Mitsubishi Electric FR-D700 Modbus register map

Small general-purpose inverter series with an RS-485 port on the PU connector that can run Modbus RTU as a slave. The Modbus map covers run and speed commands, live monitor values, the fault history and every inverter parameter.

Protocol
Modbus RTU
Defaults
Per the manual: Modbus RTU is off until Pr. 549 is set to 1. Initial station number 0 (no reply), 19200 bps (Pr. 118 = 192), even parity with 1 stop bit (Pr. 120 = 2), 8 data bits. The PU connector must be the network command source (Pr. 551 = 2) and the inverter in network mode.
Addresses in the manual
Modicon style numbers (for example 40001 is holding register 0)
32 and 64-bit values
Not stated in the manual
Registers listed
45
Checked against
IB(NA)-0600366ENG-H (1806), printed June 2018

Address base. Registers are printed as 4xxxx holding register numbers. The message format subtracts 40001 to get the address on the wire, for example register 40002 is sent as address 0001 (pp. 202 to 206). For example 40002 in the manual (Inverter reset command) is address 1 on the wire.

Word order. Every row is a single 16-bit register.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

45 registers
Manual Wire Register Type Regs Unit Scale Access Area
40002 1 Inverter reset commandInverterReset · Any value written triggers the reset. uint16 1 1 W Holding (FC03)
40009 8 Inverter status (read) or control input command (write)StatusControlWord · Read: bit 0 running, 1 forward, 2 reverse, 3 up to frequency, 4 overload, 6 frequency detection, 7 ABC output (fault by default), 9 SO output, 15 fault occurred. Write: bit 0 stop command, 1 forward, 2 reverse, 3 RH, 4 RM, 5 RL, 7 second function, 8 terminal 4 selection, 10 output stop. Bits 0, 1, 2 fixed, others follow the terminal assignment parameters. bitfield16 1 1 RW Holding (FC03)
40010 9 Operation mode (read) or mode setting (write)OperationMode · Read value: 0 external, 1 PU, 2 external JOG, 3 PU JOG, 4 network, 5 PU plus external. Write value: 0x0010 external, 0x0011 PU, 0x0014 network. Writing is limited by Pr. 79 and Pr. 340. uint16 1 1 RW Holding (FC03)
40014 13 Running frequency command, RAM valueRunningFrequencyRAM · Follows Pr. 37: with a speed display set, the unit is 1 r/min instead of 0.01 Hz. The manual example writes 60 Hz as 6000. uint16 1 Hz 0.01 RW Holding (FC03)
40015 14 Running frequency command, EEPROM valueRunningFrequencyEEPROM · Same unit rules as the RAM register 40014. uint16 1 Hz 0.01 W Holding (FC03)
40201 200 Output frequency or speedOutputFrequency · Unit is 1 r/min when Pr. 37 selects a speed display. uint16 1 Hz 0.01 R Holding (FC03)
40202 201 Output currentOutputCurrent · Value is held after a fault until reset. uint16 1 A 0.01 R Holding (FC03)
40203 202 Output voltageOutputVoltage · Value is held after a fault until reset. uint16 1 V 0.1 R Holding (FC03)
40205 204 Output frequency setting or speed settingFrequencySetting · Unit is 1 r/min when Pr. 37 selects a speed display. uint16 1 Hz 0.01 R Holding (FC03)
40208 207 Converter output (DC bus) voltageConverterOutputVoltage uint16 1 V 0.1 R Holding (FC03)
40209 208 Regenerative brake dutyRegenBrakeDuty uint16 1 % 0.1 R Holding (FC03)
40210 209 Electronic thermal relay load factorElectronicThermalLoad uint16 1 % 0.1 R Holding (FC03)
40211 210 Output current peak valueOutputCurrentPeak uint16 1 A 0.01 R Holding (FC03)
40212 211 Converter output voltage peak valueConverterVoltagePeak uint16 1 V 0.1 R Holding (FC03)
40214 213 Output powerOutputPower uint16 1 kW 0.01 R Holding (FC03)
40215 214 Input terminal statesInputTerminalStatus · Bit 0 STF, bit 1 STR, bit 4 RL, bit 5 RM, bit 6 RH; other bits are undetermined. bitfield16 1 1 R Holding (FC03)
40216 215 Output terminal statesOutputTerminalStatus · Bit 0 is RUN. The manual bit diagram also shows ABC and SO positions (see p. 211); unused bits are undetermined. bitfield16 1 1 R Holding (FC03)
40220 219 Cumulative energization timeCumulativeEnergizationTime uint16 1 h 1 R Holding (FC03)
40223 222 Actual operation timeActualOperationTime uint16 1 h 1 R Holding (FC03)
40224 223 Motor load factorMotorLoadFactor uint16 1 % 0.1 R Holding (FC03)
40225 224 Cumulative powerCumulativePower uint16 1 kWh 1 R Holding (FC03)
40252 251 PID set pointPIDSetPoint uint16 1 % 0.1 R Holding (FC03)
40253 252 PID measured valuePIDMeasuredValue uint16 1 % 0.1 R Holding (FC03)
40254 253 PID deviationPIDDeviation uint16 1 % 0.1 R Holding (FC03)
40261 260 Motor thermal load factorMotorThermalLoad uint16 1 % 0.1 R Holding (FC03)
40262 261 Inverter thermal load factorInverterThermalLoad uint16 1 % 0.1 R Holding (FC03)
40263 262 Cumulative power 2CumulativePower2 uint16 1 kWh 0.01 R Holding (FC03)
40264 263 PTC thermistor resistancePTCThermistorResistance uint16 1 kΩ 0.01 R Holding (FC03)
40501 500 Most recent fault recordFaultRecord1 · Low byte holds the fault code (for example 0x10 is E.OC1, 0x20 is E.OV1, 0x70 is E.BE, 0xB1 is E.PUE). Writing any value to this register clears the whole fault history. uint16 1 1 RW Holding (FC03)
40502 501 Fault record 2 (older)FaultRecord2 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
40503 502 Fault record 3 (older)FaultRecord3 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
40504 503 Fault record 4 (older)FaultRecord4 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
40505 504 Fault record 5 (older)FaultRecord5 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
40506 505 Fault record 6 (older)FaultRecord6 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
40507 506 Fault record 7 (older)FaultRecord7 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
40508 507 Fault record 8 (older)FaultRecord8 · Low byte holds the fault code, same table as fault record 1. uint16 1 1 R Holding (FC03)
41007 1006 Pr. 7 acceleration timePr7_AccelerationTime · Parameter registers are 41000 plus the parameter number. Setting range 0 to 3600 s in 0.1 s steps; the manual write example sets 0.5 s by writing 5 to register 41007. uint16 1 s 0.1 RW Holding (FC03)
41008 1007 Pr. 8 deceleration timePr8_DecelerationTime · Setting range 0 to 3600 s in 0.1 s steps; the manual write example sets 1 s by writing 10 to register 41008. uint16 1 s 0.1 RW Holding (FC03)
41079 1078 Pr. 79 operation mode selectionPr79_OperationModeSelection · Setting range 0 to 4, 6, 7. uint16 1 1 RW Holding (FC03)
41117 1116 Pr. 117 PU communication station number (Modbus slave address)Pr117_StationNumber · Range 0 to 247, initial value 0. Station 0 means broadcast, so the inverter sends no reply until a non-zero number is set. uint16 1 1 RW Holding (FC03)
41118 1117 Pr. 118 PU communication speedPr118_CommSpeed · Value times 100 is the baud rate: 48, 96, 192 (initial) or 384. Example: 96 means 9600 bps. uint16 1 1 RW Holding (FC03)
41120 1119 Pr. 120 PU communication parity and stop bitsPr120_ParityCheck · 0 = no parity with 2 stop bits, 1 = odd parity with 1 stop bit, 2 = even parity with 1 stop bit (initial). uint16 1 1 RW Holding (FC03)
41343 1342 Pr. 343 Modbus RTU communication error countPr343_CommErrorCount · Read only. Held in RAM and cleared by a power cycle or inverter reset. uint16 1 1 R Holding (FC03)
41502 1501 Pr. 502 stop mode at communication errorPr502_CommErrorStopMode · 0 coast to stop, 1 decelerate to stop then output fault, 2 decelerate to stop without fault output. uint16 1 1 RW Holding (FC03)
41549 1548 Pr. 549 protocol selectionPr549_ProtocolSelection · 0 = Mitsubishi inverter protocol (initial), 1 = Modbus RTU. Must be 1 for Modbus. uint16 1 1 RW Holding (FC03)

Scale is the number to multiply the raw value by to get the unit.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: FR-D700 Instruction Manual (Applied) (www.mitsubishielectric.com)

IB(NA)-0600366ENG-H (1806), printed June 2018, p. 201-212 (section 4.19.6 MODBUS RTU communication specifications). Read on 2026-10-24.

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.