Siemens SENTRON PAC2200 Modbus register map

Compact three-phase power monitoring device for low-voltage networks. It reports voltages, currents, power, power factor, frequency, two-tariff energy counters per phase and in total, and has diagnostics, settings and I&M identification data. Depending on the version it has an Ethernet port (Modbus TCP), an RS485 port (Modbus RTU) or M-BUS.

Protocol
Modbus TCP (Ethernet versions) or Modbus RTU (RS485 versions)
Defaults
Modbus TCP port 502 (setting range 0 to 65534). Modbus RTU (RS485 versions only): address 126 (range 1 to 247), 19200 baud (4800, 9600, 19200, 38400, 57600, 115200), format 8N2 (8N1, 8N2, 8E1, 8O1), response time 0 ms (all p. 81 to 82). DHCP is on at the factory. Function codes supported: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F, 0x10, 0x14, 0x2B (p. 103).
Addresses in the manual
0-based protocol addresses, as sent on the wire
32 and 64-bit values
Not stated in the manual
Registers listed
185
Checked against
L1V30415167B-06, edition 12/2022 (Siemens-hosted copy, Entry ID 109746835)

Address base. NOT proven by the manual. The manual lists an Offset for each value (the first voltage is offset 1, a two-register value starts at each odd offset), does not state how the offset maps to the Modbus start address, and prints no example frame. Zero-based (wire address = printed offset) is an assumption, supported only indirectly: the offsets match those of the SENTRON PAC3200 (for example voltages at 1, 3, 5 and total active power at 65), and Siemens' S7-1200 application example for the PAC3200 (Entry ID 40614428) reads total active power at 40001 + 65, which is holding register 65 in zero-based terms. That example is for the PAC3200, not this device. Counter-evidence: in the file-record tables (function code 0x14, p. 110 onward) the manual prints offset 1 next to the address 30001 and offset 257 next to 30257, which read as one-based Modicon numbers, but those tables are a separate record layout and do not prove how Table A-3 offsets map. If values look shifted by one register on the PAC2200, read 2 registers from offset 1 and compare with the display. A read that starts in the middle of a multi-register value returns an exception, as the manual states. Registers marked area coil are the bit parameters of Table A-6 (function codes 0x01, 0x02, 0x05, 0x0F); the manual prints them with 0 registers and does not say whether their offsets are coil addresses counted from 0 or 1, so the same offset assumption applies. Address 1 in the manual is address 1 on the wire.

Word order. The manual does not state the word or byte order of the 32-bit unsigned long, 32-bit float and 64-bit double values (it states big endian only for the object ID used with function code 0x14). Read each value from its own start offset with the full number of registers. The manual lists the same energies a second time as 32-bit floats at offsets 2801 to 2883, but prints inconsistent units for that block, so only the 64-bit double block at 801 to 965 is listed here. The current period values at 545 to 597, the file-record data (function code 0x14, A.1.4 to A.1.6) and the user-defined function 0x64 are not listed.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

185 registers
Manual Wire Register Type Regs Unit Scale Access Area
1 1 Voltage L1 to neutralVoltage_L1N float32 2 V 1 R Holding (FC03)
3 3 Voltage L2 to neutralVoltage_L2N float32 2 V 1 R Holding (FC03)
5 5 Voltage L3 to neutralVoltage_L3N float32 2 V 1 R Holding (FC03)
7 7 Voltage L1 to L2Voltage_L1L2 float32 2 V 1 R Holding (FC03)
9 9 Voltage L2 to L3Voltage_L2L3 float32 2 V 1 R Holding (FC03)
11 11 Voltage L3 to L1Voltage_L3L1 float32 2 V 1 R Holding (FC03)
13 13 Current L1Current_L1 float32 2 A 1 R Holding (FC03)
15 15 Current L2Current_L2 float32 2 A 1 R Holding (FC03)
17 17 Current L3Current_L3 float32 2 A 1 R Holding (FC03)
19 19 Apparent power L1Apparent_Power_L1 float32 2 VA 1 R Holding (FC03)
21 21 Apparent power L2Apparent_Power_L2 float32 2 VA 1 R Holding (FC03)
23 23 Apparent power L3Apparent_Power_L3 float32 2 VA 1 R Holding (FC03)
25 25 Active power L1Active_Power_L1 float32 2 W 1 R Holding (FC03)
27 27 Active power L2Active_Power_L2 float32 2 W 1 R Holding (FC03)
29 29 Active power L3Active_Power_L3 float32 2 W 1 R Holding (FC03)
31 31 Reactive power L1Reactive_Power_L1 float32 2 var 1 R Holding (FC03)
33 33 Reactive power L2Reactive_Power_L2 float32 2 var 1 R Holding (FC03)
35 35 Reactive power L3Reactive_Power_L3 float32 2 var 1 R Holding (FC03)
37 37 Power factor L1Power_Factor_L1 · Value range 0 to 1 as printed. float32 2 1 R Holding (FC03)
39 39 Power factor L2Power_Factor_L2 · Value range 0 to 1 as printed. float32 2 1 R Holding (FC03)
41 41 Power factor L3Power_Factor_L3 · Value range 0 to 1 as printed. float32 2 1 R Holding (FC03)
55 55 FrequencyFrequency · Value range 45 to 65 as printed. float32 2 Hz 1 R Holding (FC03)
57 57 Average voltage line to neutralAverage_Voltage_LN float32 2 V 1 R Holding (FC03)
59 59 Average voltage line to lineAverage_Voltage_LL float32 2 V 1 R Holding (FC03)
61 61 Average currentAverage_Current float32 2 A 1 R Holding (FC03)
63 63 Total apparent powerTotal_Apparent_Power float32 2 VA 1 R Holding (FC03)
65 65 Total active powerTotal_Active_Power float32 2 W 1 R Holding (FC03)
67 67 Total reactive powerTotal_Reactive_Power float32 2 var 1 R Holding (FC03)
69 69 Total power factorTotal_Power_Factor float32 2 1 R Holding (FC03)
71 71 Neutral currentNeutral_Current float32 2 A 1 R Holding (FC03)
205 205 Device diagnostics and device statusDevice_Diagnostics_Status · Byte 0 = global state, byte 1 = local state, byte 2 = global diagnostics, as printed. Bit masks in the 32-bit value are listed in Table A-5 (p. 128), for example 0x01000000 no synchronization pulse, 0x04000000 voltage overload, 0x08000000 current overload, 0x40000000 hardware write protection active, 0x80000000 Modbus communication write-protected. Bits are acknowledged with command register 60007. uint32 2 1 R Holding (FC03)
207 207 Status of the digital outputsDigital_Output_Status · Byte 3, bit 0 (mask 0x00000001) = digital output 0. uint32 2 1 R Holding (FC03)
209 209 Status of the digital inputsDigital_Input_Status · Byte 3, bit 0 (mask 0x00000001) = digital input 0. uint32 2 1 R Holding (FC03)
211 211 Active tariffActive_Tariff · 0 = tariff 1, 1 = tariff 2. uint32 2 1 R Holding (FC03)
215 215 Universal counterUniversal_Counter · Value range 0 to 999999999 as printed. uint32 2 1 RW Holding (FC03)
217 217 Relevant parameter changes counterRelevant_Parameter_Changes_Counter uint32 2 1 R Holding (FC03)
219 219 Counter of all parameter changesAll_Parameter_Changes_Counter uint32 2 1 R Holding (FC03)
231 231 Configurable energy counterConfigurable_Energy_Counter · The table prints the unit as kWh, kvarh. Setting 50051 (configurable counter source) is printed with the value 0 = digital input. float32 2 kWh or kvarh 1 R Holding (FC03)
265 265 Daily profile counterDaily_Profile_Counter uint32 2 1 R Holding (FC03)
267 267 Monthly profile counterMonthly_Profile_Counter uint32 2 1 R Holding (FC03)
269 269 Annual profile counterAnnual_Profile_Counter uint32 2 1 R Holding (FC03)
501 501 Cumulated average active power importCumulated_Avg_Active_Power_Import float32 2 W 1 R Holding (FC03)
503 503 Cumulated average reactive power importCumulated_Avg_Reactive_Power_Import float32 2 var 1 R Holding (FC03)
505 505 Cumulated average active power exportCumulated_Avg_Active_Power_Export float32 2 W 1 R Holding (FC03)
507 507 Cumulated average reactive power exportCumulated_Avg_Reactive_Power_Export float32 2 var 1 R Holding (FC03)
509 509 Maximum active power reading during the periodMax_Active_Power_In_Period float32 2 W 1 R Holding (FC03)
511 511 Minimum active power reading during the periodMin_Active_Power_In_Period float32 2 W 1 R Holding (FC03)
513 513 Maximum reactive power reading during the periodMax_Reactive_Power_In_Period float32 2 var 1 R Holding (FC03)
515 515 Minimum reactive power reading during the periodMin_Reactive_Power_In_Period float32 2 var 1 R Holding (FC03)
517 517 Length of the current measuring periodCurrent_Period_Length uint32 2 s 1 R Holding (FC03)
519 519 Time since start of the active demand periodTime_Since_Demand_Period_Start uint32 2 s 1 R Holding (FC03)
799 799 Date and time (UTC)Date_Time_UTC · Printed format Unix_ts (Unix time stamp). The manual does not state the epoch unit. uint32 2 1 RW Holding (FC03)
801 801 Active energy import tariff 1Active_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
805 805 Active energy import tariff 2Active_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
809 809 Active energy export tariff 1Active_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
813 813 Active energy export tariff 2Active_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
817 817 Reactive energy import tariff 1Reactive_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
821 821 Reactive energy import tariff 2Reactive_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
825 825 Reactive energy export tariff 1Reactive_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
829 829 Reactive energy export tariff 2Reactive_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
833 833 Apparent energy tariff 1Apparent_Energy_T1 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
837 837 Apparent energy tariff 2Apparent_Energy_T2 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
841 841 L1 active energy import tariff 1L1_Active_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
845 845 L1 active energy import tariff 2L1_Active_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
849 849 L1 active energy export tariff 1L1_Active_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
853 853 L1 active energy export tariff 2L1_Active_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
857 857 L1 reactive energy import tariff 1L1_Reactive_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
861 861 L1 reactive energy import tariff 2L1_Reactive_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
865 865 L1 reactive energy export tariff 1L1_Reactive_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
869 869 L1 reactive energy export tariff 2L1_Reactive_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
873 873 L1 apparent energy tariff 1L1_Apparent_Energy_T1 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
877 877 L1 apparent energy tariff 2L1_Apparent_Energy_T2 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
881 881 L2 active energy import tariff 1L2_Active_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
885 885 L2 active energy import tariff 2L2_Active_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
889 889 L2 active energy export tariff 1L2_Active_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
893 893 L2 active energy export tariff 2L2_Active_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
897 897 L2 reactive energy import tariff 1L2_Reactive_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
901 901 L2 reactive energy import tariff 2L2_Reactive_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
905 905 L2 reactive energy export tariff 1L2_Reactive_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
909 909 L2 reactive energy export tariff 2L2_Reactive_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
913 913 L2 apparent energy tariff 1L2_Apparent_Energy_T1 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
917 917 L2 apparent energy tariff 2L2_Apparent_Energy_T2 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
921 921 L3 active energy import tariff 1L3_Active_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
925 925 L3 active energy import tariff 2L3_Active_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
929 929 L3 active energy export tariff 1L3_Active_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
933 933 L3 active energy export tariff 2L3_Active_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 Wh 1 R Holding (FC03)
937 937 L3 reactive energy import tariff 1L3_Reactive_Energy_Import_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
941 941 L3 reactive energy import tariff 2L3_Reactive_Energy_Import_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
945 945 L3 reactive energy export tariff 1L3_Reactive_Energy_Export_T1 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
949 949 L3 reactive energy export tariff 2L3_Reactive_Energy_Export_T2 · Overflow at 1.0e+12 as printed. float64 4 varh 1 R Holding (FC03)
953 953 L3 apparent energy tariff 1L3_Apparent_Energy_T1 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
957 957 L3 apparent energy tariff 2L3_Apparent_Energy_T2 · Overflow at 1.0e+12 as printed. float64 4 VAh 1 R Holding (FC03)
961 961 Secondary total of active energy import (MID register)Secondary_Total_Active_Energy_Import_MID float64 4 Wh 1 R Holding (FC03)
965 965 Secondary total of active energy export (MID register)Secondary_Total_Active_Energy_Export_MID float64 4 Wh 1 R Holding (FC03)
108 108 Relevant parameter changesRelevant_Parameter_Changes_Flag · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. Writable bits (RW) are changed with function codes 0x05 and 0x0F. bool 1 1 RW Coil (FC01)
110 110 Maximum pulse rate exceeded (acknowledgeable flag)Max_Pulse_Rate_Exceeded_Saving_Flag · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. Writable bits (RW) are changed with function codes 0x05 and 0x0F. bool 1 1 RW Coil (FC01)
111 111 Restart of the deviceDevice_Restart_Flag · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. Writable bits (RW) are changed with function codes 0x05 and 0x0F. bool 1 1 RW Coil (FC01)
112 112 Resetting of energy counter by userEnergy_Counter_Reset_Flag · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. Writable bits (RW) are changed with function codes 0x05 and 0x0F. bool 1 1 RW Coil (FC01)
117 117 Maximum pulse rate exceeded (status)Max_Pulse_Rate_Exceeded_Status · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
122 122 SNTP not synchronizedSNTP_Not_Synchronized · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
123 123 Wait for user actionWait_For_User_Action · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
124 124 No synchronization pulseNo_Synchronization_Pulse · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
125 125 Device configuration menu is activeConfig_Menu_Active · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
126 126 Voltage overloadVoltage_Overload · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
127 127 Current overloadCurrent_Overload · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
128 128 Date/time inaccurateDate_Time_Inaccurate · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
130 130 The device is hardware write-protectedHardware_Write_Protected · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
131 131 Modbus communication is write-protectedModbus_Write_Protected · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
200 200 Digital input 0Digital_Input_0 · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
300 300 Digital output 0Digital_Output_0 · Bit status, read with function code 0x01 or 0x02; 0 = not active, 1 = active. bool 1 1 R Coil (FC01)
49999 49999 Rated current display rangeRated_Current_Display_Range · Value range 1 to 10000 as printed. uint32 2 A 1 RW Holding (FC03)
50001 50001 Connection typeConnection_Type · 0 = 3P4W, 4 = 1P2W. uint32 2 1 RW Holding (FC03)
50011 50011 Primary currentPrimary_Current · Printed range 1 to 99999 A for the 5 A device, 65 A for the 65 A device. Read/write on the 5 A device, read only on the 65 A device. uint32 2 A 1 RW Holding (FC03)
50013 50013 Secondary currentSecondary_Current · Printed values 1 A or 5 A for the 5 A device, 65 A for the 65 A device. Read/write on the 5 A device, read only on the 65 A device. uint32 2 A 1 RW Holding (FC03)
50021 50021 Load profile demand periodLoad_Profile_Demand_Period · Printed values 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60. uint32 2 min 1 R Holding (FC03)
50023 50023 SynchronizationSynchronization · 0 = no synchronization, 1 = via bus, 2 = via digital input, 3 = via internal clock. uint32 2 1 R Holding (FC03)
50025 50025 Digital input usage typeDI_Usage_Type · 0 = no action, 1 = pulse interface, 2 = switching on/off peak, 3 = synchronization, 4 = display backlight. uint32 2 1 RW Holding (FC03)
50029 50029 Digital input indexDI_Index · 0 = kWh, 1 = kvarh. uint32 2 1 RW Holding (FC03)
50031 50031 Digital input pulses per kWh or kvarhDI_Pulses_Per_kWh_kvarh · Value range 1 to 4000 as printed. uint32 2 1 RW Holding (FC03)
50033 50033 Digital output group assignmentDO_Group_Assignment · Value range 0 to 99. The table prints the name as DI group assignment in the digital output table. uint32 2 1 RW Holding (FC03)
50035 50035 Digital output usage typeDO_Usage_Type · 0 = no action, 1 = device active, 2 = switching output, 3 = direction of rotation, 5 = pulse output. uint32 2 1 RW Holding (FC03)
50041 50041 Digital output indexDO_Index · 0 = import kWh, 1 = export kWh, 2 = import kvarh, 3 = export kvarh. uint32 2 1 RW Holding (FC03)
50043 50043 Digital output pulses per kWh or kvarhDO_Pulses_Per_kWh_kvarh · Value range 1 to 4000 as printed. uint32 2 1 RW Holding (FC03)
50045 50045 Digital output pulse lengthDO_Pulse_Length · Value range 30 to 500 as printed. The table prints no unit. uint32 2 1 RW Holding (FC03)
50047 50047 Dialog languageDialog_Language · 0 = German, 1 = English. uint32 2 1 RW Holding (FC03)
50049 50049 Phase labels EU/USPhase_Labels · 0 = IEC, 1 = US. uint32 2 1 RW Holding (FC03)
50051 50051 Configurable counter sourceConfigurable_Counter_Source · 0 = digital input. uint32 2 1 RW Holding (FC03)
50055 50055 Display contrastDisplay_Contrast · Value range 1 to 10. uint32 2 1 RW Holding (FC03)
50057 50057 Display backlight level (normal mode)Display_Backlight_Normal · Value range 0 to 3 as printed. The table prints the unit % but the range is 0 to 3, so it is a level setting, not a percentage. uint32 2 % 1 RW Holding (FC03)
50059 50059 Display backlight level (dimmed mode)Display_Backlight_Dimmed · Value range 0 to 3 as printed. The table prints the unit % but the range is 0 to 3, so it is a level setting, not a percentage. uint32 2 % 1 RW Holding (FC03)
50061 50061 Time until dimmedTime_Until_Dimmed · Value range 0 to 99. uint32 2 min 1 RW Holding (FC03)
50147 50147 Digital output remote timeoutDO_Timeout · Table A-7 prints 1 to 18000 seconds with 0 disabling the timeout (default) and no unit; Table A-9 prints unit s with 0 = off and 0.1 to 18000 (output reset after the time expires with no operator input). The two tables differ on the lower bound. uint32 2 s 1 RW Holding (FC03)
50149 50149 Default menu numberDefault_Menu_Number · 1 = MEAS_VLN, 2 = MEAS_VLL, 3 = MEAS_I, 4 = MEAS_S, 5 = MEAS_P, 6 = MEAS_Q, 7 = MEAS_SPQ, 8 = MEAS_PF, 9 = MEAS_F, 10 = MEAS_WORK_P, 11 = MEAS_WORK_Q, 12 = MEAS_WORK_S. uint32 2 1 RW Holding (FC03)
50151 50151 Timeout for return to default menuTimeout_Return_To_Default_Menu · 0 = no timeout; 10 s to 3600 s. A value from 1 s up to below 10 s is set to 10 s. uint32 2 s 1 RW Holding (FC03)
50231 50231 Date formatDate_Format · 0 = dd.mm.yyyy, 1 = mm/dd/yy, 2 = yyyy-mm-dd. uint32 2 1 RW Holding (FC03)
50233 50233 Daylight savingDaylight_Saving · 0 = no, 1 = auto EU, 2 = auto US, 3 = daylight saving table. uint32 2 1 RW Holding (FC03)
50235 50235 Time zoneTime_Zone · Printed format long (signed); value must be a multiple of 30. int32 2 min 1 RW Holding (FC03)
50237 50237 Output pulse dividerOutput_Pulse_Divider · 0 = 1 kWh, 1 = 10 kWh, 2 = 100 kWh, 3 = 1000 kWh. uint32 2 1 RW Holding (FC03)
50239 50239 Input pulse dividerInput_Pulse_Divider · 0 = 1 kWh, 1 = 10 kWh, 2 = 100 kWh, 3 = 1000 kWh. uint32 2 1 RW Holding (FC03)
50241 50241 Invert displayInvert_Display · 0 = no, 1 = yes. uint32 2 1 RW Holding (FC03)
50243 50243 Change current L1 directionChange_Current_L1_Direction · 0 = no, 1 = yes. uint32 2 1 RW Holding (FC03)
50245 50245 Change current L2 directionChange_Current_L2_Direction · 0 = no, 1 = yes. uint32 2 1 RW Holding (FC03)
50247 50247 Change current L3 directionChange_Current_L3_Direction · 0 = no, 1 = yes. uint32 2 1 RW Holding (FC03)
50249 50249 I(N) on displayIN_On_Display · 0 = no, 1 = yes. uint32 2 1 RW Holding (FC03)
62983 62983 Aggregation file 1 period lengthAggregation_File_1_Period_Length · Printed range: greater than 3 s, an integer divider of a minute, an hour or a day. uint32 2 1 RW Holding (FC03)
62985 62985 Aggregation file 1 methodAggregation_File_1_Method · 0 = AUTO, 1 = RMS, 2 = ARITHMETIC. uint32 2 1 RW Holding (FC03)
62987 62987 Aggregation file 2 period lengthAggregation_File_2_Period_Length · Printed range: preferred integer multiplier of the stage (-1) period length, and an integer divider of a minute, an hour or a day. uint32 2 1 RW Holding (FC03)
62989 62989 Aggregation file 2 methodAggregation_File_2_Method · 0 = AUTO, 1 = RMS, 2 = ARITHMETIC. uint32 2 1 RW Holding (FC03)
62991 62991 DHCP on/offDHCP_Enable · Value range 0 to 1 as printed; the manual does not state which value is on. uint32 2 1 RW Holding (FC03)
62993 62993 SNTP server IP addressSNTP_Server_IP · Value range 0 to FFFFFFFFh. uint32 2 1 RW Holding (FC03)
62995 62995 SNTP client modeSNTP_Client_Mode · 0 = SNTP client off, 1 = SNTP active client, 2 = SNTP broadcast client. uint32 2 1 RW Holding (FC03)
62997 62997 Subnet firewall on/offSubnet_Firewall · No value range is printed. uint32 2 1 RW Holding (FC03)
63001 63001 IP addressIP_Address · Value range 0 to FFFFFFFFh. uint32 2 1 RW Holding (FC03)
63003 63003 Subnet maskSubnet_Mask · Value range 0 to FFFFFFFFh. uint32 2 1 RW Holding (FC03)
63005 63005 GatewayGateway · Value range 0 to FFFFFFFFh. uint32 2 1 RW Holding (FC03)
63007 63007 Bootloader versionBootloader_Version · Printed value range: char, uchar, uchar, uchar (one byte each). uint32 2 1 R Holding (FC03)
63009 63009 Password protection on/offPassword_Protection · 0 or 1 as printed. uint32 2 1 R Holding (FC03)
63135 63135 Modbus RTU addressModbus_RTU_Address · Range 1 to 247. Only on devices with an RS485 port. uint32 2 1 RW Holding (FC03)
63137 63137 Modbus RTU baud rateModbus_RTU_Baud_Rate · 0 = 4800, 1 = 9600, 2 = 19200, 3 = 38400, 4 = 57600, 5 = 115200 baud. Only on devices with an RS485 port. uint32 2 1 RW Holding (FC03)
63139 63139 Modbus RTU data bits, parity and stop bitsModbus_RTU_Format · 0 = 8N2, 1 = 8E1, 2 = 8O1, 3 = 8N1. Only on devices with an RS485 port. uint32 2 1 RW Holding (FC03)
63141 63141 Modbus RTU response timeModbus_RTU_Response_Time · Range 0 to 255. Only on devices with an RS485 port. uint32 2 ms 1 RW Holding (FC03)
63143 63143 HTTP server port numberHTTP_Server_Port · 0 = off. uint32 2 1 RW Holding (FC03)
65290 65290 Hardware write protection on/offHardware_Write_Protection · 0 = on, 1 = off, as printed. Written with function code 0x10; requires pressing the SW key on the device. uint32 2 1 RW Holding (FC03)
64001 64001 I&M0 manufacturer IDIM0_Manufacturer_ID · Printed value 42, which stands for Siemens AG. I&M0 is read as a whole block of 27 registers starting at 64001. uint16 1 1 R Holding (FC03)
64002 64002 I&M0 order numberIM0_Order_Number · ASCII, 20 characters. string 10 1 R Holding (FC03)
64012 64012 I&M0 serial numberIM0_Serial_Number · ASCII, 16 characters. string 8 1 R Holding (FC03)
64020 64020 I&M0 hardware versionIM0_Hardware_Version · Value range 0 to 65535. uint16 1 1 R Holding (FC03)
64021 64021 I&M0 firmware versionIM0_Firmware_Version · Printed format: 1 char followed by 3 unsigned char, value range V 0.0.0 to V 255.255.255. Four bytes in 2 registers; the manual does not give the byte layout. string 2 1 R Holding (FC03)
64023 64023 I&M0 counter for changesIM0_Change_Counter · Value range 1 to 65535. uint16 1 1 R Holding (FC03)
64024 64024 I&M0 profile IDIM0_Profile_ID · Printed value range 3A00 to F6FF. uint16 1 1 R Holding (FC03)
64025 64025 I&M0 specific profile IDIM0_Specific_Profile_ID uint16 1 1 R Holding (FC03)
64026 64026 I&M0 version of the I&M dataIM0_Version · Two unsigned chars, value range 0.0 to 255.255. uint16 1 1 R Holding (FC03)
64027 64027 I&M0 supported I&M dataIM0_Supported_IM_Data · Printed value range 00 to FF. uint16 1 1 R Holding (FC03)
64028 64028 I&M1 plant identifierIM1_Plant_Identifier · ASCII, 32 characters. I&M1 to I&M4 are read or written as a whole block of 89 registers starting at 64028. string 16 1 RW Holding (FC03)
64044 64044 I&M1 location identifierIM1_Location_Identifier · ASCII, 22 characters. string 11 1 RW Holding (FC03)
64055 64055 I&M2 installation dateIM2_Installation_Date · ASCII, 16 characters. string 8 1 RW Holding (FC03)
64063 64063 I&M3 commentIM3_Comment · ASCII, 54 characters. string 27 1 RW Holding (FC03)
64090 64090 I&M4 signatureIM4_Signature · 54 characters; the manual prints no value range. string 27 1 RW Holding (FC03)
60000 60000 Reset the device to factory settingsCmd_Factory_Reset · Single register command, written with function code 0x06. uint16 1 1 W Holding (FC03)
60001 60001 Device reset (without changing the Modbus address)Cmd_Device_Reset · Single register command, written with function code 0x06. uint16 1 1 W Holding (FC03)
60005 60005 Load profile synchronizationCmd_Load_Profile_Sync · Single register command, written with function code 0x06. Minutes. Printed values 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60. uint16 1 1 W Holding (FC03)
60006 60006 Switching tariffCmd_Switch_Tariff · Single register command, written with function code 0x06. 0 = main tariff, 1 = secondary tariff. uint16 1 1 W Holding (FC03)
60007 60007 Acknowledge the diagnostics bitsCmd_Acknowledge_Diagnostics · Single register command, written with function code 0x06. Value range 0 to FFFFh. The Modbus master must acknowledge the diagnostics bits stored in the register at offset 205. uint16 1 1 W Holding (FC03)
60008 60008 Switching outputs (if parameterized)Cmd_Switch_Outputs · Single register command, written with function code 0x06. Printed value range 0FFh to 1FFh: byte 0 selects the digital output (printed as 0.0), byte 1 = 0 switches OFF and 1 switches ON. uint16 1 1 W Holding (FC03)
60009 60009 Switching command for vector groupCmd_Switch_Vector_Group · Single register command, written with function code 0x06. High byte = group assignment 0 to 99, low byte = 1 for ON or 0 for OFF. uint16 1 1 W Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: SENTRON 7KM Power Monitoring Device PAC2200 Equipment Manual (cache.industry.siemens.com)

L1V30415167B-06, edition 12/2022 (Siemens-hosted copy, Entry ID 109746835), p. 81-82 (communication defaults), p. 103-137 (Appendix A.1 Modbus). Read on 2026-10-24.

Also used: PAC2200 measuring device manual, Entry ID 109746835 (support.industry.siemens.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.