Schneider Electric ATV312 Modbus register map

Variable speed drive for asynchronous motors. The communication variables listed here cover the control and status words, frequency and speed references, motor measurements, fault codes, ramp and motor settings, and the Modbus line parameters.

Protocol
Modbus RTU
Defaults
Modbus RTU through the RJ45 port. Factory settings: drive address 1 (range 1 to 247), 19200 bps, 8 data bits with even parity and 1 stop bit (8E1), time-out 10 s (Modbus manual BBV52816, p. 9). The remote display terminal only works with 19200 bps and 8E1.
Addresses in the manual
0-based protocol addresses, as sent on the wire
32 and 64-bit values
Low word first (CD AB)
Registers listed
49
Checked against
BBV51701 06/2009

Address base. The variables manual (p. 7) lists each Modbus address in decimal. The companion Modbus manual (BBV52816, p. 12) shows a read of words W3102 to W3105 sent with start address 16#0C1E, which is 3102, so the printed decimal address is the address sent in the Modbus frame. Address 8601 in the manual is address 8601 on the wire.

Word order. Almost every variable is a single 16-bit word. The only 32-bit value is the motor speed in customer units, split into a low word at 12002 and a high word at 12003, so the low word comes first.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

49 registers
Manual Wire Register Type Regs Unit Scale Access Area
8601 8601 IEC 61800-7 control wordCMDD · Identical to CMD. Bit 0 switch on, bit 1 disable voltage (active at 0), bit 2 quick stop (active at 0), bit 3 enable operation, bit 7 fault reset on a rising edge. bitfield16 1 1 RW Holding (FC03)
8602 8602 Speed reference via the busLFRD · Signed. 1 = 1 rpm when bit 9 of CMI is 0; when bit 9 of CMI is 1 one count is about 0.018 Hz (32767 points = 600 Hz). int16 1 rpm 1 RW Holding (FC03)
8603 8603 IEC 61800-7 status wordETAD · Identical to ETA. bitfield16 1 1 R Holding (FC03)
8605 8605 Speed reference at ramp inputFRHD · Signed value. int16 1 rpm 1 R Holding (FC03)
8604 8604 Output speedRFRD · Signed. 1 = 1 rpm when bit 9 of CMI is 0; about 0.018 Hz per count when bit 9 of CMI is 1. int16 1 rpm 1 R Holding (FC03)
8606 8606 Fault codeERRD · Error code; for example 0x0000 = no fault saved, 0x2310 = overcurrent. The manual lists the full code table. uint16 1 1 R Holding (FC03)
8501 8501 Control wordCMD · Bit 0 switch on, bit 1 disable voltage (active at 0), bit 2 quick stop (active at 0), bit 3 enable operation, bit 7 fault reset on a rising edge, bit 11 direction (0 forward, 1 reverse). The manual lists the examples 0x000F forward run, 0x080F reverse run, 0x400F fast stop. bitfield16 1 1 RW Holding (FC03)
8502 8502 Frequency reference via the busLFr · Signed. 1 = 0.1 Hz when bit 9 of CMI is 0; about 0.018 Hz per count when bit 9 of CMI is 1. int16 1 Hz 0.1 RW Holding (FC03)
8503 8503 PI regulator reference via the busPISP · Range 0 to 1000. uint16 1 % 0.1 RW Holding (FC03)
8504 8504 Extended control wordCMI · Bit 1 saves configuration to EEPROM, bit 9 selects high resolution references, bit 14 disables Modbus communication monitoring. See the manual before writing. bitfield16 1 1 RW Holding (FC03)
5240 5240 Logic I/O valueIOLR · Bits 8, 9 and 10 give relay R1, relay R2 and logic output LO, writable only when the output is not assigned. bitfield16 1 1 RW Holding (FC03)
5261 5261 Analog output valueAO1R · Range 0 to 10000; 10000 corresponds to 10 V or 20 mA depending on the analog output type. Writable only when the analog output is not assigned. uint16 1 1 RW Holding (FC03)
3201 3201 Status wordETA · Bit 0 ready to switch on, bit 1 switched on, bit 2 operation enabled, bit 3 fault, bit 5 quick stop, bit 6 switch on disabled, bit 7 alarm, bit 10 reference reached, bit 15 reverse rotation. bitfield16 1 1 R Holding (FC03)
3202 3202 Output frequencyrFr · Signed. 1 = 0.1 Hz when bit 9 of CMI is 0; about 0.018 Hz per count when bit 9 of CMI is 1. int16 1 Hz 0.1 R Holding (FC03)
3203 3203 Frequency reference before rampFrH · Absolute value. uint16 1 Hz 0.1 R Holding (FC03)
3204 3204 Motor currentLCr uint16 1 A 0.1 R Holding (FC03)
3205 3205 Motor torqueOtr · 100 % is the nominal motor torque. The manual does not state whether the value is signed. uint16 1 % 1 R Holding (FC03)
3211 3211 Motor powerOPr · 100 % is the nominal motor power. The manual does not state whether the value is signed. uint16 1 % 1 R Holding (FC03)
3207 3207 Line voltageULn · Measured through the DC bus, motor running or stopped. uint16 1 V 0.1 R Holding (FC03)
3209 3209 Drive thermal statetHd · 100 % is the nominal thermal state; 118 % is the drive overheating threshold. uint16 1 % 1 R Holding (FC03)
3210 3210 Maximum drive thermal state reachedTDM · Reset to zero when the drive is powered down. uint16 1 % 1 R Holding (FC03)
9630 9630 Motor thermal statetHr · 100 % is the nominal thermal state; 118 % is the motor overload threshold. uint16 1 % 1 R Holding (FC03)
3231 3231 Operating timertH · Total time the motor has been powered up. uint16 1 h 1 R Holding (FC03)
3206 3206 Extended status wordETI · Bit 0 = 1 means writing parameters is not authorized while the drive saves to EEPROM. bitfield16 1 1 R Holding (FC03)
12002 12002 Motor speed in customer units, low wordUSPL · Low order word of a 32-bit value equal to rFr x SdS. uint16 1 1 R Holding (FC03)
12003 12003 Motor speed in customer units, high wordUSPH · High order word of the same 32-bit value. uint16 1 1 R Holding (FC03)
7121 7121 Last detected faultLFt · 0 = no fault code saved. The manual lists the full fault code table. uint16 1 1 R Holding (FC03)
7201 7201 Past detected fault 1DP1 uint16 1 1 R Holding (FC03)
3105 3105 Low speedLSP · Motor frequency at minimum reference. uint16 1 Hz 0.1 RW Holding (FC03)
3104 3104 High speedHSP · Motor frequency at maximum reference. uint16 1 Hz 0.1 RW Holding (FC03)
9001 9001 Acceleration ramp timeACC · Defined for accelerating between 0 and the nominal motor frequency FrS. The 0.1 s scale applies only when the ramp increment Inr (register 9020) is at its factory value; Inr = 0 makes one count 0.01 s and Inr = 2 makes it 1 s. uint16 1 s 0.1 RW Holding (FC03)
9002 9002 Deceleration ramp timedEC · Defined for decelerating between the nominal motor frequency FrS and 0. The 0.1 s scale applies only when the ramp increment Inr (register 9020) is at its factory value; Inr = 0 makes one count 0.01 s and Inr = 2 makes it 1 s. uint16 1 s 0.1 RW Holding (FC03)
9020 9020 Ramp incrementInr · 0 = 0.01 s per count, 1 = 0.1 s per count (factory setting), 2 = 1 s per count; applies to ACC, dEC, AC2 and DE2. Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
3102 3102 Switching frequencySFr · Adjustment range 20 to 160 (2.0 to 16.0 kHz). uint16 1 kHz 0.1 RW Holding (FC03)
3103 3103 Maximum output frequencytFr · Adjustment range 100 to 5000. Write access only while the drive is stopped (R/WS in the manual). uint16 1 Hz 0.1 RW Holding (FC03)
9601 9601 Nominal motor voltageUnS · From the motor rating plate. Write access only while the drive is stopped (R/WS in the manual). uint16 1 V 1 RW Holding (FC03)
9602 9602 Nominal motor frequencyFrS · From the motor rating plate. Write access only while the drive is stopped (R/WS in the manual). uint16 1 Hz 0.1 RW Holding (FC03)
9603 9603 Nominal motor currentnCr · From the motor rating plate. Write access only while the drive is stopped (R/WS in the manual). uint16 1 A 0.1 RW Holding (FC03)
9604 9604 Nominal motor speednSP · From the motor rating plate. Write access only while the drive is stopped (R/WS in the manual). uint16 1 rpm 1 RW Holding (FC03)
9606 9606 Motor power factor (cos phi)COS · From the motor rating plate; range 50 to 100. Write access only while the drive is stopped (R/WS in the manual). uint16 1 0.01 RW Holding (FC03)
9622 9622 Motor thermal protection currentItH · Set to the nominal motor current on the rating plate. uint16 1 A 0.1 RW Holding (FC03)
9201 9201 Current limitCLI · Used to limit the torque and the motor temperature rise. uint16 1 A 0.1 RW Holding (FC03)
11201 11201 Normal stop modeStt · 0 = ramp stop, 1 = fast stop, 2 = freewheel stop, 3 = DC injection stop. Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
8413 8413 Configuration reference 1Fr1 · 1 = AI1, 2 = AI2, 3 = AI3, 16 = potentiometer, with more assignments at higher access levels. Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
8423 8423 Control channel 1 configurationCd1 · 1 = terminal block, 2 = keypad, 3 = remote display terminal, 10 = Modbus, 20 = CANopen. Active when CHCF = SEP and LAC = L3. Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
6001 6001 Modbus drive addressAdd · Range 1 to 247, factory setting 1. Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
6003 6003 Modbus transmission speed codetbr · 24 = 4800 bps, 28 = 9600 bps, 32 = 19200 bps (factory setting; the remote display terminal only works with this value). Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
6004 6004 Modbus communication format codetFO · 2 = 8 data bits odd parity 1 stop, 3 = 8E1 (factory setting), 4 = 8N1, 5 = 8N2. Write access only while the drive is stopped (R/WS in the manual). uint16 1 1 RW Holding (FC03)
6005 6005 Modbus time-outttO · Unit 0.1 s, range 1 to 100, factory setting 100 as printed in this manual; the companion Modbus manual states an adjustable range of 0.1 to 30 s with a 10 s default. Write access only while the drive is stopped (R/WS in the manual). uint16 1 s 0.1 RW Holding (FC03)

Scale is the number to multiply the raw value by to get the unit.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to CD AB.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: Altivar 312 communication variables manual (download.schneider-electric.com)

BBV51701 06/2009, p. 7, 16-55. Read on 2026-10-24.

Also used: Altivar 312 Modbus communication manual (BBV52816 04/2009) (download.schneider-electric.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.

More from Schneider Electric

All Schneider Electric register maps

Other variable frequency drives

All register maps · Modbus addressing explained