Yaskawa V1000 Modbus register map
Compact vector control AC drive with a built-in RS-422/RS-485 MEMOBUS/Modbus RTU slave port. The data table covers the run and frequency command registers, drive status, fault and alarm bit words, live monitors, fault codes and the Enter command, and the parameter registers listed here include the communication settings (H5). This file lists the data table plus selected parameters; the full parameter list is in the manual.
- Protocol
- Modbus RTU
- Defaults
- Per the parameter list: node address 1FH (H5-01), 9600 bps (H5-02 = 3), no parity (H5-03 = 0); data length 8 bit and 1 stop bit are fixed. Slave addresses 0 to 20H are allowed and address 0 is broadcast with no response. Control over Modbus needs b1-01 = 2 and b1-02 = 2. H5-01 to H5-03 need a power cycle to take effect.
- Addresses in the manual
- 0-based protocol addresses, as sent on the wire
- 32 and 64-bit values
- High word first (AB CD)
- Registers listed
- 93
- Checked against
- SIEP C710606 19B, published in Japan December 2011. Yaskawa PDF as hosted by Omron Europe; copy hosted by a third party, vendor-hosted copy could not be fetched.
Address base. The data table prints hex register numbers and the message examples use them directly as the starting number (a read starting at 0020H uses bytes 00 20 and returns the drive status registers; a write starting at 0001H writes the command word), so the printed number is the wire address (pp. 414 to 416). Parameter registers are the hex addresses printed in the parameter list, for example H5-01 is 0425H. Addresses here are those hex numbers converted to decimal, and each note repeats the hex value. The manual lists only function codes 03H (read), 08H (loopback) and 10H (write multiple registers), at most 16 registers per read (p. 412 and p. 414). Parameter changes need an Enter command (0900H or 0910H) unless H5-11 = 1. Address 1 in the manual is address 1 on the wire.
Word order. The data table gives accumulated operation time and cooling fan operation time as a high word at the lower register and a low word at the next register (0098H and 0099H, 009AH and 009BH), so 32-bit values are high word first. All other rows are single 16-bit registers.
Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.
Downloads
The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.
Registers
| Manual | Wire | Register | Type | Regs | Unit | Scale | Access | Area |
|---|---|---|---|---|---|---|---|---|
| 1 | 1 | Run command and multi-function input command wordCommandWord · Bit 0 forward run or run (depends on H5-12), bit 1 reverse run or forward/reverse (H5-12), bit 2 external fault EF0, bit 3 fault reset, bit 4 multi-function input 1 (ComRef when H1-01 = 40), bit 5 multi-function input 2 (ComCtrl when H1-02 = 41), bits 6 to 9 multi-function inputs 3 to 6. Bits A to F reserved. Register 0001H. |
bitfield16 | 1 | 1 | RW | Holding (FC03) | |
| 2 | 2 | Frequency referenceFrequencyReference · Units are set by o1-03: 0.01 Hz when o1-03 = 0 (default), 0.01% of maximum output frequency when 1, r/min when 2 (p. 235). The manual's write example on p. 415 sends 0258H (600) and describes it as 60.0 Hz, which does not match 0.01 Hz units (600 would be 6.00 Hz), so check the scale on the device. Register 0002H. |
uint16 | 1 | Hz | 0.01 | RW | Holding (FC03) |
| 3 | 3 | Output voltage gainOutputVoltageGain · Set in units of 1 (0.1%) with a setting range of 20 to 2000 (2.0% to 200.0%). Initial value at power up is 1000 (100.0%). Register 0003H. |
uint16 | 1 | % | 0.1 | RW | Holding (FC03) |
| 6 | 6 | PID targetPidTarget · 0.01% units, signed. Bit 1 of register 000FH is the PID target input bit. Register 0006H. |
int16 | 1 | % | 0.01 | RW | Holding (FC03) |
| 7 | 7 | Analog output terminal AM settingAnalogOutputAmSetting · 10 V corresponds to 4000H. Register 0007H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 9 | 9 | Settings for multi-function digital outputsDigitalOutputSettings · Bit 0 contact output (terminal MA/MB-MC), bit 1 photocoupler output 1 (P1-PC), bit 2 photocoupler output 2 (P2-PC). Bits 3 to F reserved. Register 0009H. |
bitfield16 | 1 | 1 | RW | Holding (FC03) | |
| 10 | 10 | Pulse output terminal MP settingPulseOutputMpSetting · Setting range 0 to 32000. Register 000AH. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 15 | 15 | Control selection settingControlSelectionSetting · Bit 1 PID target input, bit C enable terminal S5 input for broadcast data, bit D enable terminal S6 input for broadcast data. Other bits reserved. Register 000FH. |
bitfield16 | 1 | 1 | RW | Holding (FC03) | |
| 32 | 32 | Drive status 1DriveStatus1 · Bit 0 during run, bit 1 during reverse, bit 2 drive ready, bit 3 fault, bit 4 data setting error, bit 5 multi-function contact output (MA/MB-MC), bit 6 photocoupler output 1, bit 7 photocoupler output 2, bit E ComRef status, bit F NetRef status. Register 0020H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 33 | 33 | Fault contents 1FaultContents1 · Bit 0 oC, GF or SC, bit 1 ov, bit 2 oL2, bit 3 oH1 or oH2, bit 4 rr or rH, bit 6 PID feedback loss (FbL/FbH), bit 7 EF0 to EF6, bit 8 CPFoo or oFAoo hardware fault, bit 9 oL1, oL3/oL4 or UL3/UL4, bit A PGo, oS or dEv, bit B Uv, bit C Uv1, Uv2 or Uv3, bit D LF or PF, bit E CE or bUS, bit F oPr. Register 0021H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 34 | 34 | Data link statusDataLinkStatus · Bit 0 writing data or switching motors, bit 3 upper or lower limit error, bit 4 data conformity error, bit 5 writing to EEPROM. Register 0022H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 35 | 35 | Frequency reference monitorFrequencyReferenceMonitor · Units are set by o1-03 (0.01 Hz when o1-03 = 0, the default). Register 0023H. |
uint16 | 1 | Hz | 0.01 | R | Holding (FC03) |
| 36 | 36 | Output frequencyOutputFrequency · Units are set by o1-03 (0.01 Hz when o1-03 = 0, the default). Register 0024H. |
uint16 | 1 | Hz | 0.01 | R | Holding (FC03) |
| 37 | 37 | Output voltage referenceOutputVoltageReference · 0.1 V units when H5-10 = 0 (default), 1 V units when H5-10 = 1. Register 0025H. |
uint16 | 1 | V | 0.1 | R | Holding (FC03) |
| 38 | 38 | Output currentOutputCurrent · Units are 0.01 A for drives set to 11 kW or less in Heavy or Normal Duty and 0.1 A for drives set to 15 kW and above, so no fixed scale is given. Register 0026H. |
uint16 | 1 | A | 1 | R | Holding (FC03) |
| 41 | 41 | Fault contents 2FaultContents2 · Bit 0 SC, bit 1 GF, bit 2 PF, bit 3 LF, bit 4 rH, bit 6 oH4. Other bits reserved. Register 0029H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 42 | 42 | Alarm contents 1AlarmContents1 · Bit 2 EF, bit 3 bb, bit 4 oL3, bit 5 oH, bit 6 ov, bit 7 Uv, bit 9 CE, bit A bUS, bit B UL3/UL4, bit C oH3, bit D FbL/FbH, bit F CALL. Other bits reserved. Register 002AH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 43 | 43 | Input terminal statusInputTerminalStatus · Bits 0 to 5 are terminals S1 to S6 closed. Other bits reserved. Register 002BH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 44 | 44 | Drive status 2DriveStatus2 · Bit 0 during run, bit 1 zero speed, bit 2 speed agree, bit 3 user speed agree, bit 4 frequency detection 1, bit 5 frequency detection 2, bit 6 drive ready, bit 7 during undervoltage, bit 8 during baseblock, bit 9 frequency reference from operator keypad, bit A run command from operator keypad, bit B over/undertorque 1, 2, bit C frequency reference loss, bit D during fault restart, bit E fault, bit F communication timeout. Register 002CH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 45 | 45 | Output terminal statusOutputTerminalStatus · Bit 0 multi-function contact output (MA/MB-MC), bit 1 photocoupler output 1 (P1-PC), bit 2 photocoupler output 2 (P2-PC). Register 002DH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 49 | 49 | DC bus voltageDcBusVoltage · 1 Vdc units. Register 0031H. |
uint16 | 1 | V | 1 | R | Holding (FC03) |
| 52 | 52 | Product code 1 (ASCII), product typeProductCode1 · ASCII, product type (V0 for V1000). Register 0034H. |
string | 1 | 1 | R | Holding (FC03) | |
| 53 | 53 | Product code 2 (ASCII), region codeProductCode2 · ASCII region code. Register 0035H. |
string | 1 | 1 | R | Holding (FC03) | |
| 56 | 56 | PID feedbackPidFeedback · 0.1% units, unsigned, 100% corresponds to maximum output frequency. Register 0038H. |
uint16 | 1 | % | 0.1 | R | Holding (FC03) |
| 57 | 57 | PID inputPidInput · 0.1% units, signed, 100% corresponds to maximum output frequency. Register 0039H. |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 58 | 58 | PID outputPidOutput · 0.1% units, signed, 100% corresponds to maximum output frequency. Register 003AH. |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 61 | 61 | Communications error logCommunicationsErrorLog · Bit 0 CRC error, bit 1 data length error, bit 3 parity error, bit 4 overrun error, bit 5 framing error, bit 6 timeout. Stored until the fault is reset. Register 003DH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 62 | 62 | Output frequency in r/minOutputFrequencyRpm · r/min units. The correct motor pole number must be set in E2-04, E4-04 or E5-05. Register 003EH. |
uint16 | 1 | r/min | 1 | R | Holding (FC03) |
| 63 | 63 | Output frequency in percentOutputFrequencyPercent · 0.01% units. Register 003FH. |
uint16 | 1 | % | 0.01 | R | Holding (FC03) |
| 67 | 67 | U1-04 control modeU1_04_ControlMode · 0 V/f without PG, 2 open loop vector (OLV), 5 PM open loop vector. Registers 0040H to 004AH are listed as carrying various U1 monitors; the U1-04 address 43H is from the parameter list. Register 0043H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 75 | 75 | Drive status (U1-12)DriveStatusU1_12 · Bit 0 during run, bit 1 during zero speed, bit 2 during reverse run, bit 3 during fault reset signal input, bit 4 during speed agree, bit 5 drive ready, bit 6 alarm, bit 7 fault, bit 8 during operation error (oPEoo), bit 9 during momentary power loss, bit A motor 2 selected, bit E ComRef/NetRef status, bit F ComCtrl/NetCtrl status. Register 004BH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 77 | 77 | U1-25 software number (Flash)U1_25_SoftwareNumberFlash · Flash ID. Address 4DH is from the parameter list; the data table lists registers 004CH to 007EH as carrying various monitors. Register 004DH. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 91 | 91 | U1-26 software number (ROM)U1_26_SoftwareNumberRom · ROM ID. Address 5BH is from the parameter list; the data table lists registers 004CH to 007EH as carrying various monitors. Register 005BH. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 127 | 127 | Alarm codeAlarmCode · Alarm codes are listed in Table C.5 on p. 426, for example 0001H Uv, 0002H ov, 0003H oH, 0014H CE. Register 007FH. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 128 | 128 | U2-01 current faultU2_01_CurrentFault · Fault codes are listed in Table C.4 on p. 425, for example 0002H Uv1, 0007H oC, 0008H ov, 0021H CE. Registers 0080H to 0097H carry the U2 and U3 monitors. Register 0080H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 129 | 129 | U2-02 previous faultU2_02_PreviousFault · Fault code as in Table C.4 on p. 425. Register 0081H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 144 | 144 | U3-01 most recent faultU3_01_MostRecentFault · Fault code as in Table C.4 on p. 425. The parameter list also prints 800 as an alternative address for this entry. Register 0090H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 145 | 145 | U3-02 second most recent faultU3_02_SecondMostRecentFault · Fault code as in Table C.4 on p. 425. The parameter list also prints 801 as an alternative address. Register 0091H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 146 | 146 | U3-03 third most recent faultU3_03_ThirdMostRecentFault · Fault code as in Table C.4 on p. 425. The parameter list also prints 802 as an alternative address. Register 0092H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 147 | 147 | U3-04 fourth most recent faultU3_04_FourthMostRecentFault · Fault code as in Table C.4 on p. 425. The parameter list also prints 803 as an alternative address. Register 0093H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 152 | 152 | U4-01 accumulated operation timeU4_01_AccumulatedOperationTime · High word at 0098H and low word at 0099H. The parameter list prints 4CH for U4-01, which differs from this data table; the data table is followed here. Register 0098H. |
uint32 | 2 | h | 1 | R | Holding (FC03) |
| 154 | 154 | U4-03 cooling fan operation timeU4_03_CoolingFanOperationTime · High word at 009AH and low word at 009BH. Available in drive software versions PRG: 1011 and later. The parameter list prints 67H for U4-03, which differs from this data table; the data table is followed here. Register 009AH. |
uint32 | 2 | h | 1 | R | Holding (FC03) |
| 171 | 171 | Drive rated currentDriveRatedCurrent · Units are 0.01 A for drives set to 11 kW or less in Heavy or Normal Duty and 0.1 A for drives set to 15 kW and above, so no fixed scale is given. Register 00ABH. |
uint16 | 1 | A | 1 | R | Holding (FC03) |
| 176 | 176 | Option codeOptionCode · ASCII code of the installed serial communication option, for example 5353H CANopen (SI-S3/V), 5343H CC-Link (SI-C3/V), 534EH DeviceNet (SI-N3/V), 5350H PROFIBUS-DP (SI-P3/V). Register 00B0H. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 191 | 191 | oPE error numberOpeErrorNumber · Register 00BFH. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 192 | 192 | Fault contents 3FaultContents3 · Bit 1 Uv1, bit 2 Uv2, bit 3 Uv3, bit 4 SC, bit 5 GF, bit 6 oC, bit 7 ov, bit 8 oH, bit 9 oH1, bit A oL1, bit B oL2, bit C oL3, bit D oL4, bit E rr, bit F rH. Register 00C0H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 193 | 193 | Fault contents 4FaultContents4 · Bit 0 EF3, bit 1 EF4, bit 2 EF5, bit 3 EF6, bit 7 oS, bit 8 dEv, bit 9 PGo, bit A PF, bit B LF, bit C oH3, bit D oPr, bit E Err, bit F oH4. Register 00C1H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 194 | 194 | Fault contents 5FaultContents5 · Bit 0 CE, bit 1 bUS, bit 4 CF, bit 6 option external fault EF0, bit 7 FbL, bit 8 UL3, bit 9 UL4, bit A oL7, bit F hardware fault (includes oFAoo). Register 00C2H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 195 | 195 | Fault contents 6FaultContents6 · Bit 5 LF2, bit 6 STo, bit 7 PGo, bit 8 SI-T3/V watchdog error E5, bit A SEr. Register 00C3H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 196 | 196 | Fault contents 7FaultContents7 · Bit 0 FbH, bit 1 EF1, bit 2 EF2, bit 3 oL5, bit 4 UL5, bit 5 CoF, bit 8 dWFL. Register 00C4H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 200 | 200 | Alarm contents 2AlarmContents2 · Bit 0 Uv, bit 1 ov, bit 2 oH, bit 3 oH2, bit 4 oL3, bit 5 oL4, bit 6 EF, bit 7 bb, bit 8 EF3, bit 9 EF4, bit A EF5, bit B EF6, bit F oS. Register 00C8H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 201 | 201 | Alarm contents 3AlarmContents3 · Bit 0 dEv, bit 1 PGo, bit 2 oPr, bit 3 CE, bit 4 bUS, bit 5 CALL, bit 6 oL1, bit 7 oL2, bit 9 option card EF0, bit A rUn, bit C CALL, bit D UL3, bit E UL4, bit F SE. Register 00C9H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 202 | 202 | Alarm contents 4AlarmContents4 · Bit 1 oH3, bit 6 FbL, bit 7 FbH, bit 9 dnE. Register 00CAH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 203 | 203 | Alarm contents 5AlarmContents5 · Bit 0 SI-T3/V watchdog error E5, bit 2 CyC, bit 3 HCA, bit 4 LT-1, bit 5 LT-2, bit 7 EEP, bit 8 EF1, bit 9 EF2, bit A HbbF, bit B Hbb, bit C oL5, bit D UL5. Register 00CBH. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 208 | 208 | CPF contents 1CpfContents1 · Bit 2 CPF02, bit 3 CPF03, bit 6 CPF06, bit 7 CPF07, bit 8 CPF08, bit B CPF11, bit C CPF12, bit D CPF13, bit E CPF14. Register 00D0H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 209 | 209 | CPF contents 2CpfContents2 · Bit 0 CPF16, bit 1 CPF17, bit 2 CPF18, bit 3 CPF19, bit 4 CPF20, bit 5 CPF21, bit 6 CPF22, bit 7 CPF23, bit 8 CPF24, bit 9 CPF25. Register 00D1H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 216 | 216 | Option card fault contentsOptionCardFaultContents · Bit 0 oFA00, bit 1 oFA01, bit 3 oFA03, bit 4 oFA04. Register 00D8H. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 384 | 384 | b1-01 frequency reference selection 1b1_01_FrequencyReferenceSelection1 · 0 operator, 1 terminals (analog input A1 or A2), 2 MEMOBUS communications, 3 option PCB, 4 pulse input (terminal RP). Default 1. Set 2 for Modbus frequency control. Register 0180H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 385 | 385 | b1-02 run command selection 1b1_02_RunCommandSelection1 · 0 operator, 1 digital input terminals, 2 MEMOBUS communications, 3 option PCB. Default 1. Set 2 for Modbus run control. Register 0181H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 386 | 386 | b1-03 stopping method selectionb1_03_StoppingMethodSelection · 0 ramp to stop, 1 coast to stop, 2 DC injection braking to stop, 3 coast with timer, 9 simple positioning. Default 0. Register 0182H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 387 | 387 | b1-04 reverse operation selectionb1_04_ReverseOperationSelection · 0 reverse enabled, 1 reverse disabled. Default 0. Register 0183H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 512 | 512 | C1-01 acceleration time 1C1_01_AccelerationTime1 · Range 0.0 to 6000.0 s, default 10.0 s. The scale follows the resolution set in C1-10, but the parameter list does not state the register scaling, so none is given. Register 0200H. |
uint16 | 1 | s | 1 | RW | Holding (FC03) |
| 513 | 513 | C1-02 deceleration time 1C1_02_DecelerationTime1 · Range 0.0 to 6000.0 s, default 10.0 s. The scale follows the resolution set in C1-10, but the parameter list does not state the register scaling, so none is given. Register 0201H. |
uint16 | 1 | s | 1 | RW | Holding (FC03) |
| 514 | 514 | C1-03 acceleration time 2C1_03_AccelerationTime2 · Range 0.0 to 6000.0 s, default 10.0 s. Register scaling is not stated in the parameter list, so no scale is given. Register 0202H. |
uint16 | 1 | s | 1 | RW | Holding (FC03) |
| 515 | 515 | C1-04 deceleration time 2C1_04_DecelerationTime2 · Range 0.0 to 6000.0 s, default 10.0 s. Register scaling is not stated in the parameter list, so no scale is given. Register 0203H. |
uint16 | 1 | s | 1 | RW | Holding (FC03) |
| 521 | 521 | C1-10 accel/decel time setting unitsC1_10_AccelDecelTimeUnits · 0 resolution 0.01 s (0.00 to 600.00 s), 1 resolution 0.1 s (0.0 to 6000.0 s). Default 1. Register 0209H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 640 | 640 | d1-01 frequency reference 1d1_01_FrequencyReference1 · Range 0.00 to 400.00 Hz, default 0.00 Hz, entered in the units set by o1-03. Register scaling is not stated in the parameter list, so no scale is given. Register 0280H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 641 | 641 | d1-02 frequency reference 2d1_02_FrequencyReference2 · Range 0.00 to 400.00 Hz, default 0.00 Hz, entered in the units set by o1-03. Register scaling is not stated in the parameter list, so no scale is given. Register 0281H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 642 | 642 | d1-03 frequency reference 3d1_03_FrequencyReference3 · Range 0.00 to 400.00 Hz, default 0.00 Hz, entered in the units set by o1-03. Register scaling is not stated in the parameter list, so no scale is given. Register 0282H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 643 | 643 | d1-04 frequency reference 4d1_04_FrequencyReference4 · Range 0.00 to 400.00 Hz, default 0.00 Hz, entered in the units set by o1-03. Register scaling is not stated in the parameter list, so no scale is given. Register 0283H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 649 | 649 | d2-01 frequency reference upper limitd2_01_FrequencyReferenceUpperLimit · Range 0.0 to 110.0 %, default 100.0 %, as a percentage of E1-04. Register scaling is not stated in the parameter list, so no scale is given. Register 0289H. |
uint16 | 1 | % | 1 | RW | Holding (FC03) |
| 650 | 650 | d2-02 frequency reference lower limitd2_02_FrequencyReferenceLowerLimit · Range 0.0 to 110.0 %, default 0.0 %, as a percentage of E1-04. Register scaling is not stated in the parameter list, so no scale is given. Register 028AH. |
uint16 | 1 | % | 1 | RW | Holding (FC03) |
| 771 | 771 | E1-04 maximum output frequencyE1_04_MaxOutputFrequency · Range 40.0 to 400.0 Hz. Register scaling is not stated in the parameter list, so no scale is given. Register 0303H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 772 | 772 | E1-05 maximum output voltageE1_05_MaxOutputVoltage · Range 0.0 to 255.0 V for 200 V class drives. Register scaling is not stated in the parameter list, so no scale is given. Register 0304H. |
uint16 | 1 | V | 1 | RW | Holding (FC03) |
| 773 | 773 | E1-06 base frequencyE1_06_BaseFrequency · Range 0.0 Hz up to E1-04. Register scaling is not stated in the parameter list, so no scale is given. Register 0305H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 776 | 776 | E1-09 minimum output frequencyE1_09_MinOutputFrequency · Range 0.0 Hz up to E1-04. Register scaling is not stated in the parameter list, so no scale is given. Register 0308H. |
uint16 | 1 | Hz | 1 | RW | Holding (FC03) |
| 782 | 782 | E2-01 motor rated currentE2_01_MotorRatedCurrent · Range 10 to 200% of drive rated current. The resolution depends on the drive rated output power and the register scaling is not stated, so no scale is given. Register 030EH. |
uint16 | 1 | A | 1 | RW | Holding (FC03) |
| 785 | 785 | E2-04 number of motor polesE2_04_NumberOfMotorPoles · Range 2 to 48 poles, default 4. Register 0311H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1061 | 1061 | H5-01 drive node addressH5_01_DriveNodeAddress · Range 0 to 20H, default 1FH. Cycle power for the setting to take effect. The drive does not respond to address 0, which is the broadcast address. Register 0425H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1062 | 1062 | H5-02 communication speed selectionH5_02_CommunicationSpeedSelection · 0 = 1200 bps, 1 = 2400, 2 = 4800, 3 = 9600 (default), 4 = 19200, 5 = 38400, 6 = 57600, 7 = 76800, 8 = 115200. Cycle power for the setting to take effect. Register 0426H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1063 | 1063 | H5-03 communication parity selectionH5_03_CommunicationParitySelection · 0 no parity (default), 1 even parity, 2 odd parity. Cycle power for the setting to take effect. Register 0427H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1064 | 1064 | H5-04 stopping method after communication errorH5_04_StoppingMethodAfterCommError · 0 ramp to stop, 1 coast to stop, 2 fast-stop, 3 alarm only (default). Register 0428H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1065 | 1065 | H5-05 communication fault detection selectionH5_05_CommunicationFaultDetection · 0 disabled, 1 enabled (default). When enabled, a CE fault occurs if data is not received for longer than H5-09. Register 0429H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1066 | 1066 | H5-06 drive transmit wait timeH5_06_DriveTransmitWaitTime · Range 5 to 65 ms, default 5 ms. Register 042AH. |
uint16 | 1 | ms | 1 | RW | Holding (FC03) |
| 1067 | 1067 | H5-07 RTS control selectionH5_07_RtsControlSelection · 0 disabled (RTS always on), 1 enabled (RTS turns on only when sending, for RS-485). Default 1. Register 042BH. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1077 | 1077 | H5-09 CE detection timeH5_09_CeDetectionTime · Range 0.0 to 10.0 s, default 2.0 s. The register scale is not stated in the parameter list, so none is given. Register 0435H. |
uint16 | 1 | s | 1 | RW | Holding (FC03) |
| 1078 | 1078 | H5-10 unit selection for MEMOBUS/Modbus register 0025HH5_10_UnitSelectionRegister0025H · 0 = 0.1 V units (default), 1 = 1 V units for the output voltage monitor in register 0025H. Register 0436H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1084 | 1084 | H5-11 communications Enter function selectionH5_11_EnterFunctionSelection · 0 parameter changes are activated when an Enter command is sent (default), 1 changes are activated immediately without an Enter command. Register 043CH. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1085 | 1085 | H5-12 run command method selectionH5_12_RunCommandMethodSelection · 0 FWD/STOP and REV/STOP method (default), 1 RUN/STOP and FWD/REV method. Sets the meaning of bits 0 and 1 of register 0001H. Register 043DH. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1152 | 1152 | L1-01 motor overload protection selectionL1_01_MotorOverloadProtectionSelection · Setting range 0 to 4 and 6; the meaning of each setting is in the parameter list. The default depends on the control method (A1-02). Register 0480H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 1282 | 1282 | o1-03 digital operator display selectiono1_03_DigitalOperatorDisplaySelection · 0 = 0.01 Hz units (default), 1 = 0.01% units (100% = maximum output frequency), 2 = r/min units, 3 = user-set units (o1-10, o1-11). Sets the units of frequency reference registers 0002H, 0023H and 0024H and of d1-01 to d1-17. Register 0502H. |
uint16 | 1 | 1 | RW | Holding (FC03) | |
| 2304 | 2304 | Enter command: write data to EEPROM and enable it in RAMEnterCommandSaveToEeprom · Write 0 to enable. Parameter changes remain after a power cycle. Write only: reading this register causes an error. Not needed when H5-11 = 1. Register 0900H. |
uint16 | 1 | 1 | W | Holding (FC03) | |
| 2320 | 2320 | Enter command: write data to RAM onlyEnterCommandRamOnly · Write 0 to enable. Parameter changes are lost when the drive is switched off. Write only: reading this register causes an error. Register 0910H. |
uint16 | 1 | 1 | W | Holding (FC03) |
Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.
Open in Modbus Poll
- Download the Modbus Poll blocks file.
- Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to AB CD.
- In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
- The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.
Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.
Source and accuracy
Manufacturer document: YASKAWA AC Drive V1000 Compact Vector Control Drive Technical Manual (assets.omron.eu)
SIEP C710606 19B, published in Japan December 2011. Yaskawa PDF as hosted by Omron Europe; copy hosted by a third party, vendor-hosted copy could not be fetched., Appendix C MEMOBUS/Modbus communications pp. 404 to 427 (data table pp. 416 to 426); Appendix B parameter list pp. 332 to 373; p. 235 (o1-03). Read on 2026-10-24.
Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.
Found a mistake? Report it by email with the register address and the manual page.