Siemens SINAMICS G120 Modbus register map

Modular low-voltage AC converter family from Siemens. Control units with an RS485 port (such as the CU240B-2 and CU240E-2) can act as a Modbus RTU slave and expose process data, converter data, diagnostics and the technology controller through fixed holding registers.

Protocol
Modbus RTU (RS485)
Defaults
Modbus RTU is selected with p2030 = 2. The manual's Modbus settings list baud rate 19200 bit/s (p2020 = 7, range 4800 to 187500 bit/s) and states the converter is set at the factory for even parity (p2031 = 2). The address comes from the Control Unit address switch (1 to 127), or from p2021 (1 to 247, default 1) only when the switch is 0. An address change takes effect after a power cycle (p. 135-136).
Addresses in the manual
Modicon style numbers (for example 40001 is holding register 0)
32 and 64-bit values
Not stated in the manual
Registers listed
63
Checked against
A5E34229197B AG, Edition 11/2020, FW V4.7 SP13

Address base. Registers are printed in the 4xxxx style. The manual's request example for register 40110 puts 0x006D (109) in the start-address field and for register 40100 it uses 0x0063 (99), so the wire address is the printed number minus 40001 (p. 145, p. 147). For example 40100 in the manual (Control word (process data 1)) is address 99 on the wire.

Word order. Every register listed here is a single 16-bit register, so no multi-register word order applies to these rows.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

63 registers
Manual Wire Register Type Regs Unit Scale Access Area
40100 99 Control word (process data 1)ControlWord · Bit layout is given in the CU240B-2/CU240E-2 operating instructions, p. 212-213 (OFF1, OFF2, OFF3, enable operation, ramp controls, fault acknowledge, control from PLC, reversal, MOP up and down). bitfield16 1 1 RW Holding (FC03)
40101 100 Main setpoint (process data 2)MainSetpoint · Scaling is 1 as printed; the value is normalized to the reference speed (see register 40324). int16 1 1 RW Holding (FC03)
40110 109 Status word (process data 1)StatusWord · Bit layout is given in the operating instructions, p. 213-214 (ready, running, fault, OFF2 and OFF3 state, switch-on inhibit, alarm, speed in tolerance, direction). bitfield16 1 1 R Holding (FC03)
40111 110 Main actual value (process data 2)MainActualValue · Scaling is 1 as printed; the value is normalized to the reference speed. int16 1 1 R Holding (FC03)
40200 199 Digital output 0DigitalOutput0 · Maps to p0730, r0747.0 and p0748.0. bool 1 1 RW Holding (FC03)
40201 200 Digital output 1DigitalOutput1 · Maps to p0731, r0747.1 and p0748.1. bool 1 1 RW Holding (FC03)
40202 201 Digital output 2DigitalOutput2 · Maps to p0732, r0747.2 and p0748.2. bool 1 1 RW Holding (FC03)
40220 219 Analog output 0 actual valueAnalogOutputActual0 · Maps to r0774.0. Printed range -100.0 to 100.0 percent. int16 1 % 0.01 R Holding (FC03)
40221 220 Analog output 1 actual valueAnalogOutputActual1 · Maps to r0774.1. Printed range -100.0 to 100.0 percent. int16 1 % 0.01 R Holding (FC03)
40222 221 Analog output 2 actual valueAnalogOutputActual2 · Maps to r0774.2. Printed range -100.0 to 100.0 percent. int16 1 % 0.01 R Holding (FC03)
40523 522 Analog output 0 setpoint from fieldbusAnalogOutputWrite0 · Maps to p0791.0. Printed range -199.99 to 199.99 percent. With Modbus selected, registers 40523 and 40524 drive the analog outputs directly (p. 137). int16 1 % 0.01 RW Holding (FC03)
40524 523 Analog output 1 setpoint from fieldbusAnalogOutputWrite1 · Maps to p0791.1. Printed range -199.99 to 199.99 percent. With Modbus selected, registers 40523 and 40524 drive the analog outputs directly (p. 137). int16 1 % 0.01 RW Holding (FC03)
40525 524 Analog output 2 setpoint from fieldbusAnalogOutputWrite2 · Maps to p0791.2. Printed range -199.99 to 199.99 percent. With Modbus selected, registers 40523 and 40524 drive the analog outputs directly (p. 137). int16 1 % 0.01 RW Holding (FC03)
40240 239 Digital input 0DigitalInput0 · Maps to r0722.0. bool 1 1 R Holding (FC03)
40241 240 Digital input 1DigitalInput1 · Maps to r0722.1. bool 1 1 R Holding (FC03)
40242 241 Digital input 2DigitalInput2 · Maps to r0722.2. bool 1 1 R Holding (FC03)
40243 242 Digital input 3DigitalInput3 · Maps to r0722.3. bool 1 1 R Holding (FC03)
40244 243 Digital input 4DigitalInput4 · Maps to r0722.4. bool 1 1 R Holding (FC03)
40245 244 Digital input 5DigitalInput5 · Maps to r0722.5. bool 1 1 R Holding (FC03)
40260 259 Analog input 0AnalogInput0 · Maps to r0755[0]. Printed range -300.0 to 300.0 percent. int16 1 % 0.01 R Holding (FC03)
40261 260 Analog input 1AnalogInput1 · Maps to r0755[1]. Printed range -300.0 to 300.0 percent. int16 1 % 0.01 R Holding (FC03)
40262 261 Analog input 2AnalogInput2 · Maps to r0755[2]. Printed range -300.0 to 300.0 percent. int16 1 % 0.01 R Holding (FC03)
40263 262 Analog input 3AnalogInput3 · Maps to r0755[3]. Printed range -300.0 to 300.0 percent. int16 1 % 0.01 R Holding (FC03)
40300 299 Power stack numberPowerStackNumber · Maps to r0200. uint16 1 1 R Holding (FC03)
40301 300 Converter firmware versionFirmwareVersion · Maps to r0018 divided by 10000, for example 470. uint16 1 1 R Holding (FC03)
40320 319 Rated powerRatedPower · Maps to r0206. uint16 1 kW 0.01 R Holding (FC03)
40321 320 Current limitCurrentLimit · Maps to p0640. Printed range 10.0 to 400.0. uint16 1 A 0.1 RW Holding (FC03)
40322 321 Ramp-up timeRampUpTime · Maps to p1120. Printed range 0.00 to 650.0. uint16 1 s 0.01 RW Holding (FC03)
40323 322 Ramp-down timeRampDownTime · Maps to p1121. Printed range 0.00 to 650.0. uint16 1 s 0.01 RW Holding (FC03)
40324 323 Reference speedReferenceSpeed · Maps to p2000. Printed range 6 to 32767. uint16 1 rpm 1 RW Holding (FC03)
40340 339 Speed setpointSpeedSetpoint · Maps to r0020. int16 1 rpm 1 R Holding (FC03)
40341 340 Actual speedActualSpeed · Maps to r0022. int16 1 rpm 1 R Holding (FC03)
40342 341 Output frequencyOutputFrequency · Maps to r0024. int16 1 Hz 0.01 R Holding (FC03)
40343 342 Output voltageOutputVoltage · Maps to r0025. uint16 1 V 1 R Holding (FC03)
40344 343 DC link voltageDCLinkVoltage · Maps to r0026. uint16 1 V 1 R Holding (FC03)
40345 344 Current actual valueCurrentActual · Maps to r0027. uint16 1 A 0.01 R Holding (FC03)
40346 345 Actual torqueTorqueActual · Maps to r0031. int16 1 N·m 0.01 R Holding (FC03)
40347 346 Actual active powerActivePower · Maps to r0032. uint16 1 kW 0.01 R Holding (FC03)
40348 347 Energy consumptionEnergyConsumption · Maps to r0039. uint16 1 kWh 1 R Holding (FC03)
40349 348 Control priority (hand or auto)ControlPriority · Maps to r0807. uint16 1 1 R Holding (FC03)
40400 399 Fault number, index 0FaultNumber0 · Maps to r0947[0]. uint16 1 1 R Holding (FC03)
40401 400 Fault number, index 1FaultNumber1 · Maps to r0947[1]. uint16 1 1 R Holding (FC03)
40402 401 Fault number, index 2FaultNumber2 · Maps to r0947[2]. uint16 1 1 R Holding (FC03)
40403 402 Fault number, index 3FaultNumber3 · Maps to r0947[3]. uint16 1 1 R Holding (FC03)
40404 403 Fault number, index 4FaultNumber4 · Maps to r0947[4]. uint16 1 1 R Holding (FC03)
40405 404 Fault number, index 5FaultNumber5 · Maps to r0947[5]. uint16 1 1 R Holding (FC03)
40406 405 Fault number, index 6FaultNumber6 · Maps to r0947[6]. uint16 1 1 R Holding (FC03)
40407 406 Fault number, index 7FaultNumber7 · Maps to r0947[7]. uint16 1 1 R Holding (FC03)
40408 407 Alarm numberAlarmNumber · Maps to r2110[0]. uint16 1 1 R Holding (FC03)
40409 408 Actual alarm codeActualAlarmCode · Maps to r2132. uint16 1 1 R Holding (FC03)
40499 498 Parameter access error codePrmErrorCode · Internal error code for the last failed register write (p. 147). Printed range 0 to 255. uint16 1 1 R Holding (FC03)
40500 499 Technology controller enableTechCtrlEnable · Maps to p2200 and r2349.0. Values 0 or 1. uint16 1 1 RW Holding (FC03)
40501 500 Technology controller motorized potentiometer setpointTechCtrlMOP · Maps to p2240. Printed range -200.0 to 200.0 percent. int16 1 % 0.01 RW Holding (FC03)
40510 509 Actual value filter time constantTechCtrlActualFilterTime · Maps to p2265. Printed range 0.00 to 60.0. uint16 1 0.01 RW Holding (FC03)
40511 510 Actual value scaling factorTechCtrlActualScale · Maps to p2269. Printed range 0.00 to 500.00. uint16 1 % 0.01 RW Holding (FC03)
40512 511 Proportional gainTechCtrlProportionalGain · Maps to p2280. Printed range 0.000 to 65.000. uint16 1 0.001 RW Holding (FC03)
40513 512 Integral timeTechCtrlIntegralTime · Maps to p2285. Printed range 0 to 60. uint16 1 s 1 RW Holding (FC03)
40514 513 Derivative time constantTechCtrlDerivativeTime · Maps to p2274. Printed range 0 to 60. uint16 1 1 RW Holding (FC03)
40515 514 Output upper limitTechCtrlMaxLimit · Maps to p2291. Printed range -200.0 to 200.0 percent. int16 1 % 0.01 RW Holding (FC03)
40516 515 Output lower limitTechCtrlMinLimit · Maps to p2292. Printed range -200.0 to 200.0 percent. int16 1 % 0.01 RW Holding (FC03)
40520 519 Effective setpoint after rampTechCtrlEffectiveSetpoint · Maps to r2250. int16 1 % 0.01 R Holding (FC03)
40521 520 Actual value after filterTechCtrlActualFiltered · Maps to r2266. int16 1 % 0.01 R Holding (FC03)
40522 521 Technology controller outputTechCtrlOutput · Maps to r2294. int16 1 % 0.01 R Holding (FC03)

Scale is the number to multiply the raw value by to get the unit.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: SINAMICS G120, G120P, G120C, G120D, G110M, G115D Fieldbuses Function Manual (cache.industry.siemens.com)

A5E34229197B AG, Edition 11/2020, FW V4.7 SP13, p. 133-147. Read on 2026-10-24.

Also used: Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions 01/2017, FW V4.7 SP6 (control and status word bit tables, Modbus RTU settings) (cache.industry.siemens.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.