SmartGen HGM9520N Modbus register map

The SmartGen HGM9520N is a genset paralleled (with mains) controller. SmartGen publishes one communication protocol document for the HGM9510N, HGM9520N and HGM9530N, and this map follows it: status and alarm bit words, seven alarm class fields, generator, mains and busbar voltage, current, power and frequency, engine and ECU values, running hours, energy counters, controller clock, DM1 and DM2 diagnostic codes, and remote command coils. Rows where the document distinguishes the HGM9520N from the other two models are marked in their notes.

Protocol
Modbus RTU (RS485) and Modbus TCP/UDP
Defaults
RS485: Modbus RTU slave, 9600 baud, 8 data bits, parity none by default (odd or even selectable), communication address default 1. The protocol document gives the address range as 1 to 245 in the physical layer text and 1 to 254 in Table 2; the user manual (Table 17) gives 1 to 254. The protocol text says 1 stop bit with 2 selectable; the user manual lists RS485(1) stop bit default 0, meaning 2 stop bits. Ethernet: Modbus TCP/UDP on port 502 (TCP/IP Modbus is enabled by default in the user manual network settings). Only function codes 03H, 05H and 06H are supported.
Addresses in the manual
0-based protocol addresses, as sent on the wire
32 and 64-bit values
Low word first (CD AB)
Registers listed
312
Checked against
SmartGen (Zhengzhou) Technology Co., Ltd., HGM9510N/HGM9520N/HGM9530N Genset Controller Communication Protocol, version 1.5 dated 2024-07-22 (vendor-hosted at smartgen.cn)

Address base. Table 5 and Table 11 print a Modbus Address column (decimal, for example 0174) and a PLC Address column (40175). The worked example on p. 31 reads A phase active power with starting address 0174 sent on the wire as 00AEH, so the Modbus Address column is the zero-based protocol address and the PLC address is that value plus 40001. Addresses in this file are the Modbus Address column. Function code 05H coil addresses (Table 17) are also printed zero-based, with a PLC address one higher. Address 0 in the manual is address 0 on the wire.

Word order. For 32-bit items the lower address holds the low word. Table 11 marks the first register LSB and the second MSB for the voltage and power rows, note 2 says 4-byte data is the high-order word times 65536 plus the low-order word, and the worked example on p. 31 to 32 reads 123456 as E240H at address 0174 and 0001H at address 0175. Some 32-bit rows (accumulated fuel, mains power, energy counters) carry no LSB or MSB marker and are assumed to follow note 2. Note 3 says a raw value of 32766 means no normal data. Bit words use bit 0 as the least significant bit, as in the p. 13 example where 8407H has bit 10 set.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

312 registers
Manual Wire Register Type Regs Unit Scale Access Area
0 0 Common alarm and operating mode flagsStatus_Word_0 · Bits as printed (bit 0 is the least significant): bit 0 Common alarm; bit 1 Common shutdown alarm; bit 2 Common warning alarm; bit 3 Common trip and stop alarm; bit 4 Common trip alarm; bit 5 Common safety trip and stop alarm; bit 6 Common safety trip alarm; bit 7 Common block alarm; bit 8 In test mode; bit 9 In auto mode; bit 10 In manual mode; bit 11 In stop mode; bit 12 Remote lock. Bits 13 to 15 are reserved. Each bit is 1 when active. The worked example on p. 13 reads 8407H, which the document interprets as manual mode active (bit 10). bitfield16 1 1 R Holding (FC03)
1 1 Shutdown alarm field, word 0Shutdown_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
2 2 Shutdown alarm field, word 1Shutdown_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
3 3 Shutdown alarm field, word 2Shutdown_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
4 4 Shutdown alarm field, word 3Shutdown_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
5 5 Shutdown alarm field, word 4Shutdown_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
6 6 Shutdown alarm field, word 5Shutdown_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
7 7 Shutdown alarm field, word 6Shutdown_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
8 8 Shutdown alarm field, word 7Shutdown_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
9 9 Shutdown alarm field, word 8Shutdown_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
10 10 Shutdown alarm field, word 9Shutdown_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
11 11 Shutdown alarm field, word 10Shutdown_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
12 12 Shutdown alarm field, word 11Shutdown_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
13 13 Shutdown alarm field, word 12Shutdown_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
14 14 Shutdown alarm field, word 13Shutdown_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
15 15 Shutdown alarm field, word 14Shutdown_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
16 16 Trip And Stop alarm field, word 0Trip_And_Stop_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
17 17 Trip And Stop alarm field, word 1Trip_And_Stop_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
18 18 Trip And Stop alarm field, word 2Trip_And_Stop_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
19 19 Trip And Stop alarm field, word 3Trip_And_Stop_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
20 20 Trip And Stop alarm field, word 4Trip_And_Stop_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
21 21 Trip And Stop alarm field, word 5Trip_And_Stop_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
22 22 Trip And Stop alarm field, word 6Trip_And_Stop_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
23 23 Trip And Stop alarm field, word 7Trip_And_Stop_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
24 24 Trip And Stop alarm field, word 8Trip_And_Stop_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
25 25 Trip And Stop alarm field, word 9Trip_And_Stop_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
26 26 Trip And Stop alarm field, word 10Trip_And_Stop_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
27 27 Trip And Stop alarm field, word 11Trip_And_Stop_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
28 28 Trip And Stop alarm field, word 12Trip_And_Stop_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
29 29 Trip And Stop alarm field, word 13Trip_And_Stop_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
30 30 Trip And Stop alarm field, word 14Trip_And_Stop_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
31 31 Trip alarm field, word 0Trip_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
32 32 Trip alarm field, word 1Trip_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
33 33 Trip alarm field, word 2Trip_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
34 34 Trip alarm field, word 3Trip_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
35 35 Trip alarm field, word 4Trip_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
36 36 Trip alarm field, word 5Trip_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
37 37 Trip alarm field, word 6Trip_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
38 38 Trip alarm field, word 7Trip_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
39 39 Trip alarm field, word 8Trip_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
40 40 Trip alarm field, word 9Trip_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
41 41 Trip alarm field, word 10Trip_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
42 42 Trip alarm field, word 11Trip_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
43 43 Trip alarm field, word 12Trip_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
44 44 Trip alarm field, word 13Trip_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
45 45 Trip alarm field, word 14Trip_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
46 46 Safety Trip And Stop alarm field, word 0Safety_Trip_And_Stop_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
47 47 Safety Trip And Stop alarm field, word 1Safety_Trip_And_Stop_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
48 48 Safety Trip And Stop alarm field, word 2Safety_Trip_And_Stop_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
49 49 Safety Trip And Stop alarm field, word 3Safety_Trip_And_Stop_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
50 50 Safety Trip And Stop alarm field, word 4Safety_Trip_And_Stop_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
51 51 Safety Trip And Stop alarm field, word 5Safety_Trip_And_Stop_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
52 52 Safety Trip And Stop alarm field, word 6Safety_Trip_And_Stop_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
53 53 Safety Trip And Stop alarm field, word 7Safety_Trip_And_Stop_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
54 54 Safety Trip And Stop alarm field, word 8Safety_Trip_And_Stop_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
55 55 Safety Trip And Stop alarm field, word 9Safety_Trip_And_Stop_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
56 56 Safety Trip And Stop alarm field, word 10Safety_Trip_And_Stop_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
57 57 Safety Trip And Stop alarm field, word 11Safety_Trip_And_Stop_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
58 58 Safety Trip And Stop alarm field, word 12Safety_Trip_And_Stop_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
59 59 Safety Trip And Stop alarm field, word 13Safety_Trip_And_Stop_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
60 60 Safety Trip And Stop alarm field, word 14Safety_Trip_And_Stop_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
61 61 Safety Trip alarm field, word 0Safety_Trip_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
62 62 Safety Trip alarm field, word 1Safety_Trip_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
63 63 Safety Trip alarm field, word 2Safety_Trip_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
64 64 Safety Trip alarm field, word 3Safety_Trip_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
65 65 Safety Trip alarm field, word 4Safety_Trip_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
66 66 Safety Trip alarm field, word 5Safety_Trip_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
67 67 Safety Trip alarm field, word 6Safety_Trip_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
68 68 Safety Trip alarm field, word 7Safety_Trip_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
69 69 Safety Trip alarm field, word 8Safety_Trip_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
70 70 Safety Trip alarm field, word 9Safety_Trip_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
71 71 Safety Trip alarm field, word 10Safety_Trip_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
72 72 Safety Trip alarm field, word 11Safety_Trip_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
73 73 Safety Trip alarm field, word 12Safety_Trip_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
74 74 Safety Trip alarm field, word 13Safety_Trip_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
75 75 Safety Trip alarm field, word 14Safety_Trip_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
76 76 Block alarm field, word 0Block_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
77 77 Block alarm field, word 1Block_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
78 78 Block alarm field, word 2Block_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
79 79 Block alarm field, word 3Block_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
80 80 Block alarm field, word 4Block_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
81 81 Block alarm field, word 5Block_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
82 82 Block alarm field, word 6Block_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
83 83 Block alarm field, word 7Block_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
84 84 Block alarm field, word 8Block_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
85 85 Block alarm field, word 9Block_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
86 86 Block alarm field, word 10Block_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
87 87 Block alarm field, word 11Block_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
88 88 Block alarm field, word 12Block_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
89 89 Block alarm field, word 13Block_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
90 90 Block alarm field, word 14Block_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
91 91 Warning alarm field, word 0Warning_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
92 92 Warning alarm field, word 1Warning_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
93 93 Warning alarm field, word 2Warning_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
94 94 Warning alarm field, word 3Warning_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
95 95 Warning alarm field, word 4Warning_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
96 96 Warning alarm field, word 5Warning_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
97 97 Warning alarm field, word 6Warning_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
98 98 Warning alarm field, word 7Warning_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
99 99 Warning alarm field, word 8Warning_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
100 100 Warning alarm field, word 9Warning_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
101 101 Warning alarm field, word 10Warning_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
102 102 Warning alarm field, word 11Warning_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
103 103 Warning alarm field, word 12Warning_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
104 104 Warning alarm field, word 13Warning_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
105 105 Warning alarm field, word 14Warning_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. bitfield16 1 1 R Holding (FC03)
106 106 Emergency stop and auxiliary input 1 to 15 statusInput_Status_Word_1 · Bit 0 emergency input port status; bits 1 to 15 auxiliary input 1 to 15 status. 1 for active. bitfield16 1 1 R Holding (FC03)
107 107 Expansion input 1 to 16 statusExpansion_Input_Status_Word · Bits 0 to 15 expansion input 1 to 16 status. 1 for active. bitfield16 1 1 R Holding (FC03)
108 108 Fuel, crank and auxiliary output 1 to 8 statusOutput_Status_Word_1 · Bit 0 fuel output port; bit 1 crank output port; bits 2 to 9 auxiliary output 1 to 8; bits 10 to 15 reserved. 1 for active. The table prints no description text for bit 9 (auxiliary output 8). bitfield16 1 1 R Holding (FC03)
109 109 Expansion output 1 to 16 statusExpansion_Output_Status_Word · Bits 0 to 15 expansion output 1 to 16 status. 1 for active. bitfield16 1 1 R Holding (FC03)
114 114 Mains and generator normal and breaker statusMains_Gen_Switch_Status_Word · Bit 0 mains normal; bit 1 mains on load; bit 2 gen normal; bit 3 gen close; bits 4 to 15 reserved. 1 for active. bitfield16 1 1 R Holding (FC03)
120 120 Busbar or mains voltage UABBusMains_Voltage_UAB uint32 2 V 0.1 R Holding (FC03)
122 122 Busbar or mains voltage UBCBusMains_Voltage_UBC uint32 2 V 0.1 R Holding (FC03)
124 124 Busbar or mains voltage UCABusMains_Voltage_UCA uint32 2 V 0.1 R Holding (FC03)
126 126 Busbar or mains voltage UABusMains_Voltage_UA uint32 2 V 0.1 R Holding (FC03)
128 128 Busbar or mains voltage UBBusMains_Voltage_UB uint32 2 V 0.1 R Holding (FC03)
130 130 Busbar or mains voltage UCBusMains_Voltage_UC uint32 2 V 0.1 R Holding (FC03)
132 132 Busbar or mains UA phase angleBusMains_Angle_UA uint16 1 ° 0.1 R Holding (FC03)
133 133 Busbar or mains UB phase angleBusMains_Angle_UB uint16 1 ° 0.1 R Holding (FC03)
134 134 Busbar or mains UC phase angleBusMains_Angle_UC uint16 1 ° 0.1 R Holding (FC03)
135 135 Busbar or mains frequencyBusMains_Frequency uint16 1 Hz 0.01 R Holding (FC03)
140 140 Generator voltage UABGen_Voltage_UAB uint32 2 V 0.1 R Holding (FC03)
142 142 Generator voltage UBCGen_Voltage_UBC uint32 2 V 0.1 R Holding (FC03)
144 144 Generator voltage UCAGen_Voltage_UCA uint32 2 V 0.1 R Holding (FC03)
146 146 Generator voltage UAGen_Voltage_UA uint32 2 V 0.1 R Holding (FC03)
148 148 Generator voltage UBGen_Voltage_UB uint32 2 V 0.1 R Holding (FC03)
150 150 Generator voltage UCGen_Voltage_UC uint32 2 V 0.1 R Holding (FC03)
152 152 Generator UA phase angleGen_Angle_UA uint16 1 ° 0.1 R Holding (FC03)
153 153 Generator UB phase angleGen_Angle_UB uint16 1 ° 0.1 R Holding (FC03)
154 154 Generator UC phase angleGen_Angle_UC uint16 1 ° 0.1 R Holding (FC03)
155 155 Generator frequencyGen_Frequency uint16 1 Hz 0.01 R Holding (FC03)
156 156 Voltage differenceSync_Voltage_Difference int16 1 V 0.1 R Holding (FC03)
157 157 Frequency differenceSync_Frequency_Difference int16 1 Hz 0.01 R Holding (FC03)
158 158 Phase differenceSync_Phase_Difference int16 1 ° 0.1 R Holding (FC03)
159 159 Current generator active percentageGen_Active_Percentage_Current int16 1 % 0.1 R Holding (FC03)
160 160 Target generator active percentageGen_Active_Percentage_Target int16 1 % 0.1 R Holding (FC03)
161 161 Current generator reactive percentageGen_Reactive_Percentage_Current int16 1 % 0.1 R Holding (FC03)
162 162 Target generator reactive percentageGen_Reactive_Percentage_Target int16 1 % 0.1 R Holding (FC03)
163 163 Governor (GOV) output percentageGOV_Output_Percent int16 1 % 0.1 R Holding (FC03)
164 164 AVR output percentageAVR_Output_Percent int16 1 % 0.1 R Holding (FC03)
166 166 A phase currentGen_Current_A uint16 1 A 0.1 R Holding (FC03)
167 167 B phase currentGen_Current_B uint16 1 A 0.1 R Holding (FC03)
168 168 C phase currentGen_Current_C uint16 1 A 0.1 R Holding (FC03)
169 169 Earth currentGen_Earth_Current uint16 1 A 0.1 R Holding (FC03)
170 170 A phase current phase angleGen_Current_Angle_A uint16 1 ° 0.1 R Holding (FC03)
171 171 B phase current phase angleGen_Current_Angle_B uint16 1 ° 0.1 R Holding (FC03)
172 172 C phase current phase angleGen_Current_Angle_C uint16 1 ° 0.1 R Holding (FC03)
173 173 Earth current phase angleGen_Current_Angle_Earth uint16 1 ° 0.1 R Holding (FC03)
174 174 A phase active powerGen_A_Active_Power int32 2 kW 0.1 R Holding (FC03)
176 176 B phase active powerGen_B_Active_Power int32 2 kW 0.1 R Holding (FC03)
178 178 C phase active powerGen_C_Active_Power int32 2 kW 0.1 R Holding (FC03)
180 180 Total active powerGen_Total_Active_Power int32 2 kW 0.1 R Holding (FC03)
182 182 A phase reactive powerGen_A_Reactive_Power int32 2 kvar 0.1 R Holding (FC03)
184 184 B phase reactive powerGen_B_Reactive_Power int32 2 kvar 0.1 R Holding (FC03)
186 186 C phase reactive powerGen_C_Reactive_Power int32 2 kvar 0.1 R Holding (FC03)
188 188 Total reactive powerGen_Total_Reactive_Power int32 2 kvar 0.1 R Holding (FC03)
190 190 A phase apparent powerGen_A_Apparent_Power int32 2 kVA 0.1 R Holding (FC03)
192 192 B phase apparent powerGen_B_Apparent_Power int32 2 kVA 0.1 R Holding (FC03)
194 194 C phase apparent powerGen_C_Apparent_Power int32 2 kVA 0.1 R Holding (FC03)
196 196 Total apparent powerGen_Total_Apparent_Power int32 2 kVA 0.1 R Holding (FC03)
198 198 A phase power factorGen_Power_Factor_A · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. int16 1 0.001 R Holding (FC03)
199 199 B phase power factorGen_Power_Factor_B · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. int16 1 0.001 R Holding (FC03)
200 200 C phase power factorGen_Power_Factor_C · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. int16 1 0.001 R Holding (FC03)
201 201 Average power factorGen_Power_Factor_Average · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. int16 1 0.001 R Holding (FC03)
204 204 Unbalanced currentUnbalanced_Current · Table 11 lists the range as 0 to 65535 and the remark as Signed. int16 1 A 0.1 R Holding (FC03)
212 212 Engine speedEngine_Speed uint16 1 r/min 1 R Holding (FC03)
213 213 Battery voltageBattery_Voltage uint16 1 V 0.1 R Holding (FC03)
214 214 Charger voltageCharger_Voltage uint16 1 V 0.1 R Holding (FC03)
220 220 Temperature sensor valueTemp_Sensor_Value · Printed range -50 to 10000. int16 1 °C 1 R Holding (FC03)
222 222 Pressure sensor valuePressure_Sensor_Value uint16 1 kPa 1 R Holding (FC03)
224 224 Level sensor valueLevel_Sensor_Value uint16 1 % 1 R Holding (FC03)
232 232 Load percentageLoad_Percentage int16 1 % 1 R Holding (FC03)
233 233 Coolant levelCoolant_Level uint16 1 % 1 R Holding (FC03)
234 234 Oil temperatureOil_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 °C 1 R Holding (FC03)
235 235 Coolant pressureCoolant_Pressure · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 kPa 1 R Holding (FC03)
236 236 Fuel pressureFuel_Pressure · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 kPa 1 R Holding (FC03)
237 237 Fuel temperatureFuel_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 °C 1 R Holding (FC03)
238 238 Inlet temperatureInlet_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 °C 1 R Holding (FC03)
239 239 Exhaust temperatureExhaust_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 °C 1 R Holding (FC03)
240 240 Turbo pressureTurbo_Pressure · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 kPa 1 R Holding (FC03)
241 241 Fuel consumptionFuel_Consumption · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. int16 1 L/h 0.1 R Holding (FC03)
242 242 Accumulated fuel consumptionFuel_Consumption_Accumulated · Table 11 remark: 32-bit unsigned, 4 bytes. uint32 2 L 1 R Holding (FC03)
251 251 Current mains active percentageMains_Active_Percentage int16 1 % 0.1 R Holding (FC03)
252 252 Current mains reactive percentageMains_Reactive_Percentage int16 1 % 0.1 R Holding (FC03)
253 253 Mains active powerMains_Active_Power int32 2 kW 0.1 R Holding (FC03)
255 255 Mains reactive powerMains_Reactive_Power int32 2 kvar 0.1 R Holding (FC03)
257 257 Mains apparent powerMains_Apparent_Power int32 2 kVA 0.1 R Holding (FC03)
259 259 Mains power factorMains_Power_Factor · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. int16 1 0.001 R Holding (FC03)
260 260 Generator statusGenerator_Status · Value is the item number in Table 28: 0 standby, 1 preheat, 2 fuel output, 3 crank, 4 crank rest, 5 safety run, 6 start idle, 7 high speed warming up, 8 wait for load, 9 normal running, 10 high speed cooling, 11 stop idle, 12 ETS, 13 wait for stop, 14 after stop, 15 stop failure. uint16 1 1 R Holding (FC03)
261 261 Generator status delay valueGenerator_Status_Delay · Delay value for the current generator status. The unit is not printed. Statuses 0, 2, 8, 9 and 15 have no delay value. uint16 1 1 R Holding (FC03)
262 262 Remote start statusRemote_Start_Status · Value is the item number in Table 29: 0 no delay, 1 start delay, 2 stop delay. uint16 1 1 R Holding (FC03)
263 263 Remote start delay valueRemote_Start_Delay · The unit is not printed. uint16 1 1 R Holding (FC03)
264 264 Generator ATS statusGen_ATS_Status · Value is the item number in Table 30: 0 synchronizing, 1 close delay, 2 wait for closing, 3 closed, 4 unloading, 5 open delay, 6 wait for opening, 7 opened. uint16 1 1 R Holding (FC03)
265 265 Generator ATS delay valueGen_ATS_Delay · The unit is not printed. uint16 1 1 R Holding (FC03)
266 266 Mains statusMains_Status · Value is the item number in Table 31: 0 normal, 1 normal delay, 2 abnormal, 3 abnormal delay. uint16 1 1 R Holding (FC03)
267 267 Mains status delay valueMains_Status_Delay · The unit is not printed. uint16 1 1 R Holding (FC03)
268 268 Mains ATS statusMains_ATS_Status · Uses the ATS status table (Table 30). uint16 1 1 R Holding (FC03)
269 269 Mains ATS delay valueMains_ATS_Delay · The unit is not printed. uint16 1 1 R Holding (FC03)
270 270 Accumulated running hoursAccumulated_Running_Hours uint16 1 h 1 R Holding (FC03)
271 271 Accumulated running minutesAccumulated_Running_Minutes uint16 1 min 1 R Holding (FC03)
272 272 Accumulated running secondsAccumulated_Running_Seconds uint16 1 s 1 R Holding (FC03)
273 273 Accumulated start timesAccumulated_Start_Count uint16 1 1 R Holding (FC03)
274 274 Accumulated energyAccumulated_Energy_kWh uint32 2 kWh 0.1 R Holding (FC03)
276 276 Accumulated reactive energyAccumulated_Energy_kvarh uint32 2 kvarh 0.1 R Holding (FC03)
278 278 Accumulated apparent energyAccumulated_Energy_kVAh uint32 2 kVAh 0.1 R Holding (FC03)
282 282 Maintenance time left, hoursMaintenance_Left_Hours uint16 1 h 1 R Holding (FC03)
283 283 Maintenance time left, minutesMaintenance_Left_Minutes uint16 1 min 1 R Holding (FC03)
284 284 Maintenance time left, secondsMaintenance_Left_Seconds uint16 1 s 1 R Holding (FC03)
288 288 Controller modelController_Model uint16 1 1 R Holding (FC03)
289 289 Software versionSoftware_Version uint16 1 0.1 R Holding (FC03)
290 290 Hardware versionHardware_Version uint16 1 0.1 R Holding (FC03)
291 291 Release year (last two digits)Release_Year uint16 1 year 1 R Holding (FC03)
292 292 Release monthRelease_Month uint16 1 month 1 R Holding (FC03)
293 293 Release dayRelease_Day uint16 1 day 1 R Holding (FC03)
296 296 Controller time: year (last two digits)Clock_Year · Function code 06 can write addresses 296 to 302; the document lists no other writable addresses in Table 11. uint16 1 year 1 RW Holding (FC03)
297 297 Controller time: monthClock_Month uint16 1 month 1 RW Holding (FC03)
298 298 Controller time: dayClock_Day uint16 1 day 1 RW Holding (FC03)
299 299 Controller time: weekClock_Week uint16 1 week 1 RW Holding (FC03)
300 300 Controller time: hourClock_Hour uint16 1 h 1 RW Holding (FC03)
301 301 Controller time: minuteClock_Minute uint16 1 min 1 RW Holding (FC03)
302 302 Controller time: secondClock_Second uint16 1 s 1 RW Holding (FC03)
303 303 Module MSC IDModule_MSC_ID uint16 1 1 R Holding (FC03)
304 304 Module priorityModule_Priority int16 1 1 R Holding (FC03)
305 305 Total module countTotal_Module_Count uint16 1 1 R Holding (FC03)
306 306 Multi-unit total active powerMultiUnit_Total_Active_Power int32 2 kW 0.1 R Holding (FC03)
341 341 A accumulated running time: hourA_Accum_Running_Hours uint16 1 h 1 R Holding (FC03)
342 342 A accumulated running time: minuteA_Accum_Running_Minutes uint16 1 min 1 R Holding (FC03)
343 343 A accumulated running time: secondA_Accum_Running_Seconds uint16 1 s 1 R Holding (FC03)
344 344 A accumulated start timesA_Accum_Start_Count uint16 1 1 R Holding (FC03)
345 345 A accumulated energyA_Accum_Energy int32 2 kWh 0.1 R Holding (FC03)
347 347 B accumulated running time: hourB_Accum_Running_Hours uint16 1 h 1 R Holding (FC03)
348 348 B accumulated running time: minuteB_Accum_Running_Minutes uint16 1 min 1 R Holding (FC03)
349 349 B accumulated running time: secondB_Accum_Running_Seconds uint16 1 s 1 R Holding (FC03)
350 350 B accumulated start timesB_Accum_Start_Count uint16 1 1 R Holding (FC03)
351 351 B accumulated energyB_Accum_Energy int32 2 kWh 0.1 R Holding (FC03)
406 406 ECU temperatureECU_Temperature int16 1 °C 1 R Holding (FC03)
407 407 Current running time: hourCurrent_Running_Hours uint16 1 h 1 R Holding (FC03)
408 408 Current running time: minuteCurrent_Running_Minutes uint16 1 min 1 R Holding (FC03)
409 409 Current running time: secondCurrent_Running_Seconds uint16 1 s 1 R Holding (FC03)
410 410 Current accumulated energyCurrent_Accum_Energy int32 2 kWh 0.1 R Holding (FC03)
412 412 THD 1THD1 int16 1 % 0.1 R Holding (FC03)
413 413 THD 2THD2 int16 1 % 0.1 R Holding (FC03)
414 414 THD 3THD3 int16 1 % 0.1 R Holding (FC03)
415 415 Unbalanced generator voltageGen_Voltage_Unbalance int16 1 % 0.1 R Holding (FC03)
416 416 DM1 alarm typeDM1_Alarm_Type · Value is the item number in Table 32: 0 no alarm, 1 warning, 2 block, 3 safety trip, 4 safety trip and stop, 5 trip, 6 trip and stop, 7 shutdown. uint16 1 1 R Holding (FC03)
417 417 DM1 alarm quantityDM1_Alarm_Quantity uint16 1 1 R Holding (FC03)
418 418 DM1 alarm 1 SPNDM1_Alarm_1_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
420 420 DM1 alarm 1 occurrence count and FMIDM1_Alarm_1_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
421 421 DM1 alarm 2 SPNDM1_Alarm_2_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
423 423 DM1 alarm 2 occurrence count and FMIDM1_Alarm_2_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
424 424 DM1 alarm 3 SPNDM1_Alarm_3_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
426 426 DM1 alarm 3 occurrence count and FMIDM1_Alarm_3_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
427 427 DM1 alarm 4 SPNDM1_Alarm_4_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
429 429 DM1 alarm 4 occurrence count and FMIDM1_Alarm_4_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
430 430 DM1 alarm 5 SPNDM1_Alarm_5_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
432 432 DM1 alarm 5 occurrence count and FMIDM1_Alarm_5_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
433 433 DM1 alarm 6 SPNDM1_Alarm_6_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
435 435 DM1 alarm 6 occurrence count and FMIDM1_Alarm_6_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
436 436 DM1 alarm 7 SPNDM1_Alarm_7_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
438 438 DM1 alarm 7 occurrence count and FMIDM1_Alarm_7_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
439 439 DM1 alarm 8 SPNDM1_Alarm_8_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
441 441 DM1 alarm 8 occurrence count and FMIDM1_Alarm_8_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
442 442 DM1 alarm 9 SPNDM1_Alarm_9_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
444 444 DM1 alarm 9 occurrence count and FMIDM1_Alarm_9_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
445 445 DM1 alarm 10 SPNDM1_Alarm_10_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
447 447 DM1 alarm 10 occurrence count and FMIDM1_Alarm_10_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
448 448 DM2 alarm typeDM2_Alarm_Type · Uses the alarm type table (Table 32). uint16 1 1 R Holding (FC03)
449 449 DM2 alarm quantityDM2_Alarm_Quantity uint16 1 1 R Holding (FC03)
450 450 DM2 alarm 1 SPNDM2_Alarm_1_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
452 452 DM2 alarm 1 occurrence count and FMIDM2_Alarm_1_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
453 453 DM2 alarm 2 SPNDM2_Alarm_2_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
455 455 DM2 alarm 2 occurrence count and FMIDM2_Alarm_2_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
456 456 DM2 alarm 3 SPNDM2_Alarm_3_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
458 458 DM2 alarm 3 occurrence count and FMIDM2_Alarm_3_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
459 459 DM2 alarm 4 SPNDM2_Alarm_4_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
461 461 DM2 alarm 4 occurrence count and FMIDM2_Alarm_4_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
462 462 DM2 alarm 5 SPNDM2_Alarm_5_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
464 464 DM2 alarm 5 occurrence count and FMIDM2_Alarm_5_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
465 465 DM2 alarm 6 SPNDM2_Alarm_6_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
467 467 DM2 alarm 6 occurrence count and FMIDM2_Alarm_6_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
468 468 DM2 alarm 7 SPNDM2_Alarm_7_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
470 470 DM2 alarm 7 occurrence count and FMIDM2_Alarm_7_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
471 471 DM2 alarm 8 SPNDM2_Alarm_8_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
473 473 DM2 alarm 8 occurrence count and FMIDM2_Alarm_8_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
474 474 DM2 alarm 9 SPNDM2_Alarm_9_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
476 476 DM2 alarm 9 occurrence count and FMIDM2_Alarm_9_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
477 477 DM2 alarm 10 SPNDM2_Alarm_10_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. uint32 2 1 R Holding (FC03)
479 479 DM2 alarm 10 occurrence count and FMIDM2_Alarm_10_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). uint16 1 1 R Holding (FC03)
511 511 Alarm quantityAlarm_Quantity uint16 1 1 R Holding (FC03)
4368 4368 Load parallel output active power percentageParallel_Output_Active_Power_Percentage · Active in gen control mode (constant power). Data range 0 to 1000, corresponding to 0.0% to 100.0%. Written with function code 06. The document does not describe reading it back. PLC address 44369. uint16 1 % 0.1 W Holding (FC03)
4370 4370 Load parallel output reactive power percentageParallel_Output_Reactive_Power_Percentage · Data range 0 to 1000, corresponding to 0.0% to 100.0%. Written with function code 06. The document does not describe reading it back. PLC address 44371. uint16 1 % 0.1 W Holding (FC03)
0 0 Remote start keyRemote_Start_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
1 1 Remote stop keyRemote_Stop_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
3 3 Remote auto keyRemote_Auto_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
4 4 Remote manual keyRemote_Manual_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
5 5 Remote mains close or open key (HGM9520N)Remote_Mains_Close_Open_Key · Table 17 prints this address as Remote Mains Close/Open Key for the HGM9520N and as Remote Gen Close Key for the HGM9510N and HGM9530N. Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
6 6 Remote generator close or open key (HGM9520N)Remote_Gen_Close_Open_Key · Table 17 prints this address as Remote Gen Close/Open Key for the HGM9520N and as Remote Gen Open Key for the HGM9510N and HGM9530N. Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
7 7 Remote up keyRemote_Up_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
8 8 Remote down keyRemote_Down_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
11 11 Remote confirm keyRemote_Confirm_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
12 12 Remote mute keyRemote_Mute_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
15 15 Remote diesel engine fast stopRemote_Engine_Fast_Stop · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
17 17 Remote alarm resetRemote_Alarm_Reset · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). bool 1 1 W Coil (FC01)
20 20 Remote output 1 activeRemote_Output_1 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
21 21 Remote output 2 activeRemote_Output_2 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
22 22 Remote output 3 activeRemote_Output_3 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
23 23 Remote output 4 activeRemote_Output_4 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
24 24 Remote output 5 activeRemote_Output_5 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
25 25 Remote output 6 activeRemote_Output_6 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
26 26 Remote output 7 activeRemote_Output_7 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
27 27 Remote output 8 activeRemote_Output_8 · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)
31 31 Remote lockRemote_Lock · Function code 05. Send FF00H for active and 0000H for inactive. bool 1 1 W Coil (FC01)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to CD AB.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: HGM9510N/HGM9520N/HGM9530N Genset Controller Communication Protocol (www.smartgen.cn)

SmartGen (Zhengzhou) Technology Co., Ltd., HGM9510N/HGM9520N/HGM9530N Genset Controller Communication Protocol, version 1.5 dated 2024-07-22 (vendor-hosted at smartgen.cn), p. 4 to 9 (communication format), p. 10 to 13 (Table 5), p. 14 to 32 (Table 11), p. 33 (Table 17), p. 35 (Table 22), p. 36 to 44 (Tables 27 to 33). Read on 2026-10-24.

Also used: HGM9520N Genset Paralleled Controller User Manual (SmartGen, version 1.3, 2025-04-18) (www.smartgen.cn)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.

Other generator controllers

All register maps · Modbus addressing explained