Danfoss VLT Micro Drive FC 51 Modbus register map

Compact AC drive with a built-in RS-485 port that can run Modbus RTU. Drive parameters are mapped to holding registers at ten times the parameter number, and the control and status words are available both as holding registers and as coils.

Protocol
Modbus RTU
Defaults
Modbus RTU must be selected with 8-30 Protocol = [2] (default is FC protocol) and takes effect after a power cycle. Defaults per the guides: address 1 (8-31), 19200 baud when Modbus is selected (8-32), even parity with 1 stop bit (8-33).
Addresses in the manual
1-based register numbers (wire address is the number minus 1)
32 and 64-bit values
High word first (AB CD)
Registers listed
91
Checked against
Design Guide MG02K402, Danfoss A/S 01/2016. Parameter scales and data types from VLT Micro Drive FC 51 Programming Guide MG02C702, 12/2014

Address base. The guide numbers registers and coils from 1 and says every data address in a telegram is the printed number minus 1, for example holding register 40001 is sent as address 0000 and coil 33 as coil 32 (pp. 74, 77, 78). Parameter registers are 10 times the parameter number, for example 3-12 is register 3120 (p. 76). For example 1 in the manual (Control word coil: Preset reference select, low bit) is address 0 on the wire.

Word order. 32-bit parameters use two consecutive registers. The read example for 3-03 in the Design Guide shows the high word in the lower register number (register 3030 = 0016h, register 3031 = E360h, p. 79). Values are integers, apply the scale from the conversion index (for example -3 means 0.001).

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

91 registers
Manual Wire Register Type Regs Unit Scale Access Area
1 0 Control word coil: Preset reference select, low bitCoil01_CTW_PresetRefLsb · 0 and 1 together choose one of the four preset references. bool 1 1 RW Coil (FC01)
2 1 Control word coil: Preset reference select, high bitCoil02_CTW_PresetRefMsb · 0 and 1 together choose one of the four preset references (with coil 1). bool 1 1 RW Coil (FC01)
3 2 Control word coil: DC brakeCoil03_CTW_DCBrake · 0 = DC brake, 1 = no DC brake. bool 1 1 RW Coil (FC01)
4 3 Control word coil: Coast stopCoil04_CTW_CoastStop · 0 = coast stop, 1 = no coast stop. bool 1 1 RW Coil (FC01)
5 4 Control word coil: Quick stopCoil05_CTW_QuickStop · 0 = quick stop, 1 = no quick stop. bool 1 1 RW Coil (FC01)
6 5 Control word coil: Freeze output frequencyCoil06_CTW_FreezeFrequency · 0 = freeze, 1 = no freeze. bool 1 1 RW Coil (FC01)
7 6 Last fault codeLastFaultCode · Fault code received from the parameter database. uint16 1 1 R Holding (FC03)
7 6 Control word coil: Ramp stop or startCoil07_CTW_RampStopStart · 0 = ramp stop, 1 = start. bool 1 1 RW Coil (FC01)
8 7 Register address of the last access errorLastErrorRegister uint16 1 1 R Holding (FC03)
8 7 Control word coil: Reset tripCoil08_CTW_Reset · 0 = no reset, 1 = reset. bool 1 1 RW Coil (FC01)
9 8 Sub-index pointer for array parametersIndexPointer · Sets the sub-index used when reading or writing array parameters. uint16 1 1 RW Holding (FC03)
9 8 Control word coil: JogCoil09_CTW_Jog · 0 = no jog, 1 = jog. bool 1 1 RW Coil (FC01)
10 9 Control word coil: Select ramp 2Coil10_CTW_Ramp2 · 0 = ramp 1, 1 = ramp 2. bool 1 1 RW Coil (FC01)
11 10 Control word coil: Control word data validCoil11_CTW_DataValid · 0 = data not valid, 1 = data valid. bool 1 1 RW Coil (FC01)
12 11 Control word coil: Relay 1Coil12_CTW_Relay1 · 0 = off, 1 = on. bool 1 1 RW Coil (FC01)
13 12 Control word coil: Relay 2Coil13_CTW_Relay2 · 0 = off, 1 = on. bool 1 1 RW Coil (FC01)
14 13 Control word coil: Set-up select, low bitCoil14_CTW_SetupLsb · Set-up selection bit. bool 1 1 RW Coil (FC01)
16 15 Control word coil: ReversingCoil16_CTW_Reversing · 0 = no reversing, 1 = reversing. bool 1 1 RW Coil (FC01)
33 32 Status word coil: Control readyCoil33_STW_ControlReady · 0 = control not ready, 1 = control ready. bool 1 1 R Coil (FC01)
34 33 Status word coil: Drive readyCoil34_STW_DriveReady · 0 = not ready, 1 = ready. bool 1 1 R Coil (FC01)
35 34 Status word coil: Coast stop or safetyCoil35_STW_CoastStop · 0 = coast stop, 1 = safety closed. bool 1 1 R Coil (FC01)
36 35 Status word coil: AlarmCoil36_STW_Alarm · 0 = no alarm, 1 = alarm. bool 1 1 R Coil (FC01)
40 39 Status word coil: WarningCoil40_STW_Warning · 0 = no warning, 1 = warning. bool 1 1 R Coil (FC01)
41 40 Status word coil: At referenceCoil41_STW_AtReference · 0 = not at reference, 1 = at reference. bool 1 1 R Coil (FC01)
42 41 Status word coil: Hand or auto modeCoil42_STW_AutoMode · 0 = hand mode, 1 = auto mode. bool 1 1 R Coil (FC01)
43 42 Status word coil: Within frequency rangeCoil43_STW_InFrequencyRange · 0 = out of frequency range, 1 = in range. bool 1 1 R Coil (FC01)
44 43 Status word coil: RunningCoil44_STW_Running · 0 = stopped, 1 = running. bool 1 1 R Coil (FC01)
46 45 Status word coil: Voltage warningCoil46_STW_VoltageWarning · 0 = no voltage warning, 1 = voltage warning. bool 1 1 R Coil (FC01)
47 46 Status word coil: Current limitCoil47_STW_CurrentLimit · 0 = not in current limit, 1 = in current limit. bool 1 1 R Coil (FC01)
48 47 Status word coil: Thermal warningCoil48_STW_ThermalWarning · 0 = no thermal warning, 1 = thermal warning. bool 1 1 R Coil (FC01)
65 64 Parameter write controlCoil65_ParameterWriteControl · 0 = parameter changes go to RAM only, 1 = changes go to RAM and EEPROM. bool 1 1 RW Coil (FC01)
1220 1219 Motor nameplate voltage (1-22)P1_22_MotorVoltage uint16 1 V 1 RW Holding (FC03)
1230 1229 Motor nameplate frequency (1-23)P1_23_MotorFrequency uint16 1 Hz 1 RW Holding (FC03)
1240 1239 Motor nameplate current (1-24)P1_24_MotorCurrent · The manual example sets 7.38 A by writing 738. uint16 1 A 0.01 RW Holding (FC03)
1250 1249 Motor nameplate speed (1-25)P1_25_MotorNominalSpeed uint16 1 rpm 1 RW Holding (FC03)
2810 2809 FC profile control word (lower register area)ControlWordLow · Available on software version 2.32 and later. Bits as in the FC profile control word table: bit 0/1 preset reference select, 2 DC brake, 3 coast, 4 quick stop, 5 hold output frequency, 6 ramp stop or start, 7 reset, 8 jog, 9 ramp 1 or 2, 10 data valid, 11 relay 1, 12 relay 2, 13 set-up select, 15 reverse. The manual places this table under the setting 8-30 Protocol = [0] FC. bitfield16 1 1 RW Holding (FC03)
2811 2810 Bus speed reference (lower register area)BusReferenceLow · Relative value: 16384 (4000h) is 100 percent of the reference range, negative values use two's complement. Available on software version 2.32 and later. int16 1 1 RW Holding (FC03)
2910 2909 FC profile status word (lower register area)StatusWordLow · Bit 0 control ready, 1 drive ready, 2 enabled (not coasting), 3 trip, 4 error without trip, 6 trip lock, 7 warning, 8 speed equals reference, 9 bus control active, 10 frequency within limits, 11 running, 12 stopped by over-temperature with auto start, 13 voltage limit exceeded, 14 current limit exceeded, 15 timer limit exceeded. Software 2.32 and later. bitfield16 1 1 R Holding (FC03)
2911 2910 Main actual value, output frequency (lower register area)MainActualValueLow · Scaled like the bus reference: 16384 (4000h) is 100 percent. Software 2.32 and later. int16 1 1 R Holding (FC03)
3020 3019 Minimum reference (3-02)P3_02_MinimumReference int32 2 0.001 RW Holding (FC03)
3030 3029 Maximum reference (3-03)P3_03_MaximumReference · The manual read example fetches this parameter from registers 3030 and 3031. int32 2 0.001 RW Holding (FC03)
3110 3109 Jog speed (3-11)P3_11_JogSpeed uint16 1 Hz 0.1 RW Holding (FC03)
3410 3409 Ramp 1 ramp-up time (3-41)P3_41_Ramp1UpTime uint32 2 s 0.01 RW Holding (FC03)
3420 3419 Ramp 1 ramp-down time (3-42)P3_42_Ramp1DownTime uint32 2 s 0.01 RW Holding (FC03)
4120 4119 Motor speed low limit (4-12)P4_12_MotorSpeedLowLimit uint16 1 Hz 0.1 RW Holding (FC03)
4140 4139 Motor speed high limit (4-14)P4_14_MotorSpeedHighLimit uint16 1 Hz 0.1 RW Holding (FC03)
4160 4159 Torque limit, motor mode (4-16)P4_16_TorqueLimitMotor uint16 1 % 1 RW Holding (FC03)
8010 8009 Control site (8-01)P8_01_ControlSite · 0 digital and control word (default), 1 digital only, 2 control word only. uint16 1 1 RW Holding (FC03)
8020 8019 Control word source (8-02)P8_02_ControlWordSource · 0 none, 1 FC RS-485 (default). uint16 1 1 RW Holding (FC03)
8030 8029 Control word timeout time (8-03)P8_03_ControlWordTimeout · Range 0.1 to 6500 s. uint16 1 s 0.1 RW Holding (FC03)
8040 8039 Control word timeout function (8-04)P8_04_ControlWordTimeoutFunction · 0 off, 1 freeze output, 2 stop, 3 jogging, 4 max speed, 5 stop and trip. uint16 1 1 RW Holding (FC03)
8300 8299 Serial protocol (8-30)P8_30_Protocol · 0 = FC (default), 2 = Modbus RTU. Takes effect after a power cycle. uint16 1 1 RW Holding (FC03)
8310 8309 Bus address (8-31)P8_31_Address · Default 1. Modbus range is 1 to 247. uint16 1 1 RW Holding (FC03)
8320 8319 Baud rate (8-32)P8_32_BaudRate · 0 2400, 1 4800, 2 9600, 3 19200, 4 38400 baud. Default is 19200 when Modbus is selected. uint16 1 1 RW Holding (FC03)
8330 8329 Parity and stop bits (8-33)P8_33_Parity · 0 even with 1 stop bit (default), 1 odd, 2 no parity with 1 stop bit, 3 no parity with 2 stop bits. Affects Modbus only. uint16 1 1 RW Holding (FC03)
15000 14999 Time the drive has been powered (15-00)P15_00_OperatingTime uint32 2 days 1 R Holding (FC03)
15010 15009 Motor running hours (15-01)P15_01_RunningHours uint32 2 h 1 R Holding (FC03)
15020 15019 Energy counter (15-02)P15_02_kWhCounter · Range 0 to 65535 kWh. uint32 2 kWh 1 R Holding (FC03)
15030 15029 Number of power-ups (15-03)P15_03_PowerUps uint32 2 1 R Holding (FC03)
15300 15299 Fault log error code (15-30)P15_30_FaultLogErrorCode · Array parameter, pick the entry with the index pointer register 9. uint16 1 1 R Holding (FC03)
16000 15999 Control word as received (16-00)P16_00_ControlWord bitfield16 1 1 R Holding (FC03)
16010 16009 Reference in the reference unit (16-01)P16_01_Reference · Unit depends on the speed unit selection. int32 2 0.001 R Holding (FC03)
16020 16019 Reference in percent (16-02)P16_02_ReferencePct int16 1 % 0.1 R Holding (FC03)
16030 16029 Status word (16-03)P16_03_StatusWord bitfield16 1 1 R Holding (FC03)
16050 16049 Main actual value in percent (16-05)P16_05_MainActualValuePct int16 1 % 0.01 R Holding (FC03)
16100 16099 Output power (16-10)P16_10_PowerKW uint16 1 kW 0.001 R Holding (FC03)
16110 16109 Output power in horsepower (16-11)P16_11_PowerHP uint16 1 hp 0.001 R Holding (FC03)
16120 16119 Motor voltage (16-12)P16_12_MotorVoltage uint16 1 V 1 R Holding (FC03)
16130 16129 Output frequency (16-13)P16_13_Frequency uint16 1 Hz 0.1 R Holding (FC03)
16140 16139 Motor current (16-14)P16_14_MotorCurrent uint16 1 A 0.01 R Holding (FC03)
16150 16149 Output frequency in percent (16-15)P16_15_FrequencyPct uint16 1 % 0.1 R Holding (FC03)
16180 16179 Motor thermal load (16-18)P16_18_MotorThermal · Parameter data type is an 8-bit unsigned value. uint16 1 % 1 R Holding (FC03)
16300 16299 DC link voltage (16-30)P16_30_DCLinkVoltage uint16 1 V 1 R Holding (FC03)
16340 16339 Heatsink temperature (16-34)P16_34_HeatsinkTemp · Parameter data type is an 8-bit unsigned value. uint16 1 °C 1 R Holding (FC03)
16350 16349 Inverter thermal load (16-35)P16_35_InverterThermal · Parameter data type is an 8-bit unsigned value. uint16 1 % 1 R Holding (FC03)
16360 16359 Inverter nominal current (16-36)P16_36_InverterNominalCurrent uint16 1 A 0.01 R Holding (FC03)
16370 16369 Inverter maximum current (16-37)P16_37_InverterMaxCurrent uint16 1 A 0.01 R Holding (FC03)
16500 16499 External reference (16-50)P16_50_ExternalReference int16 1 % 0.1 R Holding (FC03)
16600 16599 Digital input states, terminals 18, 19, 27, 33 (16-60)P16_60_DigitalInputs bitfield16 1 1 R Holding (FC03)
16620 16619 Analog input 53 voltage (16-62)P16_62_AnalogInput53Volt uint16 1 V 0.01 R Holding (FC03)
16630 16629 Analog input 53 current (16-63)P16_63_AnalogInput53mA uint16 1 mA 0.01 R Holding (FC03)
16640 16639 Analog input 60 current (16-64)P16_64_AnalogInput60 uint16 1 mA 0.01 R Holding (FC03)
16650 16649 Analog output 42 value (16-65)P16_65_AnalogOutput42 uint16 1 mA 0.01 R Holding (FC03)
16710 16709 Relay output states (16-71)P16_71_RelayOutput · Parameter data type is an 8-bit unsigned value. bitfield16 1 1 R Holding (FC03)
16900 16899 Alarm word (16-90)P16_90_AlarmWord uint32 2 1 R Holding (FC03)
16920 16919 Warning word (16-92)P16_92_WarningWord uint32 2 1 R Holding (FC03)
16940 16939 Extended status word (16-94)P16_94_ExtendedStatusWord uint32 2 1 R Holding (FC03)
50000 49999 FC profile control wordControlWord · Same bit layout as register 2810. bitfield16 1 1 RW Holding (FC03)
50010 50009 Bus speed referenceBusReference · 16384 (4000h) is 100 percent of the reference range. int16 1 1 RW Holding (FC03)
50200 50199 FC profile status wordStatusWord · Same bit layout as register 2910. bitfield16 1 1 R Holding (FC03)
50210 50209 Main actual value, output frequencyMainActualValue · 16384 (4000h) is 100 percent. int16 1 1 R Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to AB CD.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: VLT Micro Drive FC 51 Design Guide (assets.danfoss.com)

Design Guide MG02K402, Danfoss A/S 01/2016. Parameter scales and data types from VLT Micro Drive FC 51 Programming Guide MG02C702, 12/2014, Design Guide p. 72-83; Programming Guide p. 57-63. Read on 2026-10-24.

Also used: VLT Micro Drive FC 51 Programming Guide (SW 3.1X) (assets.danfoss.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.

More from Danfoss

All Danfoss register maps

Other variable frequency drives

All register maps · Modbus addressing explained