Autonics TK Series Modbus register map

Panel-mount PID temperature controllers with heating and cooling outputs and an optional RS-485 port. The communication manual lists the coil, discrete input, input register and holding register map for the TK series over Modbus RTU.

Protocol
Modbus RTU (RS-485)
Defaults
Factory settings listed in the map: communication address 01, 9600 bps, parity none, 2 stop bits, response waiting time 20 ms. Broadcast commands are not supported.
Addresses in the manual
Modicon style numbers (for example 40001 is holding register 0)
32 and 64-bit values
Not stated in the manual
Registers listed
85
Checked against
Autonics TK Series communication manual, document code MCT-TKC1-V01.7-1701EN

Address base. Each table prints a Modicon-style number with the hex wire address in brackets, for example holding 400001 (0000H) and input register 301001 (03E8H). The worked read examples on pp. 11-14 confirm the frame carries the bracketed value, so wire address equals the printed number minus 400001 for holding registers, minus 300001 for input registers, minus 100001 for discrete inputs and minus 1 for coils. For example 1 in the manual (Control output run or stop) is address 0 on the wire.

Word order. Every value in the map is a single 16-bit register, so word order does not apply. Decimal place count for temperature values is given by the decimal point location register 301002, and several settings are shown in the manual with an implied decimal point.

Modbus Poll and the Modbus protocol itself count from 0. The "Wire address" column is the number to type into Modbus Poll.

Downloads

The register table has every column on this page. The blocks file imports into Modbus Poll. The template JSON holds the same blocks plus unit, scale and access for scripts.

Registers

85 registers
Manual Wire Register Type Regs Unit Scale Access Area
1 0 Control output run or stopRunStop · 0 run, 1 stop. bool 1 1 RW Coil (FC01)
2 1 Auto-tuning run or stopAutoTuneRun · 0 off, 1 on. bool 1 1 RW Coil (FC01)
100001 0 Degrees C indicatorIndC · 1 means on. bool 1 1 R Discrete (FC02)
100002 1 Degrees F indicatorIndF · 1 means on. bool 1 1 R Discrete (FC02)
100003 2 Percent indicatorIndPercent · 1 means on. bool 1 1 R Discrete (FC02)
100004 3 Control output 1 indicatorOut1Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100005 4 Control output 2 indicatorOut2Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100006 5 Auto-tuning indicatorAtIndicator · 1 means on. bool 1 1 R Discrete (FC02)
100007 6 Multi SV 1 indicatorSv1Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100008 7 Multi SV 2 indicatorSv2Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100009 8 Multi SV 3 indicatorSv3Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100010 9 Alarm output 1 indicatorAl1Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100011 10 Alarm output 2 indicatorAl2Indicator · 1 means on. bool 1 1 R Discrete (FC02)
100012 11 Manual control indicatorManIndicator · 1 means on. bool 1 1 R Discrete (FC02)
100013 12 Digital input 1 stateDi1Input · 1 means on. bool 1 1 R Discrete (FC02)
100014 13 Digital input 2 stateDi2Input · 1 means on. bool 1 1 R Discrete (FC02)
300103 102 Hardware versionHardwareVersion uint16 1 1 R Input (FC04)
300104 103 Software versionSoftwareVersion uint16 1 1 R Input (FC04)
300105 104 Model name textModelName · Ten registers holding the model name pieces (product name, display rows, option output, power type, output types). string 10 1 R Input (FC04)
301001 1000 Present valuePV · Range -1999 to 9999. Decimal places are given by register 301002. int16 1 1 R Input (FC04)
301002 1001 Decimal point locationDecimalPointLocation · 0 no decimal, 1 one decimal place, 2 two, 3 three. uint16 1 1 R Input (FC04)
301003 1002 Indicator unitIndicatorUnit · 0 degC, 1 degF, 2 and 3 other unit displays listed in the manual. uint16 1 1 R Input (FC04)
301004 1003 SV setting value (read-only copy)SvSettingValue · Within the L-SV to H-SV limits. int16 1 1 R Input (FC04)
301005 1004 Heating side MVHeatingMv · Raw range 0 to 1000. uint16 1 % 0.1 R Input (FC04)
301006 1005 Cooling side MVCoolingMv · Raw range 0 to 1000. uint16 1 % 0.1 R Input (FC04)
301007 1006 Indicator and digital input status bitsIndicatorStatus · Bit 0 degC, 1 degF, 2 percent, 3 OUT1, 4 OUT2, 5 AT, 6 SV1, 7 SV2, 8 SV3, 9 AL1, 10 AL2, 11 MAN, 12 DI-1, 13 DI-2. bitfield16 1 1 R Input (FC04)
301008 1007 Heater current value monitorHeaterCurrentMonitor · Listed range 0.0 to 50.0. Scale is inferred from that range. uint16 1 A 0.1 R Input (FC04)
400001 0 SV set valueSv · Within the L-SV to H-SV limits. Decimal places follow the decimal point setting. int16 1 1 RW Holding (FC03)
400002 1 Heating MVHeatingMvSet · Raw range 0 to 1000. uint16 1 % 0.1 RW Holding (FC03)
400003 2 Cooling MVCoolingMvSet · Raw range 0 to 1000. uint16 1 % 0.1 RW Holding (FC03)
400004 3 Auto or manual controlAutoManual · 0 auto, 1 manual. uint16 1 1 RW Holding (FC03)
400051 50 Control output run or stop parameterRunStopParam · 0 run, 1 stop. uint16 1 1 RW Holding (FC03)
400052 51 Multi SV numberMultiSvNumber · 0 to 3 selects SV-0 to SV-3. uint16 1 1 RW Holding (FC03)
400053 52 Heater current monitoringHeaterCurrentParam · Raw range 0 to 500. The manual lists this under a read/write group although it is a monitoring item. uint16 1 A 0.1 RW Holding (FC03)
400054 53 Alarm output 1 low-limit set valueAl1Low int16 1 1 RW Holding (FC03)
400055 54 Alarm output 1 high-limit set valueAl1High int16 1 1 RW Holding (FC03)
400056 55 Alarm output 2 low-limit set valueAl2Low int16 1 1 RW Holding (FC03)
400057 56 Alarm output 2 high-limit set valueAl2High int16 1 1 RW Holding (FC03)
400058 57 Set value SV-0Sv0 · Within the L-SV to H-SV limits. int16 1 1 RW Holding (FC03)
400059 58 Set value SV-1Sv1 · Within the L-SV to H-SV limits. int16 1 1 RW Holding (FC03)
400060 59 Set value SV-2Sv2 · Within the L-SV to H-SV limits. int16 1 1 RW Holding (FC03)
400061 60 Set value SV-3Sv3 · Within the L-SV to H-SV limits. int16 1 1 RW Holding (FC03)
400062 61 Alarm output 3 low-limit set valueAl3Low int16 1 1 RW Holding (FC03)
400063 62 Alarm output 3 high-limit set valueAl3High int16 1 1 RW Holding (FC03)
400101 100 Auto-tuning run or stopAutoTuning · 0 off, 1 on. uint16 1 1 RW Holding (FC03)
400102 101 Heating proportional bandHeatingProportionalBand · Raw range 1 to 9999; decimal placement depends on input type. uint16 1 1 RW Holding (FC03)
400103 102 Cooling proportional bandCoolingProportionalBand · Raw range 1 to 9999. uint16 1 1 RW Holding (FC03)
400104 103 Heating integral timeHeatingIntegralTime · Range 0 to 9999. uint16 1 s 1 RW Holding (FC03)
400105 104 Cooling integral timeCoolingIntegralTime · Range 0 to 9999. uint16 1 s 1 RW Holding (FC03)
400106 105 Heating derivative timeHeatingDerivativeTime · Range 0 to 9999. uint16 1 s 1 RW Holding (FC03)
400107 106 Cooling derivative timeCoolingDerivativeTime · Range 0 to 9999. uint16 1 s 1 RW Holding (FC03)
400108 107 Dead or overlap bandDeadOverlapBand int16 1 1 RW Holding (FC03)
400110 109 Heating hysteresisHeatingHysteresis uint16 1 1 RW Holding (FC03)
400114 113 MV low-limit set valueMvLowLimit · Printed with one decimal place. The heating and cooling control range starts below zero, so the value is signed. int16 1 % 0.1 RW Holding (FC03)
400115 114 MV high-limit set valueMvHighLimit · Raw range up to 1000, printed as up to 100.0 %. uint16 1 % 0.1 RW Holding (FC03)
400118 117 Ramp time unitRampTimeUnit · 0 seconds, 1 minutes, 2 hours. uint16 1 1 RW Holding (FC03)
400151 150 Input typeInputType · Code for the sensor or analog input; the manual refers to the input specification order. uint16 1 1 RW Holding (FC03)
400152 151 Sensor temperature unitSensorTempUnit · 0 degC, 1 degF. uint16 1 1 RW Holding (FC03)
400155 154 Scaling decimal pointScalingDecimalPoint · 0 to 3 decimal places. uint16 1 1 RW Holding (FC03)
400158 157 Display unitDisplayUnit · 0 degC, 1 degF, 2 and 3 other displays listed in the manual. uint16 1 1 RW Holding (FC03)
400159 158 Input correctionInputCorrection int16 1 1 RW Holding (FC03)
400160 159 Input digital filterInputDigitalFilter · Raw range 1 to 1200, which the manual prints as 0.1 to 120.0 s. uint16 1 s 0.1 RW Holding (FC03)
400161 160 SV low-limit set valueLowSvLimit int16 1 1 RW Holding (FC03)
400162 161 SV high-limit set valueHighSvLimit int16 1 1 RW Holding (FC03)
400163 162 Control output operation modeControlOutputMode · Standard type: 0 heat, 1 cool. Heating and cooling type: 0 heat, 1 cool, 2 heat-cool. uint16 1 1 RW Holding (FC03)
400164 163 Control typeControlType · Standard control: 0 PID, 1 ONOF. Heating and cooling control: codes pP (0), Pon (1), OnP (2), OnON (3) as printed. uint16 1 1 RW Holding (FC03)
400165 164 Auto-tuning modeAutoTuningMode · 0 TUN1, 1 TUN2. uint16 1 1 RW Holding (FC03)
400166 165 OUT1 control output selectionOut1Selection · 0 SSR, 1 current. uint16 1 1 RW Holding (FC03)
400171 170 Heating control timeHeatingControlTime uint16 1 s 1 RW Holding (FC03)
400172 171 Cooling control timeCoolingControlTime uint16 1 s 1 RW Holding (FC03)
400201 200 Alarm output 1 operation modeAl1Mode · 0 is off; codes 1 to 9 are listed in the manual and include LBA (7), SBA (8) and HBA (9). uint16 1 1 RW Holding (FC03)
400203 202 Alarm output 1 hysteresisAl1Hysteresis uint16 1 1 RW Holding (FC03)
400204 203 Alarm output 1 normally open or closedAl1NoNc · 0 N.O., 1 N.C. uint16 1 1 RW Holding (FC03)
400205 204 Alarm output 1 ON delayAl1OnDelay · Range 0 to 3600. uint16 1 s 1 RW Holding (FC03)
400206 205 Alarm output 1 OFF delayAl1OffDelay · Range 0 to 3600. uint16 1 s 1 RW Holding (FC03)
400207 206 Alarm output 2 operation modeAl2Mode · Same code list as alarm 1 mode. uint16 1 1 RW Holding (FC03)
400219 218 Communication addressCommAddress · 1 to 99. Factory default 01. uint16 1 1 RW Holding (FC03)
400220 219 Communication speedCommSpeed · 0 is 2400 bps, 1 is 4800, 2 is 9600, 3 is 19200, 4 is 38400 (values shown in units of 100 bps). Factory default 9600. uint16 1 1 RW Holding (FC03)
400221 220 Communication parityCommParity · 0 none, 1 even, 2 odd. Factory default none. uint16 1 1 RW Holding (FC03)
400222 221 Communication stop bitsCommStopBits · 0 is 1 bit, 1 is 2 bits. Factory default 2 bits. uint16 1 1 RW Holding (FC03)
400223 222 Communication response waiting timeCommResponseWait · Range 5 to 99. Factory default 20 ms. uint16 1 ms 1 RW Holding (FC03)
400224 223 Communication write enableCommWrite · 0 enabled, 1 disabled. uint16 1 1 RW Holding (FC03)
400253 252 DI-1 terminal functionDi1Function · 0 off, 1 stop, 2 alarm reset, 3 manual, 4 multi SV. uint16 1 1 RW Holding (FC03)
400254 253 DI-2 terminal functionDi2Function · Same list as DI-1. uint16 1 1 RW Holding (FC03)
400268 267 Password settingPassword · 0000 is off, 0002 to 9999 sets a password, 0001 is a read-only password. uint16 1 1 RW Holding (FC03)

Scale is the number to multiply the raw value by to get the unit. Types with more than one register (32 and 64-bit) follow the word order above.

Open in Modbus Poll

  1. Download the Modbus Poll blocks file.
  2. Open Modbus Poll, connect to the device and set its unit ID. The manual does not state the word order for 32-bit values. Check one known value (a voltage or a counter) and switch the setting if it reads wrong.
  3. In the blocks panel on the right, click Import CSV and pick the file. CSV import is a Pro feature. Without Pro, Modbus Poll polls the first 20 values of your blocks.
  4. The wire addresses are already in the file, so there is no 0-based or 1-based conversion to do.

Once the values look right, export the tag list to Ignition, Kepware, Node-RED, Home Assistant or Voltrus SCADA.

Source and accuracy

Manufacturer document: User Manual for Communication, TK Series (www.instrumart.com)

Autonics TK Series communication manual, document code MCT-TKC1-V01.7-1701EN, p. 11-27. Read on 2026-10-24.

Also used: Autonics TK series manuals (www.autonics.com)

Addresses, types, units and scale are taken from the document above. Names and descriptions are written by Voltrus. Firmware versions can differ, so confirm a value on your own device before you rely on it.

Found a mistake? Report it by email with the register address and the manual page.