)
300031 30 Phase 1 reactive powerReactivePower_L1 int32 2 var 0.1 R Input (FC04)
300033 32 Phase 2 reactive powerReactivePower_L2 int32 2 var 0.1 R Input (FC04)
300035 34 Phase 3 reactive powerReactivePower_L3 int32 2 var 0.1 R Input (FC04)
300037 36 System line to neutral voltageVoltageLN_Sys int32 2 V 0.1 R Input (FC04)
300039 38 System line to line voltageVoltageLL_Sys int32 2 V 0.1 R Input (FC04)
300041 40 System active powerActivePower_Sys int32 2 W 0.1 R Input (FC04)
300043 42 System apparent powerApparentPower_Sys int32 2 VA 0.1 R Input (FC04)
300045 44 System reactive powerReactivePower_Sys int32 2 var 0.1 R Input (FC04)
300047 46 Phase 1 power factorPowerFactor_L1 · Negative means exported active power, positive means imported. int16 1 0.001 R Input (FC04)
300048 47 Phase 2 power factorPowerFactor_L2 int16 1 0.001 R Input (FC04)
300049 48 Phase 3 power factorPowerFactor_L3 int16 1 0.001 R Input (FC04)
300050 49 System power factorPowerFactor_Sys int16 1 0.001 R Input (FC04)
300051 50 Phase sequencePhaseSequence · 0 = L1-L2-L3 order, 1 = L1-L3-L2 order. Meaningful only on a 3-phase system. int16 1 1 R Input (FC04)
300052 51 FrequencyFrequency int16 1 Hz 0.1 R Input (FC04)
300053 52 Total imported active energyEnergyImport_kWh int32 2 kWh 0.1 R Input (FC04)
300055 54 Total imported reactive energyEnergyImport_kvarh int32 2 kvarh 0.1 R Input (FC04)
300057 56 Active power demandPowerDemand int32 2 W 0.1 R Input (FC04)
300059 58 Active power demand peakPowerDemandPeak int32 2 W 0.1 R Input (FC04)
300061 60 Partial imported active energyEnergyImportPartial_kWh int32 2 kWh 0.1 R Input (FC04)
300063 62 Partial imported reactive energyEnergyImportPartial_kvarh int32 2 kvarh 0.1 R Input (FC04)
300065 64 Phase 1 imported active energyEnergyImport_kWh_L1 int32 2 kWh 0.1 R Input (FC04)
300067 66 Phase 2 imported active energyEnergyImport_kWh_L2 int32 2 kWh 0.1 R Input (FC04)
300069 68 Phase 3 imported active energyEnergyImport_kWh_L3 int32 2 kWh 0.1 R Input (FC04)
300071 70 Imported active energy, tariff 1EnergyImport_kWh_T1 int32 2 kWh 0.1 R Input (FC04)
300073 72 Imported active energy, tariff 2EnergyImport_kWh_T2 int32 2 kWh 0.1 R Input (FC04)
300079 78 Total exported active energyEnergyExport_kWh · The manual does not state this for the 0x004E row itself. For the matching 3-decimal export totals at 301033 to 301039 it states the value is 0 on PFA models and on X models in measurement mode A (p. 11). int32 2 kWh 0.1 R Input (FC04)
300081 80 Total exported reactive energyEnergyExport_kvarh int32 2 kvarh 0.1 R Input (FC04)
301025 1024 Total imported active energy, integer partEnergyImport_kWh_Int · Available only on EM340 units made from 1 October 2018. Combine with the decimal part at 301027. int32 2 kWh 1 R Input (FC04)
301027 1026 Total imported active energy, decimal partEnergyImport_kWh_Dec · Thousandths of a kWh, as a 32-bit value with the high word always 0. int32 2 kWh 0.001 R Input (FC04)
300771 770 Firmware version codeVersionCode · 0 = version A, 1 = version B, and so on. uint16 1 1 R Input (FC04)
300772 771 Firmware revision codeRevisionCode · 0 = revision 0, and so on. uint16 1 1 R Input (FC04)
300012 11 Carlo Gavazzi identification codeProductCode · Read one word at a time. The manual lists 341 for the EM340 AV2 versions. uint16 1 1 R Input (FC04)
320497 20496 Production yearProductionYear · Available only on EM330 and EM340 made from 1 October 2018. uint16 1 1 R Input (FC04)
304097 4096 Programming passwordPassword · Valid 0 to 9999. uint16 1 1 RW Holding (FC03)
304099 4098 Measuring systemMeasuringSystem · 0 = 3-phase with neutral, 1 = 3-phase without neutral, 2 = 2-phase with neutral. uint16 1 1 RW Holding (FC03)
304100 4099 Current transformer ratioCT_Ratio · Raw 10 to 10000 means CT ratio 1.0 to 1000.0. uint32 2 0.1 RW Holding (FC03)
304102 4101 Voltage transformer ratioVT_Ratio · Raw 10 to 10000 means VT ratio 1.0 to 1000.0. uint32 2 0.1 RW Holding (FC03)
304353 4352 Display modeDisplayMode · 0 = full (default), 1 = easy. uint16 1 1 RW Holding (FC03)
304354 4353 Tariff management enableTariffEnable · 0 = off, 1 = on. uint16 1 1 RW Holding (FC03)
304356 4355 Measurement mode selectionMeasurementMode · 0 = mode A (easy connection), 1 = mode B (bidirectional). uint16 1 1 RW Holding (FC03)
304358 4357 Wrong connection statusWiringStatus · Bit 0 wrong voltage sequence, bits 1-3 phase 1/2/3 inverted, bits 4-6 phases 1-2, 1-3, 2-3 exchanged, bit 7 all three exchanged. bitfield16 1 1 RW Holding (FC03)
304609 4608 Tariff selection sourceTariffMode · 0 = via digital inputs, 1 = via serial command. uint16 1 1 RW Holding (FC03)
304610 4609 Active tariff via serialTariffNumber · 1 or 2. Read only while tariff selection is by digital input. uint16 1 1 RW Holding (FC03)
308193 8192 RS485 instrument addressModbusAddress · 1 to 247, default 1. uint16 1 1 RW Holding (FC03)
308194 8193 RS485 baud rateBaudRate · 1 = 9.6 kbps (default), 2 = 19.2, 3 = 38.4, 4 = 57.6, 5 = 115.2 kbps. uint16 1 1 RW Holding (FC03)
308195 8194 RS485 parityParity · 1 = no parity (default), 2 = even. uint16 1 1 RW Holding (FC03)
308196 8195 RS485 stop bitsStopBits · 0 or 1 = 1 stop bit, 2 = 2 stop bits (only with even parity). uint16 1 1 RW Holding (FC03)
308197 8196 Maximum words per read requestMaxWordsPerRead · Fixed at 50. uint16 1 1 R Holding (FC03)
316385 16384 Reset partial, tariff and demand metersResetPartialAndTariff · Write 1 to run the command; reads 0 when done. uint16 1 1 RW Holding (FC03)
316386 16385 Reset total energy metersResetTotalEnergy · Write 1 to run the command; only on non-MID (X option) versions. uint16 1 1 RW Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to CD AB.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: EM300 Series and ET300 Series Communication Protocol (www.gavazziautomation.com)

EM300 Series and ET300 Series Communication Protocol, Version 2 Revision 17 (July 05, 2021), pp. 3-18. Read on 2026-10-24.

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.