Omron E5CC Modbus register map

Panel-mount digital temperature controller from the E5@C family with thermocouple, RTD and analog inputs, PID control and several alarm outputs. This map covers the Modbus RTU variable area, including process value, set points, alarms, status words and communications settings.

Protocol
Modbus RTU
Defaults
Unit number is set between 1 and 99. Baud rate options are 9.6, 19.2, 38.4 and 57.6 kbit/s. For Modbus the data length must be 8 bits, with 1 stop bit plus parity or 2 stop bits with no parity. Send data wait time defaults to 20 ms.
Addresses in the manual
0-based protocol addresses, as sent on the wire
32 and 64-bit values
Not stated in the manual
Registers listed
67
Checked against
Cat. No. H175, document code H175-E1-17

Address base. The manual prints addresses in hex and offers two modes. This file uses the two-byte mode column (one 16-bit register per value), which starts at hex 2000. The worked read and write examples on p. 4-12 use the printed value directly in the frame (for example hex 2105), so printed equals wire address. Addresses here are the decimal equivalents of the printed hex. Four-byte mode uses a separate address column and 32-bit values. Address 8192 in the manual is address 8192 on the wire.

Word order. Two-byte mode gives one 16-bit value per register. In four-byte mode a value spans two registers read from an even address. Status words read in two-byte mode are split into a lower and an upper word at separate addresses. Access flags in this file follow the manual's monitor versus setting classification, because the variable table has no access column.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

67 registers
Manual Wire Register Type Regs Unit Scale Access Area
8192 8192 Process value (operation level)PV · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). Range depends on the input type. int16 1 1 R Holding (FC03)
8193 8193 Controller status, lower wordStatus_Low · Bits 0 to 15: heater overcurrent CT1, heater current hold CT1, A/D converter error, HS alarm CT1, RSP input error, spare, input error, potentiometer input error, control output heating/open, control output cooling/close, HB alarm CT1, HB alarm CT2, alarm 1, alarm 2, alarm 3, program end output. In two-byte mode this is the rightmost 16 bits. bitfield16 1 1 R Holding (FC03)
8194 8194 Internal set point (monitor)InternalSetPoint · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 R Holding (FC03)
8195 8195 Heater current 1 value monitorHeaterCurrent1Monitor · Listed range 0.0 to 55.0. uint16 1 0.1 R Holding (FC03)
8196 8196 MV monitor (heating)MvMonitorHeating · Standard control: -5.0 to 105.0. Heating and cooling control: 0.0 to 105.0. int16 1 0.1 R Holding (FC03)
8197 8197 MV monitor (cooling)MvMonitorCooling · Listed range 0.0 to 105.0. uint16 1 0.1 R Holding (FC03)
8451 8451 Set point (operation level)SetPointOperation · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 RW Holding (FC03)
8452 8452 Alarm value 1 (operation level)AlarmValue1Operation · Listed range -1999 to 9999. Decimal places follow the Decimal Point parameter. int16 1 1 RW Holding (FC03)
8455 8455 Alarm value 2 (operation level)AlarmValue2Operation · Listed range -1999 to 9999. int16 1 1 RW Holding (FC03)
9218 9218 Process value (monitor block)PVMonitor · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 R Holding (FC03)
9219 9219 Internal set point (monitor block)InternalSetPointMonitor · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 R Holding (FC03)
9220 9220 Active multi-SP numberMultiSpNoMonitor · 0 to 7. uint16 1 1 R Holding (FC03)
9222 9222 Status, lower word (monitor block)StatusMonitor_Low · Same bit layout as register hex 2001. bitfield16 1 1 R Holding (FC03)
9223 9223 Status, upper word (monitor block)StatusMonitor_High · Bits 0 to 15 correspond to status bits 16 to 31: event input 1 to 4, write mode (0 backup, 1 RAM write), non-volatile memory mismatch, setup area (0 or 1), AT execution, RUN/STOP (1 stop), communications writing enabled, auto/manual (1 manual), program start, heater overcurrent CT2, heater current hold CT2, spare, HS alarm CT2. bitfield16 1 1 R Holding (FC03)
9224 9224 Status 2, lower wordStatus2Monitor_Low · Bits 0 to 7 are work bits 1 to 8; other bits spare. bitfield16 1 1 R Holding (FC03)
9225 9225 Status 2, upper wordStatus2Monitor_High · Bit 0 and 1 event input 5 and 6, bit 4 invert direct/reverse operation, bit 5 SP ramp, bit 11 SP mode (1 remote), bit 12 alarm 4. Other bits spare. bitfield16 1 1 R Holding (FC03)
9232 9232 Decimal point monitorDecimalPointMonitor · 0 to 3. Number of decimal places applied to PV and SP values. uint16 1 1 R Holding (FC03)
9472 9472 Operation/adjustment protectOperationAdjustProtect · 0 no restriction, 1 move to adjustment level prohibited, 2 only PV and PV/SP parameters may be shown and changed, 3 only PV and PV/SP may be shown. uint16 1 1 RW Holding (FC03)
9474 9474 Setting change protectSettingChangeProtect · 0 changing setup from the front panel allowed, 1 prohibited. uint16 1 1 RW Holding (FC03)
9728 9728 Manual MVManualMv · Standard control: -5.0 to 105.0. Heating and cooling control: -105.0 to 105.0. int16 1 0.1 RW Holding (FC03)
9729 9729 Set point (listed under manual control level)SetPointManualLevel · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 RW Holding (FC03)
9730 9730 Remote SP monitorRemoteSpMonitor · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 R Holding (FC03)
9732 9732 Heater current 1 value monitor (operation level)HeaterCurrent1MonitorOp · Listed range 0.0 to 55.0. uint16 1 0.1 R Holding (FC03)
9733 9733 MV monitor, heating (operation level)MvMonitorHeatingOp int16 1 0.1 R Holding (FC03)
9734 9734 MV monitor, cooling (operation level)MvMonitorCoolingOp uint16 1 0.1 R Holding (FC03)
9735 9735 Valve opening monitor (position-proportional models)ValveOpeningMonitor · Measured opening -10.0 to 110.0, or estimated opening 0.0 to 100.0 on supported models. int16 1 0.1 R Holding (FC03)
9985 9985 Proportional band (cooling)ProportionalBandCooling · Listed range 0.1 to 999.9. uint16 1 0.1 RW Holding (FC03)
9990 9990 Hysteresis (heating)HysteresisHeating · 0.1 to 999.9 for temperature input, 0.01 to 99.99 for analog input; stored without decimal point. uint16 1 1 RW Holding (FC03)
9991 9991 Hysteresis (cooling)HysteresisCooling · Same format as heating hysteresis. uint16 1 1 RW Holding (FC03)
9992 9992 Control period (heating)ControlPeriodHeating · -2 means 0.1 s, -1 means 0.2 s, 0 means 0.5 s, 1 to 99 is the period in seconds. int16 1 1 RW Holding (FC03)
10024 10024 Soak time remainingSoakTimeRemain · Listed range 0 to 9999. uint16 1 1 R Holding (FC03)
10025 10025 Soak timeSoakTime · Listed range 1 to 9999. uint16 1 1 RW Holding (FC03)
10496 10496 Set point 0Sp0 · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 RW Holding (FC03)
10498 10498 Alarm value 1AlarmValue1 · Listed range -1999 to 9999. int16 1 1 RW Holding (FC03)
10501 10501 Alarm value 2AlarmValue2 · Listed range -1999 to 9999. int16 1 1 RW Holding (FC03)
10504 10504 Alarm value 3AlarmValue3 · Listed range -1999 to 9999. int16 1 1 RW Holding (FC03)
10507 10507 Alarm value 4AlarmValue4 · Listed range -1999 to 9999. int16 1 1 RW Holding (FC03)
10510 10510 Set point 1Sp1 · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 RW Holding (FC03)
10524 10524 Set point 2Sp2 · Integer with the decimal point removed; the decimal place count is given by the Decimal Point Monitor register (hex 2410). int16 1 1 RW Holding (FC03)
10752 10752 Proportional bandProportionalBand · Listed range 0.1 to 999.9. uint16 1 0.1 RW Holding (FC03)
10753 10753 Integral timeIntegralTime · 0 to 9999 when the time unit is 1 s, 0.0 to 999.9 when it is 0.1 s; stored without decimal point. uint16 1 1 RW Holding (FC03)
10754 10754 Derivative timeDerivativeTime · Same format as integral time. uint16 1 1 RW Holding (FC03)
10757 10757 MV upper limitMvUpperLimit · Up to 105.0. int16 1 0.1 RW Holding (FC03)
10758 10758 MV lower limitMvLowerLimit · Standard control from -5.0; heating and cooling control -105.0 to 0.0. int16 1 0.1 RW Holding (FC03)
11264 11264 Input typeInputType · 0 to 30 selects the sensor or analog range, for example 0 Pt -200 to 850 degC, 5 K -200 to 1300 degC, 25 4 to 20 mA. Full list in the manual. uint16 1 1 RW Holding (FC03)
11265 11265 Temperature unitTemperatureUnit · 0 degC, 1 degF. uint16 1 1 RW Holding (FC03)
11273 11273 Scaling lower limitScalingLower · Listed range -1999 up to scaling upper limit minus 1. int16 1 1 RW Holding (FC03)
11275 11275 Scaling upper limitScalingUpper · Scaling lower limit plus 1 up to 9999. int16 1 1 RW Holding (FC03)
11276 11276 Decimal pointDecimalPoint · 0 to 3. uint16 1 1 RW Holding (FC03)
11535 11535 SP upper limitSpUpperLimit · Value without decimal point. int16 1 1 RW Holding (FC03)
11536 11536 SP lower limitSpLowerLimit · Value without decimal point. int16 1 1 RW Holding (FC03)
11537 11537 Standard or heating/cooling controlStandardOrHeatCool · 0 standard, 1 heating and cooling. uint16 1 1 RW Holding (FC03)
11538 11538 Direct/reverse operationDirectReverse · 0 reverse operation, 1 direct operation. uint16 1 1 RW Holding (FC03)
11540 11540 PID or ON/OFF controlPidOnOff · 0 ON/OFF, 1 2-PID control. uint16 1 1 RW Holding (FC03)
11541 11541 ST (self-tuning)AutoTuneSt · 0 off, 1 on. uint16 1 1 RW Holding (FC03)
12032 12032 Alarm 1 typeAlarm1Type · 0 alarm off, 1 upper and lower limit, 2 upper limit, 3 lower limit, up to 19; the full type list is in the manual. uint16 1 1 RW Holding (FC03)
12034 12034 Alarm 1 hysteresisAlarm1Hysteresis · 0.1 to 999.9 for temperature input, 0.01 to 99.99 for analog input; stored without decimal point. uint16 1 1 RW Holding (FC03)
12035 12035 Alarm 2 typeAlarm2Type · Same codes as alarm 1 type. uint16 1 1 RW Holding (FC03)
12038 12038 Alarm 3 typeAlarm3Type · Same codes as alarm 1 type. uint16 1 1 RW Holding (FC03)
12041 12041 Alarm 4 typeAlarm4Type · Same codes as alarm 1 type. uint16 1 1 RW Holding (FC03)
12544 12544 Protocol settingProtocolSetting · 0 CompoWay/F, 1 Modbus. uint16 1 1 RW Holding (FC03)
12545 12545 Communications unit numberUnitNo · 0 to 99. uint16 1 1 RW Holding (FC03)
12546 12546 Communications baud rateBaudRate · 3 is 9.6 kbit/s, 4 is 19.2, 5 is 38.4, 6 is 57.6. uint16 1 1 RW Holding (FC03)
12547 12547 Communications data lengthDataLength · 7 or 8 bits. Must be 8 for Modbus. uint16 1 1 RW Holding (FC03)
12548 12548 Communications stop bitsStopBits · 1 or 2. uint16 1 1 RW Holding (FC03)
12549 12549 Communications parityParity · 0 none, 1 even, 2 odd. uint16 1 1 RW Holding (FC03)
12550 12550 Send data wait timeSendDataWait · 0 to 99. Default is 20 ms. uint16 1 ms 1 RW Holding (FC03)

Scale is the number to multiply the raw value by to get the unit.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: E5@C Digital Temperature Controllers Communications Manual (H175) (files.omron.eu)

Cat. No. H175, document code H175-E1-17, p. 1-6, 3-23 to 3-26, 4-7 to 4-13, 5-1 to 5-16. Read on 2026-10-24.

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.