SmartGen HGM9520N Modbus register map
The SmartGen HGM9520N is a genset paralleled (with mains) controller. SmartGen publishes one communication protocol document for the HGM9510N, HGM9520N and HGM9530N, and this map follows it: status and alarm bit words, seven alarm class fields, generator, mains and busbar voltage, current, power and frequency, engine and ECU values, running hours, energy counters, controller clock, DM1 and DM2 diagnostic codes, and remote command coils. Rows where the document distinguishes the HGM9520N from the other two models are marked in their notes.
- Protocol
- Modbus RTU (RS485) and Modbus TCP/UDP
- Defaults
- RS485: Modbus RTU slave, 9600 baud, 8 data bits, parity none by default (odd or even selectable), communication address default 1. The protocol document gives the address range as 1 to 245 in the physical layer text and 1 to 254 in Table 2; the user manual (Table 17) gives 1 to 254. The protocol text says 1 stop bit with 2 selectable; the user manual lists RS485(1) stop bit default 0, meaning 2 stop bits. Ethernet: Modbus TCP/UDP on port 502 (TCP/IP Modbus is enabled by default in the user manual network settings). Only function codes 03H, 05H and 06H are supported.
- Addresses in the manual
- 0-based protocol addresses, as sent on the wire
- 32 and 64-bit values
- Low word first (CD AB)
- Registers listed
- 312
- Checked against
- SmartGen (Zhengzhou) Technology Co., Ltd., HGM9510N/HGM9520N/HGM9530N Genset Controller Communication Protocol, version 1.5 dated 2024-07-22 (vendor-hosted at smartgen.cn)
Address base. Table 5 and Table 11 print a Modbus Address column (decimal, for example 0174) and a PLC Address column (40175). The worked example on p. 31 reads A phase active power with starting address 0174 sent on the wire as 00AEH, so the Modbus Address column is the zero-based protocol address and the PLC address is that value plus 40001. Addresses in this file are the Modbus Address column. Function code 05H coil addresses (Table 17) are also printed zero-based, with a PLC address one higher. Address 0 in the manual is address 0 on the wire.
Word order. For 32-bit items the lower address holds the low word. Table 11 marks the first register LSB and the second MSB for the voltage and power rows, note 2 says 4-byte data is the high-order word times 65536 plus the low-order word, and the worked example on p. 31 to 32 reads 123456 as E240H at address 0174 and 0001H at address 0175. Some 32-bit rows (accumulated fuel, mains power, energy counters) carry no LSB or MSB marker and are assumed to follow note 2. Note 3 says a raw value of 32766 means no normal data. Bit words use bit 0 as the least significant bit, as in the p. 13 example where 8407H has bit 10 set.
Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.
Downloads
The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.
Registers
| Manual | Wire | Register | Type | Regs | Unit | Scale | Access | Area |
|---|---|---|---|---|---|---|---|---|
| 0 | 0 | Common alarm and operating mode flagsStatus_Word_0 · Bits as printed (bit 0 is the least significant): bit 0 Common alarm; bit 1 Common shutdown alarm; bit 2 Common warning alarm; bit 3 Common trip and stop alarm; bit 4 Common trip alarm; bit 5 Common safety trip and stop alarm; bit 6 Common safety trip alarm; bit 7 Common block alarm; bit 8 In test mode; bit 9 In auto mode; bit 10 In manual mode; bit 11 In stop mode; bit 12 Remote lock. Bits 13 to 15 are reserved. Each bit is 1 when active. The worked example on p. 13 reads 8407H, which the document interprets as manual mode active (bit 10). |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 1 | 1 | Shutdown alarm field, word 0Shutdown_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 2 | 2 | Shutdown alarm field, word 1Shutdown_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 3 | 3 | Shutdown alarm field, word 2Shutdown_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 4 | 4 | Shutdown alarm field, word 3Shutdown_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 5 | 5 | Shutdown alarm field, word 4Shutdown_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 6 | 6 | Shutdown alarm field, word 5Shutdown_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 7 | 7 | Shutdown alarm field, word 6Shutdown_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 8 | 8 | Shutdown alarm field, word 7Shutdown_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 9 | 9 | Shutdown alarm field, word 8Shutdown_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 10 | 10 | Shutdown alarm field, word 9Shutdown_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 11 | 11 | Shutdown alarm field, word 10Shutdown_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 12 | 12 | Shutdown alarm field, word 11Shutdown_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 13 | 13 | Shutdown alarm field, word 12Shutdown_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 14 | 14 | Shutdown alarm field, word 13Shutdown_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 15 | 15 | Shutdown alarm field, word 14Shutdown_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 16 | 16 | Trip And Stop alarm field, word 0Trip_And_Stop_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 17 | 17 | Trip And Stop alarm field, word 1Trip_And_Stop_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 18 | 18 | Trip And Stop alarm field, word 2Trip_And_Stop_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 19 | 19 | Trip And Stop alarm field, word 3Trip_And_Stop_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 20 | 20 | Trip And Stop alarm field, word 4Trip_And_Stop_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 21 | 21 | Trip And Stop alarm field, word 5Trip_And_Stop_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 22 | 22 | Trip And Stop alarm field, word 6Trip_And_Stop_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 23 | 23 | Trip And Stop alarm field, word 7Trip_And_Stop_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 24 | 24 | Trip And Stop alarm field, word 8Trip_And_Stop_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 25 | 25 | Trip And Stop alarm field, word 9Trip_And_Stop_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 26 | 26 | Trip And Stop alarm field, word 10Trip_And_Stop_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 27 | 27 | Trip And Stop alarm field, word 11Trip_And_Stop_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 28 | 28 | Trip And Stop alarm field, word 12Trip_And_Stop_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 29 | 29 | Trip And Stop alarm field, word 13Trip_And_Stop_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 30 | 30 | Trip And Stop alarm field, word 14Trip_And_Stop_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 31 | 31 | Trip alarm field, word 0Trip_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 32 | 32 | Trip alarm field, word 1Trip_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 33 | 33 | Trip alarm field, word 2Trip_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 34 | 34 | Trip alarm field, word 3Trip_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 35 | 35 | Trip alarm field, word 4Trip_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 36 | 36 | Trip alarm field, word 5Trip_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 37 | 37 | Trip alarm field, word 6Trip_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 38 | 38 | Trip alarm field, word 7Trip_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 39 | 39 | Trip alarm field, word 8Trip_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 40 | 40 | Trip alarm field, word 9Trip_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 41 | 41 | Trip alarm field, word 10Trip_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 42 | 42 | Trip alarm field, word 11Trip_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 43 | 43 | Trip alarm field, word 12Trip_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 44 | 44 | Trip alarm field, word 13Trip_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 45 | 45 | Trip alarm field, word 14Trip_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 46 | 46 | Safety Trip And Stop alarm field, word 0Safety_Trip_And_Stop_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 47 | 47 | Safety Trip And Stop alarm field, word 1Safety_Trip_And_Stop_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 48 | 48 | Safety Trip And Stop alarm field, word 2Safety_Trip_And_Stop_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 49 | 49 | Safety Trip And Stop alarm field, word 3Safety_Trip_And_Stop_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 50 | 50 | Safety Trip And Stop alarm field, word 4Safety_Trip_And_Stop_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 51 | 51 | Safety Trip And Stop alarm field, word 5Safety_Trip_And_Stop_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 52 | 52 | Safety Trip And Stop alarm field, word 6Safety_Trip_And_Stop_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 53 | 53 | Safety Trip And Stop alarm field, word 7Safety_Trip_And_Stop_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 54 | 54 | Safety Trip And Stop alarm field, word 8Safety_Trip_And_Stop_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 55 | 55 | Safety Trip And Stop alarm field, word 9Safety_Trip_And_Stop_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 56 | 56 | Safety Trip And Stop alarm field, word 10Safety_Trip_And_Stop_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 57 | 57 | Safety Trip And Stop alarm field, word 11Safety_Trip_And_Stop_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 58 | 58 | Safety Trip And Stop alarm field, word 12Safety_Trip_And_Stop_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 59 | 59 | Safety Trip And Stop alarm field, word 13Safety_Trip_And_Stop_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 60 | 60 | Safety Trip And Stop alarm field, word 14Safety_Trip_And_Stop_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 61 | 61 | Safety Trip alarm field, word 0Safety_Trip_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 62 | 62 | Safety Trip alarm field, word 1Safety_Trip_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 63 | 63 | Safety Trip alarm field, word 2Safety_Trip_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 64 | 64 | Safety Trip alarm field, word 3Safety_Trip_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 65 | 65 | Safety Trip alarm field, word 4Safety_Trip_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 66 | 66 | Safety Trip alarm field, word 5Safety_Trip_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 67 | 67 | Safety Trip alarm field, word 6Safety_Trip_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 68 | 68 | Safety Trip alarm field, word 7Safety_Trip_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 69 | 69 | Safety Trip alarm field, word 8Safety_Trip_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 70 | 70 | Safety Trip alarm field, word 9Safety_Trip_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 71 | 71 | Safety Trip alarm field, word 10Safety_Trip_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 72 | 72 | Safety Trip alarm field, word 11Safety_Trip_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 73 | 73 | Safety Trip alarm field, word 12Safety_Trip_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 74 | 74 | Safety Trip alarm field, word 13Safety_Trip_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 75 | 75 | Safety Trip alarm field, word 14Safety_Trip_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 76 | 76 | Block alarm field, word 0Block_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 77 | 77 | Block alarm field, word 1Block_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 78 | 78 | Block alarm field, word 2Block_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 79 | 79 | Block alarm field, word 3Block_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 80 | 80 | Block alarm field, word 4Block_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 81 | 81 | Block alarm field, word 5Block_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 82 | 82 | Block alarm field, word 6Block_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 83 | 83 | Block alarm field, word 7Block_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 84 | 84 | Block alarm field, word 8Block_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 85 | 85 | Block alarm field, word 9Block_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 86 | 86 | Block alarm field, word 10Block_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 87 | 87 | Block alarm field, word 11Block_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 88 | 88 | Block alarm field, word 12Block_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 89 | 89 | Block alarm field, word 13Block_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 90 | 90 | Block alarm field, word 14Block_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 91 | 91 | Warning alarm field, word 0Warning_Alarm_Field_0 · Alarm field word 0 of 15. Bits as printed in Table 27, Alarm Data, offset 0000 (bit 0 is the least significant): bit 0 Emergency Stop Alarm; bit 1 Overspeed Alarm; bit 2 Underspeed Alarm; bit 3 Speed Signal Loss; bit 4 Gen Overfrequency; bit 5 Gen Underfrequency; bit 6 Gen Overvoltage; bit 7 Gen Undervoltage; bit 8 Crank Failure Alarm; bit 9 Gen Overcurrent; bit 10 Current Imbalance; bit 11 Earth Fault; bit 12 Reverse Power Alarm; bit 13 Over Power Alarm; bit 14 Loss of Excitation Fault; bit 15 ECU Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 92 | 92 | Warning alarm field, word 1Warning_Alarm_Field_1 · Alarm field word 1 of 15. Bits as printed in Table 27, Alarm Data, offset 0001 (bit 0 is the least significant): bit 0 ECU Alarm; bit 1 High Temp. Input Alarm; bit 2 Low Oil Pressure Input Alarm; bit 3 MSC ID Error; bit 4 Voltage Bus Error; bit 5 Gen Phase Sequence Error; bit 6 Voltage Bus Phase Sequence Error; bit 7 Temp. Sensor Open; bit 8 High Engine Temp.; bit 9 Low Engine Temp.; bit 10 Temp. Sensor Error; bit 11 Oil Pressure Sensor Open; bit 12 High Oil Pressure; bit 13 Low Oil Pressure; bit 14 Oil Pressure Sensor Error; bit 15 Fuel Level Sensor Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 93 | 93 | Warning alarm field, word 2Warning_Alarm_Field_2 · Alarm field word 2 of 15. Bits as printed in Table 27, Alarm Data, offset 0002 (bit 0 is the least significant): bit 0 High Fuel Level; bit 1 Low Fuel Level; bit 2 Fuel Level Sensor Error; bit 3 Aux. Sensor 1 Open; bit 4 Aux. Sensor 1 High; bit 5 Aux. Sensor 1 Low; bit 6 Aux. Sensor 1 Error; bit 7 Aux. Sensor 2 Open; bit 8 Aux. Sensor 2 High; bit 9 Aux. Sensor 2 Low; bit 10 Aux. Sensor 2 Error; bit 11 Stop Failure; bit 12 Charging Failure; bit 13 Battery Overvoltage; bit 14 Battery Undervoltage; bit 15 Synchronization Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 94 | 94 | Warning alarm field, word 3Warning_Alarm_Field_3 · Alarm field word 3 of 15. Bits as printed in Table 27, Alarm Data, offset 0003 (bit 0 is the least significant): bit 0 GOV Reach Limit; bit 1 AVR Reach Limit; bit 2 Gen Insufficient Capacity; bit 3 Voltage Out of Synchronization; bit 4 Frequency Out of Synchronization; bit 5 Phase Out of Synchronization; bit 6 Mains Breaker Alarm; bit 7 Gen Breaker Alarm; bit 8 Mains Close Failure; bit 9 Gen Close Failure; bit 10 Mains Open Failure; bit 11 Gen Open Failure; bit 12 Mains Overfrequency; bit 13 Mains Underfrequency; bit 14 Mains Overvoltage; bit 15 Mains Undervoltage. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 95 | 95 | Warning alarm field, word 4Warning_Alarm_Field_4 · Alarm field word 4 of 15. Bits as printed in Table 27, Alarm Data, offset 0004 (bit 0 is the least significant): bit 0 Mains Frequency Change; bit 1 Mains Vector Drift; bit 2 Large Frequency Difference Warning; bit 3 Few MSC; bit 4 Maintenance 1 Time Due; bit 5 Maintenance 2 Time Due; bit 6 Maintenance 3 Time Due; bit 7 Low Water Level Alarm; bit 8 Detonation Alarm; bit 9 Gas Leak Alarm; bit 10 Gen Reverse Phase Sequence; bit 11 Gen Loss of Phase; bit 12 MSC1 Communication Failure; bit 13 MSC2 Communication Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 96 | 96 | Warning alarm field, word 5Warning_Alarm_Field_5 · Alarm field word 5 of 15. Bits as printed in Table 27, Alarm Data, offset 0005 (bit 0 is the least significant): bit 0 Digital Input 1; bit 1 Digital Input 2; bit 2 Digital Input 3; bit 3 Digital Input 4; bit 4 Digital Input 5; bit 5 Digital Input 6; bit 6 Digital Input 7; bit 7 Digital Input 8; bit 8 Digital Input 9; bit 9 Digital Input 10; bit 10 Digital Input 11; bit 11 Digital Input 12; bit 12 PLC Function 1; bit 13 PLC Function 2; bit 14 PLC Function 3; bit 15 PLC Function 4. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 97 | 97 | Warning alarm field, word 6Warning_Alarm_Field_6 · Alarm field word 6 of 15. Bits as printed in Table 27, Alarm Data, offset 0006 (bit 0 is the least significant): bit 0 PLC Function 5; bit 1 PLC Function 6; bit 2 PLC Function 7; bit 3 PLC Function 8; bit 4 PLC Function 9; bit 5 PLC Function 10; bit 6 PLC Function 11; bit 7 PLC Function 12; bit 8 PLC Function 13; bit 9 PLC Function 14; bit 10 PLC Function 15; bit 11 PLC Function 16; bit 12 PLC Function 17; bit 13 PLC Function 18; bit 14 PLC Function 19; bit 15 PLC Function 20. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 98 | 98 | Warning alarm field, word 7Warning_Alarm_Field_7 · Alarm field word 7 of 15. Bits as printed in Table 27, Alarm Data, offset 0007 (bit 0 is the least significant): bit 0 DIN16 Communication Failure; bit 1 DIN16 Input 1; bit 2 DIN16 Input 2; bit 3 DIN16 Input 3; bit 4 DIN16 Input 4; bit 5 DIN16 Input 5; bit 6 DIN16 Input 6; bit 7 DIN16 Input 7; bit 8 DIN16 Input 8; bit 9 DIN16 Input 9; bit 10 DIN16 Input 10; bit 11 DIN16 Input 11; bit 12 DIN16 Input 12; bit 13 DIN16 Input 13; bit 14 DIN16 Input 14; bit 15 DIN16 Input 15. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 99 | 99 | Warning alarm field, word 8Warning_Alarm_Field_8 · Alarm field word 8 of 15. Bits as printed in Table 27, Alarm Data, offset 0008 (bit 0 is the least significant): bit 0 DIN16 Input 16; bit 1 DOUT16 Communication Failure; bit 2 AIN24 1 Communication Failure; bit 3 AIN24 1 Cylinder Temp. High; bit 4 AIN24 1 Exhaust Temp. High; bit 5 AIN24 1 Large Cylinder Temp. Difference; bit 6 AIN24 1 Sensor 15 Open; bit 7 AIN24 1 Sensor 15 High; bit 8 AIN24 1 Sensor 15 Low; bit 9 AIN24 1 Sensor 16 Open; bit 10 AIN24 1 Sensor 16 High; bit 11 AIN24 1 Sensor 16 Low; bit 12 AIN24 1 Sensor 17 Open; bit 13 AIN24 1 Sensor 17 High; bit 14 AIN24 1 Sensor 17 Low; bit 15 AIN24 1 Sensor 18 Open. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 100 | 100 | Warning alarm field, word 9Warning_Alarm_Field_9 · Alarm field word 9 of 15. Bits as printed in Table 27, Alarm Data, offset 0009 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 18 High; bit 1 AIN24 1 Sensor 18 Low; bit 2 AIN24 1 Sensor 19 Open; bit 3 AIN24 1 Sensor 19 High; bit 4 AIN24 1 Sensor 19 Low; bit 5 AIN24 1 Sensor 20 Open; bit 6 AIN24 1 Sensor 20 High; bit 7 AIN24 1 Sensor 20 Low; bit 8 AIN24 1 Sensor 21 Open; bit 9 AIN24 1 Sensor 21 High; bit 10 AIN24 1 Sensor 21 Low; bit 11 AIN24 1 Sensor 22 Open; bit 12 AIN24 1 Sensor 22 High; bit 13 AIN24 1 Sensor 22 Low; bit 14 AIN24 1 Sensor 23 Open; bit 15 AIN24 1 Sensor 23 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 101 | 101 | Warning alarm field, word 10Warning_Alarm_Field_10 · Alarm field word 10 of 15. Bits as printed in Table 27, Alarm Data, offset 0010 (bit 0 is the least significant): bit 0 AIN24 1 Sensor 23 Low; bit 1 AIN24 1 Sensor 24 Open; bit 2 AIN24 1 Sensor 24 High; bit 3 AIN24 1 Sensor 24 Low; bit 4 AIN24 2 Communication Failure; bit 5 AIN24 2 Cylinder Temp. High; bit 6 AIN24 2 Exhaust Temp. High; bit 7 AIN24 2 Large Cylinder Temp. Difference; bit 8 AIN24 2 Sensor 15 Open; bit 9 AIN24 2 Sensor 15 High; bit 10 AIN24 2 Sensor 15 Low; bit 11 AIN24 2 Sensor 16 Open; bit 12 AIN24 2 Sensor 16 High; bit 13 AIN24 2 Sensor 16 Low; bit 14 AIN24 2 Sensor 17 Open; bit 15 AIN24 2 Sensor 17 High. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 102 | 102 | Warning alarm field, word 11Warning_Alarm_Field_11 · Alarm field word 11 of 15. Bits as printed in Table 27, Alarm Data, offset 0011 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 17 Low; bit 1 AIN24 2 Sensor 18 Open; bit 2 AIN24 2 Sensor 18 High; bit 3 AIN24 2 Sensor 18 Low; bit 4 AIN24 2 Sensor 19 Open; bit 5 AIN24 2 Sensor 19 High; bit 6 AIN24 2 Sensor 19 Low; bit 7 AIN24 2 Sensor 20 Open; bit 8 AIN24 2 Sensor 20 High; bit 9 AIN24 2 Sensor 20 Low; bit 10 AIN24 2 Sensor 21 Open; bit 11 AIN24 2 Sensor 21 High; bit 12 AIN24 2 Sensor 21 Low; bit 13 AIN24 2 Sensor 22 Open; bit 14 AIN24 2 Sensor 22 High; bit 15 AIN24 2 Sensor 22 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 103 | 103 | Warning alarm field, word 12Warning_Alarm_Field_12 · Alarm field word 12 of 15. Bits as printed in Table 27, Alarm Data, offset 0012 (bit 0 is the least significant): bit 0 AIN24 2 Sensor 23 Open; bit 1 AIN24 2 Sensor 23 High; bit 2 AIN24 2 Sensor 23 Low; bit 3 AIN24 2 Sensor 24 Open; bit 4 AIN24 2 Sensor 24 High; bit 5 AIN24 2 Sensor 24 Low; bit 6 Low Power Factor; bit 7 High THD; bit 8 Gen Voltage Imbalance; bit 9 MSC Mains Split; bit 10 Earth Breaker Close Failure; bit 11 Earth Breaker Open Failure; bit 12 Static Parallel Failure; bit 13 Master Controller Failure. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 104 | 104 | Warning alarm field, word 13Warning_Alarm_Field_13 · Alarm field word 13 of 15. Bits as printed in Table 27, Alarm Data, offset 0013 (bit 0 is the least significant): bit 0 AIN8 Communication Failure; bit 1 AIN8 Sensor 1 Open; bit 2 AIN8 Sensor 1 High; bit 3 AIN8 Sensor 1 Low; bit 4 AIN8 Sensor 2 Open; bit 5 AIN8 Sensor 2 High; bit 6 AIN8 Sensor 2 Low; bit 7 AIN8 Sensor 3 Open; bit 8 AIN8 Sensor 3 High; bit 9 AIN8 Sensor 3 Low; bit 10 AIN8 Sensor 4 Open; bit 11 AIN8 Sensor 4 High; bit 12 AIN8 Sensor 4 Low; bit 13 AIN8 Sensor 5 Open; bit 14 AIN8 Sensor 5 High; bit 15 AIN8 Sensor 5 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 105 | 105 | Warning alarm field, word 14Warning_Alarm_Field_14 · Alarm field word 14 of 15. Bits as printed in Table 27, Alarm Data, offset 0014 (bit 0 is the least significant): bit 0 AIN8 Sensor 6 Open; bit 1 AIN8 Sensor 6 High; bit 2 AIN8 Sensor 6 Low; bit 3 AIN8 Sensor 7 Open; bit 4 AIN8 Sensor 7 High; bit 5 AIN8 Sensor 7 Low; bit 6 AIN8 Sensor 8 Open; bit 7 AIN8 Sensor 8 High; bit 8 AIN8 Sensor 8 Low. A bit reads 1 when that alarm is active in this alarm class. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 106 | 106 | Emergency stop and auxiliary input 1 to 15 statusInput_Status_Word_1 · Bit 0 emergency input port status; bits 1 to 15 auxiliary input 1 to 15 status. 1 for active. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 107 | 107 | Expansion input 1 to 16 statusExpansion_Input_Status_Word · Bits 0 to 15 expansion input 1 to 16 status. 1 for active. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 108 | 108 | Fuel, crank and auxiliary output 1 to 8 statusOutput_Status_Word_1 · Bit 0 fuel output port; bit 1 crank output port; bits 2 to 9 auxiliary output 1 to 8; bits 10 to 15 reserved. 1 for active. The table prints no description text for bit 9 (auxiliary output 8). |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 109 | 109 | Expansion output 1 to 16 statusExpansion_Output_Status_Word · Bits 0 to 15 expansion output 1 to 16 status. 1 for active. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 114 | 114 | Mains and generator normal and breaker statusMains_Gen_Switch_Status_Word · Bit 0 mains normal; bit 1 mains on load; bit 2 gen normal; bit 3 gen close; bits 4 to 15 reserved. 1 for active. |
bitfield16 | 1 | 1 | R | Holding (FC03) | |
| 120 | 120 | Busbar or mains voltage UABBusMains_Voltage_UAB |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 122 | 122 | Busbar or mains voltage UBCBusMains_Voltage_UBC |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 124 | 124 | Busbar or mains voltage UCABusMains_Voltage_UCA |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 126 | 126 | Busbar or mains voltage UABusMains_Voltage_UA |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 128 | 128 | Busbar or mains voltage UBBusMains_Voltage_UB |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 130 | 130 | Busbar or mains voltage UCBusMains_Voltage_UC |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 132 | 132 | Busbar or mains UA phase angleBusMains_Angle_UA |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 133 | 133 | Busbar or mains UB phase angleBusMains_Angle_UB |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 134 | 134 | Busbar or mains UC phase angleBusMains_Angle_UC |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 135 | 135 | Busbar or mains frequencyBusMains_Frequency |
uint16 | 1 | Hz | 0.01 | R | Holding (FC03) |
| 140 | 140 | Generator voltage UABGen_Voltage_UAB |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 142 | 142 | Generator voltage UBCGen_Voltage_UBC |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 144 | 144 | Generator voltage UCAGen_Voltage_UCA |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 146 | 146 | Generator voltage UAGen_Voltage_UA |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 148 | 148 | Generator voltage UBGen_Voltage_UB |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 150 | 150 | Generator voltage UCGen_Voltage_UC |
uint32 | 2 | V | 0.1 | R | Holding (FC03) |
| 152 | 152 | Generator UA phase angleGen_Angle_UA |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 153 | 153 | Generator UB phase angleGen_Angle_UB |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 154 | 154 | Generator UC phase angleGen_Angle_UC |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 155 | 155 | Generator frequencyGen_Frequency |
uint16 | 1 | Hz | 0.01 | R | Holding (FC03) |
| 156 | 156 | Voltage differenceSync_Voltage_Difference |
int16 | 1 | V | 0.1 | R | Holding (FC03) |
| 157 | 157 | Frequency differenceSync_Frequency_Difference |
int16 | 1 | Hz | 0.01 | R | Holding (FC03) |
| 158 | 158 | Phase differenceSync_Phase_Difference |
int16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 159 | 159 | Current generator active percentageGen_Active_Percentage_Current |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 160 | 160 | Target generator active percentageGen_Active_Percentage_Target |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 161 | 161 | Current generator reactive percentageGen_Reactive_Percentage_Current |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 162 | 162 | Target generator reactive percentageGen_Reactive_Percentage_Target |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 163 | 163 | Governor (GOV) output percentageGOV_Output_Percent |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 164 | 164 | AVR output percentageAVR_Output_Percent |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 166 | 166 | A phase currentGen_Current_A |
uint16 | 1 | A | 0.1 | R | Holding (FC03) |
| 167 | 167 | B phase currentGen_Current_B |
uint16 | 1 | A | 0.1 | R | Holding (FC03) |
| 168 | 168 | C phase currentGen_Current_C |
uint16 | 1 | A | 0.1 | R | Holding (FC03) |
| 169 | 169 | Earth currentGen_Earth_Current |
uint16 | 1 | A | 0.1 | R | Holding (FC03) |
| 170 | 170 | A phase current phase angleGen_Current_Angle_A |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 171 | 171 | B phase current phase angleGen_Current_Angle_B |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 172 | 172 | C phase current phase angleGen_Current_Angle_C |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 173 | 173 | Earth current phase angleGen_Current_Angle_Earth |
uint16 | 1 | ° | 0.1 | R | Holding (FC03) |
| 174 | 174 | A phase active powerGen_A_Active_Power |
int32 | 2 | kW | 0.1 | R | Holding (FC03) |
| 176 | 176 | B phase active powerGen_B_Active_Power |
int32 | 2 | kW | 0.1 | R | Holding (FC03) |
| 178 | 178 | C phase active powerGen_C_Active_Power |
int32 | 2 | kW | 0.1 | R | Holding (FC03) |
| 180 | 180 | Total active powerGen_Total_Active_Power |
int32 | 2 | kW | 0.1 | R | Holding (FC03) |
| 182 | 182 | A phase reactive powerGen_A_Reactive_Power |
int32 | 2 | kvar | 0.1 | R | Holding (FC03) |
| 184 | 184 | B phase reactive powerGen_B_Reactive_Power |
int32 | 2 | kvar | 0.1 | R | Holding (FC03) |
| 186 | 186 | C phase reactive powerGen_C_Reactive_Power |
int32 | 2 | kvar | 0.1 | R | Holding (FC03) |
| 188 | 188 | Total reactive powerGen_Total_Reactive_Power |
int32 | 2 | kvar | 0.1 | R | Holding (FC03) |
| 190 | 190 | A phase apparent powerGen_A_Apparent_Power |
int32 | 2 | kVA | 0.1 | R | Holding (FC03) |
| 192 | 192 | B phase apparent powerGen_B_Apparent_Power |
int32 | 2 | kVA | 0.1 | R | Holding (FC03) |
| 194 | 194 | C phase apparent powerGen_C_Apparent_Power |
int32 | 2 | kVA | 0.1 | R | Holding (FC03) |
| 196 | 196 | Total apparent powerGen_Total_Apparent_Power |
int32 | 2 | kVA | 0.1 | R | Holding (FC03) |
| 198 | 198 | A phase power factorGen_Power_Factor_A · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. |
int16 | 1 | 0.001 | R | Holding (FC03) | |
| 199 | 199 | B phase power factorGen_Power_Factor_B · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. |
int16 | 1 | 0.001 | R | Holding (FC03) | |
| 200 | 200 | C phase power factorGen_Power_Factor_C · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. |
int16 | 1 | 0.001 | R | Holding (FC03) | |
| 201 | 201 | Average power factorGen_Power_Factor_Average · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. |
int16 | 1 | 0.001 | R | Holding (FC03) | |
| 204 | 204 | Unbalanced currentUnbalanced_Current · Table 11 lists the range as 0 to 65535 and the remark as Signed. |
int16 | 1 | A | 0.1 | R | Holding (FC03) |
| 212 | 212 | Engine speedEngine_Speed |
uint16 | 1 | r/min | 1 | R | Holding (FC03) |
| 213 | 213 | Battery voltageBattery_Voltage |
uint16 | 1 | V | 0.1 | R | Holding (FC03) |
| 214 | 214 | Charger voltageCharger_Voltage |
uint16 | 1 | V | 0.1 | R | Holding (FC03) |
| 220 | 220 | Temperature sensor valueTemp_Sensor_Value · Printed range -50 to 10000. |
int16 | 1 | °C | 1 | R | Holding (FC03) |
| 222 | 222 | Pressure sensor valuePressure_Sensor_Value |
uint16 | 1 | kPa | 1 | R | Holding (FC03) |
| 224 | 224 | Level sensor valueLevel_Sensor_Value |
uint16 | 1 | % | 1 | R | Holding (FC03) |
| 232 | 232 | Load percentageLoad_Percentage |
int16 | 1 | % | 1 | R | Holding (FC03) |
| 233 | 233 | Coolant levelCoolant_Level |
uint16 | 1 | % | 1 | R | Holding (FC03) |
| 234 | 234 | Oil temperatureOil_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | °C | 1 | R | Holding (FC03) |
| 235 | 235 | Coolant pressureCoolant_Pressure · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | kPa | 1 | R | Holding (FC03) |
| 236 | 236 | Fuel pressureFuel_Pressure · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | kPa | 1 | R | Holding (FC03) |
| 237 | 237 | Fuel temperatureFuel_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | °C | 1 | R | Holding (FC03) |
| 238 | 238 | Inlet temperatureInlet_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | °C | 1 | R | Holding (FC03) |
| 239 | 239 | Exhaust temperatureExhaust_Temperature · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | °C | 1 | R | Holding (FC03) |
| 240 | 240 | Turbo pressureTurbo_Pressure · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | kPa | 1 | R | Holding (FC03) |
| 241 | 241 | Fuel consumptionFuel_Consumption · Table 11 remark: reserved when the engine is not an ECU engine; 16-bit signed. |
int16 | 1 | L/h | 0.1 | R | Holding (FC03) |
| 242 | 242 | Accumulated fuel consumptionFuel_Consumption_Accumulated · Table 11 remark: 32-bit unsigned, 4 bytes. |
uint32 | 2 | L | 1 | R | Holding (FC03) |
| 251 | 251 | Current mains active percentageMains_Active_Percentage |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 252 | 252 | Current mains reactive percentageMains_Reactive_Percentage |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 253 | 253 | Mains active powerMains_Active_Power |
int32 | 2 | kW | 0.1 | R | Holding (FC03) |
| 255 | 255 | Mains reactive powerMains_Reactive_Power |
int32 | 2 | kvar | 0.1 | R | Holding (FC03) |
| 257 | 257 | Mains apparent powerMains_Apparent_Power |
int32 | 2 | kVA | 0.1 | R | Holding (FC03) |
| 259 | 259 | Mains power factorMains_Power_Factor · The printed range is -100.000 to 100.000 with ratio 0.001, which does not fit in one 16-bit signed register, so confirm the scaling on the device. |
int16 | 1 | 0.001 | R | Holding (FC03) | |
| 260 | 260 | Generator statusGenerator_Status · Value is the item number in Table 28: 0 standby, 1 preheat, 2 fuel output, 3 crank, 4 crank rest, 5 safety run, 6 start idle, 7 high speed warming up, 8 wait for load, 9 normal running, 10 high speed cooling, 11 stop idle, 12 ETS, 13 wait for stop, 14 after stop, 15 stop failure. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 261 | 261 | Generator status delay valueGenerator_Status_Delay · Delay value for the current generator status. The unit is not printed. Statuses 0, 2, 8, 9 and 15 have no delay value. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 262 | 262 | Remote start statusRemote_Start_Status · Value is the item number in Table 29: 0 no delay, 1 start delay, 2 stop delay. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 263 | 263 | Remote start delay valueRemote_Start_Delay · The unit is not printed. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 264 | 264 | Generator ATS statusGen_ATS_Status · Value is the item number in Table 30: 0 synchronizing, 1 close delay, 2 wait for closing, 3 closed, 4 unloading, 5 open delay, 6 wait for opening, 7 opened. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 265 | 265 | Generator ATS delay valueGen_ATS_Delay · The unit is not printed. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 266 | 266 | Mains statusMains_Status · Value is the item number in Table 31: 0 normal, 1 normal delay, 2 abnormal, 3 abnormal delay. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 267 | 267 | Mains status delay valueMains_Status_Delay · The unit is not printed. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 268 | 268 | Mains ATS statusMains_ATS_Status · Uses the ATS status table (Table 30). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 269 | 269 | Mains ATS delay valueMains_ATS_Delay · The unit is not printed. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 270 | 270 | Accumulated running hoursAccumulated_Running_Hours |
uint16 | 1 | h | 1 | R | Holding (FC03) |
| 271 | 271 | Accumulated running minutesAccumulated_Running_Minutes |
uint16 | 1 | min | 1 | R | Holding (FC03) |
| 272 | 272 | Accumulated running secondsAccumulated_Running_Seconds |
uint16 | 1 | s | 1 | R | Holding (FC03) |
| 273 | 273 | Accumulated start timesAccumulated_Start_Count |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 274 | 274 | Accumulated energyAccumulated_Energy_kWh |
uint32 | 2 | kWh | 0.1 | R | Holding (FC03) |
| 276 | 276 | Accumulated reactive energyAccumulated_Energy_kvarh |
uint32 | 2 | kvarh | 0.1 | R | Holding (FC03) |
| 278 | 278 | Accumulated apparent energyAccumulated_Energy_kVAh |
uint32 | 2 | kVAh | 0.1 | R | Holding (FC03) |
| 282 | 282 | Maintenance time left, hoursMaintenance_Left_Hours |
uint16 | 1 | h | 1 | R | Holding (FC03) |
| 283 | 283 | Maintenance time left, minutesMaintenance_Left_Minutes |
uint16 | 1 | min | 1 | R | Holding (FC03) |
| 284 | 284 | Maintenance time left, secondsMaintenance_Left_Seconds |
uint16 | 1 | s | 1 | R | Holding (FC03) |
| 288 | 288 | Controller modelController_Model |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 289 | 289 | Software versionSoftware_Version |
uint16 | 1 | 0.1 | R | Holding (FC03) | |
| 290 | 290 | Hardware versionHardware_Version |
uint16 | 1 | 0.1 | R | Holding (FC03) | |
| 291 | 291 | Release year (last two digits)Release_Year |
uint16 | 1 | year | 1 | R | Holding (FC03) |
| 292 | 292 | Release monthRelease_Month |
uint16 | 1 | month | 1 | R | Holding (FC03) |
| 293 | 293 | Release dayRelease_Day |
uint16 | 1 | day | 1 | R | Holding (FC03) |
| 296 | 296 | Controller time: year (last two digits)Clock_Year · Function code 06 can write addresses 296 to 302; the document lists no other writable addresses in Table 11. |
uint16 | 1 | year | 1 | RW | Holding (FC03) |
| 297 | 297 | Controller time: monthClock_Month |
uint16 | 1 | month | 1 | RW | Holding (FC03) |
| 298 | 298 | Controller time: dayClock_Day |
uint16 | 1 | day | 1 | RW | Holding (FC03) |
| 299 | 299 | Controller time: weekClock_Week |
uint16 | 1 | week | 1 | RW | Holding (FC03) |
| 300 | 300 | Controller time: hourClock_Hour |
uint16 | 1 | h | 1 | RW | Holding (FC03) |
| 301 | 301 | Controller time: minuteClock_Minute |
uint16 | 1 | min | 1 | RW | Holding (FC03) |
| 302 | 302 | Controller time: secondClock_Second |
uint16 | 1 | s | 1 | RW | Holding (FC03) |
| 303 | 303 | Module MSC IDModule_MSC_ID |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 304 | 304 | Module priorityModule_Priority |
int16 | 1 | 1 | R | Holding (FC03) | |
| 305 | 305 | Total module countTotal_Module_Count |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 306 | 306 | Multi-unit total active powerMultiUnit_Total_Active_Power |
int32 | 2 | kW | 0.1 | R | Holding (FC03) |
| 341 | 341 | A accumulated running time: hourA_Accum_Running_Hours |
uint16 | 1 | h | 1 | R | Holding (FC03) |
| 342 | 342 | A accumulated running time: minuteA_Accum_Running_Minutes |
uint16 | 1 | min | 1 | R | Holding (FC03) |
| 343 | 343 | A accumulated running time: secondA_Accum_Running_Seconds |
uint16 | 1 | s | 1 | R | Holding (FC03) |
| 344 | 344 | A accumulated start timesA_Accum_Start_Count |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 345 | 345 | A accumulated energyA_Accum_Energy |
int32 | 2 | kWh | 0.1 | R | Holding (FC03) |
| 347 | 347 | B accumulated running time: hourB_Accum_Running_Hours |
uint16 | 1 | h | 1 | R | Holding (FC03) |
| 348 | 348 | B accumulated running time: minuteB_Accum_Running_Minutes |
uint16 | 1 | min | 1 | R | Holding (FC03) |
| 349 | 349 | B accumulated running time: secondB_Accum_Running_Seconds |
uint16 | 1 | s | 1 | R | Holding (FC03) |
| 350 | 350 | B accumulated start timesB_Accum_Start_Count |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 351 | 351 | B accumulated energyB_Accum_Energy |
int32 | 2 | kWh | 0.1 | R | Holding (FC03) |
| 406 | 406 | ECU temperatureECU_Temperature |
int16 | 1 | °C | 1 | R | Holding (FC03) |
| 407 | 407 | Current running time: hourCurrent_Running_Hours |
uint16 | 1 | h | 1 | R | Holding (FC03) |
| 408 | 408 | Current running time: minuteCurrent_Running_Minutes |
uint16 | 1 | min | 1 | R | Holding (FC03) |
| 409 | 409 | Current running time: secondCurrent_Running_Seconds |
uint16 | 1 | s | 1 | R | Holding (FC03) |
| 410 | 410 | Current accumulated energyCurrent_Accum_Energy |
int32 | 2 | kWh | 0.1 | R | Holding (FC03) |
| 412 | 412 | THD 1THD1 |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 413 | 413 | THD 2THD2 |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 414 | 414 | THD 3THD3 |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 415 | 415 | Unbalanced generator voltageGen_Voltage_Unbalance |
int16 | 1 | % | 0.1 | R | Holding (FC03) |
| 416 | 416 | DM1 alarm typeDM1_Alarm_Type · Value is the item number in Table 32: 0 no alarm, 1 warning, 2 block, 3 safety trip, 4 safety trip and stop, 5 trip, 6 trip and stop, 7 shutdown. |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 417 | 417 | DM1 alarm quantityDM1_Alarm_Quantity |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 418 | 418 | DM1 alarm 1 SPNDM1_Alarm_1_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 420 | 420 | DM1 alarm 1 occurrence count and FMIDM1_Alarm_1_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 421 | 421 | DM1 alarm 2 SPNDM1_Alarm_2_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 423 | 423 | DM1 alarm 2 occurrence count and FMIDM1_Alarm_2_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 424 | 424 | DM1 alarm 3 SPNDM1_Alarm_3_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 426 | 426 | DM1 alarm 3 occurrence count and FMIDM1_Alarm_3_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 427 | 427 | DM1 alarm 4 SPNDM1_Alarm_4_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 429 | 429 | DM1 alarm 4 occurrence count and FMIDM1_Alarm_4_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 430 | 430 | DM1 alarm 5 SPNDM1_Alarm_5_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 432 | 432 | DM1 alarm 5 occurrence count and FMIDM1_Alarm_5_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 433 | 433 | DM1 alarm 6 SPNDM1_Alarm_6_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 435 | 435 | DM1 alarm 6 occurrence count and FMIDM1_Alarm_6_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 436 | 436 | DM1 alarm 7 SPNDM1_Alarm_7_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 438 | 438 | DM1 alarm 7 occurrence count and FMIDM1_Alarm_7_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 439 | 439 | DM1 alarm 8 SPNDM1_Alarm_8_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 441 | 441 | DM1 alarm 8 occurrence count and FMIDM1_Alarm_8_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 442 | 442 | DM1 alarm 9 SPNDM1_Alarm_9_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 444 | 444 | DM1 alarm 9 occurrence count and FMIDM1_Alarm_9_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 445 | 445 | DM1 alarm 10 SPNDM1_Alarm_10_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 447 | 447 | DM1 alarm 10 occurrence count and FMIDM1_Alarm_10_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 448 | 448 | DM2 alarm typeDM2_Alarm_Type · Uses the alarm type table (Table 32). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 449 | 449 | DM2 alarm quantityDM2_Alarm_Quantity |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 450 | 450 | DM2 alarm 1 SPNDM2_Alarm_1_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 452 | 452 | DM2 alarm 1 occurrence count and FMIDM2_Alarm_1_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 453 | 453 | DM2 alarm 2 SPNDM2_Alarm_2_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 455 | 455 | DM2 alarm 2 occurrence count and FMIDM2_Alarm_2_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 456 | 456 | DM2 alarm 3 SPNDM2_Alarm_3_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 458 | 458 | DM2 alarm 3 occurrence count and FMIDM2_Alarm_3_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 459 | 459 | DM2 alarm 4 SPNDM2_Alarm_4_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 461 | 461 | DM2 alarm 4 occurrence count and FMIDM2_Alarm_4_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 462 | 462 | DM2 alarm 5 SPNDM2_Alarm_5_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 464 | 464 | DM2 alarm 5 occurrence count and FMIDM2_Alarm_5_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 465 | 465 | DM2 alarm 6 SPNDM2_Alarm_6_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 467 | 467 | DM2 alarm 6 occurrence count and FMIDM2_Alarm_6_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 468 | 468 | DM2 alarm 7 SPNDM2_Alarm_7_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 470 | 470 | DM2 alarm 7 occurrence count and FMIDM2_Alarm_7_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 471 | 471 | DM2 alarm 8 SPNDM2_Alarm_8_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 473 | 473 | DM2 alarm 8 occurrence count and FMIDM2_Alarm_8_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 474 | 474 | DM2 alarm 9 SPNDM2_Alarm_9_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 476 | 476 | DM2 alarm 9 occurrence count and FMIDM2_Alarm_9_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 477 | 477 | DM2 alarm 10 SPNDM2_Alarm_10_SPN · Table 11 marks the first register SPN LSB and the second SPN MSB. |
uint32 | 2 | 1 | R | Holding (FC03) | |
| 479 | 479 | DM2 alarm 10 occurrence count and FMIDM2_Alarm_10_OC_FMI · High 8 bits are the occurrence count (OC) and low 8 bits the failure mode identifier (FMI). |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 511 | 511 | Alarm quantityAlarm_Quantity |
uint16 | 1 | 1 | R | Holding (FC03) | |
| 4368 | 4368 | Load parallel output active power percentageParallel_Output_Active_Power_Percentage · Active in gen control mode (constant power). Data range 0 to 1000, corresponding to 0.0% to 100.0%. Written with function code 06. The document does not describe reading it back. PLC address 44369. |
uint16 | 1 | % | 0.1 | W | Holding (FC03) |
| 4370 | 4370 | Load parallel output reactive power percentageParallel_Output_Reactive_Power_Percentage · Data range 0 to 1000, corresponding to 0.0% to 100.0%. Written with function code 06. The document does not describe reading it back. PLC address 44371. |
uint16 | 1 | % | 0.1 | W | Holding (FC03) |
| 0 | 0 | Remote start keyRemote_Start_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 1 | 1 | Remote stop keyRemote_Stop_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 3 | 3 | Remote auto keyRemote_Auto_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 4 | 4 | Remote manual keyRemote_Manual_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 5 | 5 | Remote mains close or open key (HGM9520N)Remote_Mains_Close_Open_Key · Table 17 prints this address as Remote Mains Close/Open Key for the HGM9520N and as Remote Gen Close Key for the HGM9510N and HGM9530N. Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 6 | 6 | Remote generator close or open key (HGM9520N)Remote_Gen_Close_Open_Key · Table 17 prints this address as Remote Gen Close/Open Key for the HGM9520N and as Remote Gen Open Key for the HGM9510N and HGM9530N. Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 7 | 7 | Remote up keyRemote_Up_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 8 | 8 | Remote down keyRemote_Down_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 11 | 11 | Remote confirm keyRemote_Confirm_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 12 | 12 | Remote mute keyRemote_Mute_Key · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 15 | 15 | Remote diesel engine fast stopRemote_Engine_Fast_Stop · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 17 | 17 | Remote alarm resetRemote_Alarm_Reset · Function code 05 only. Send FF00H to activate. Each remote command can only be sent once per use (note 1 under Table 17). |
bool | 1 | 1 | W | Coil (FC01) | |
| 20 | 20 | Remote output 1 activeRemote_Output_1 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 21 | 21 | Remote output 2 activeRemote_Output_2 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 22 | 22 | Remote output 3 activeRemote_Output_3 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 23 | 23 | Remote output 4 activeRemote_Output_4 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 24 | 24 | Remote output 5 activeRemote_Output_5 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 25 | 25 | Remote output 6 activeRemote_Output_6 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 26 | 26 | Remote output 7 activeRemote_Output_7 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 27 | 27 | Remote output 8 activeRemote_Output_8 · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) | |
| 31 | 31 | Remote lockRemote_Lock · Function code 05. Send FF00H for active and 0000H for inactive. |
bool | 1 | 1 | W | Coil (FC01) |
Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.
Open in Modbus Poll
- Download the Modbus Poll blocks file.
- Open Modbus Poll, connect to the device and set its unit ID. In Modbus Poll set Word order to CD AB.
- In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
- The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.
Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.
Source and accuracy
Manufacturer document: HGM9510N/HGM9520N/HGM9530N Genset Controller Communication Protocol (www.smartgen.cn)
SmartGen (Zhengzhou) Technology Co., Ltd., HGM9510N/HGM9520N/HGM9530N Genset Controller Communication Protocol, version 1.5 dated 2024-07-22 (vendor-hosted at smartgen.cn), p. 4 to 9 (communication format), p. 10 to 13 (Table 5), p. 14 to 32 (Table 11), p. 33 (Table 17), p. 35 (Table 22), p. 36 to 44 (Tables 27 to 33). Read on 2026-10-24.
Also used: HGM9520N Genset Paralleled Controller User Manual (SmartGen, version 1.3, 2025-04-18) (www.smartgen.cn)
Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.
Found a mistake? Report it by email with the register address and the manual page.