  "format": "voltrus-device-template/1",
  "template_id": "yaskawa-v1000",
  "manufacturer": "Yaskawa",
  "model": "V1000",
  "protocol": "modbus",
  "description": "Compact vector control AC drive with a built-in RS-422/RS-485 MEMOBUS/Modbus RTU slave port. The data table covers the run and frequency command registers, drive status, fault and alarm bit words, live monitors, fault codes and the Enter command, and the parameter registers listed here include the communication settings (H5). This file lists the data table plus selected parameters; the full parameter list is in the manual. Register map: https://voltrus.id/registers/yaskawa/v1000/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from SIEP C710606 19B, published in Japan December 2011. Yaskawa PDF as hosted by Omron Europe; copy hosted by a third party, vendor-hosted copy could not be fetched. (https://assets.omron.eu/downloads/latest/manual/en/v1000_users_manual_en.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 0-based addresses, the same as here.",
    "Word order from the manual: High word first (AB CD).",
    "The data table gives accumulated operation time and cooling fan operation time as a high word at the lower register and a low word at the next register (0098H and 0099H, 009AH and 009BH), so 32-bit values are high word first. All other rows are single 16-bit registers.",
    "The device speaks Modbus RTU. Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Per the parameter list: node address 1FH (H5-01), 9600 bps (H5-02 = 3), no parity (H5-03 = 0); data length 8 bit and 1 stop bit are fixed. Slave addresses 0 to 20H are allowed and address 0 is broadcast with no response. Control over Modbus needs b1-01 = 2 and b1-02 = 2. H5-01 to H5-03 need a power cycle to take effect.",
    "2 unsigned 32-bit registers are read as int32: exact up to a raw value of 2,147,483,647.",
    "Not included, because templates have no 64-bit integer or string type: ProductCode1, ProductCode2."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "CommandWord",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Run command and multi-function input command word (manual address 1)",
      "writable": true
    },
    {
      "name": "FrequencyReference",
      "offset": 2,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency reference (manual address 2)",
      "writable": true
    },
    {
      "name": "OutputVoltageGain",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Output voltage gain (manual address 3)",
      "writable": true
    },
    {
      "name": "PidTarget",
      "offset": 6,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID target (manual address 6)",
      "writable": true
    },
    {
      "name": "AnalogOutputAmSetting",
      "offset": 7,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Analog output terminal AM setting (manual address 7)",
      "writable": true
    },
    {
      "name": "DigitalOutputSettings",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Settings for multi-function digital outputs (manual address 9)",
      "writable": true
    },
    {
      "name": "PulseOutputMpSetting",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "Pulse output terminal MP setting (manual address 10)",
      "writable": true
    },
    {
      "name": "ControlSelectionSetting",
      "offset": 15,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control selection setting (manual address 15)",
      "writable": true
    },
    {
      "name": "DriveStatus1",
      "offset": 32,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive status 1 (manual address 32)"
    },
    {
      "name": "FaultContents1",
      "offset": 33,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 1 (manual address 33)"
    },
    {
      "name": "DataLinkStatus",
      "offset": 34,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Data link status (manual address 34)"
    },
    {
      "name": "FrequencyReferenceMonitor",
      "offset": 35,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency reference monitor (manual address 35)"
    },
    {
      "name": "OutputFrequency",
      "offset": 36,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency (manual address 36)"
    },
    {
      "name": "OutputVoltageReference",
      "offset": 37,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "Output voltage reference (manual address 37)"
    },
    {
      "name": "OutputCurrent",
      "offset": 38,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Output current (manual address 38)"
    },
    {
      "name": "FaultContents2",
      "offset": 41,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 2 (manual address 41)"
    },
    {
      "name": "AlarmContents1",
      "offset": 42,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm contents 1 (manual address 42)"
    },
    {
      "name": "InputTerminalStatus",
      "offset": 43,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Input terminal status (manual address 43)"
    },
    {
      "name": "DriveStatus2",
      "offset": 44,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive status 2 (manual address 44)"
    },
    {
      "name": "OutputTerminalStatus",
      "offset": 45,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Output terminal status (manual address 45)"
    },
    {
      "name": "DcBusVoltage",
      "offset": 49,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "DC bus voltage (manual address 49)"
    },
    {
      "name": "PidFeedback",
      "offset": 56,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID feedback (manual address 56)"
    },
    {
      "name": "PidInput",
      "offset": 57,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID input (manual address 57)"
    },
    {
      "name": "PidOutput",
      "offset": 58,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID output (manual address 58)"
    },
    {
      "name": "CommunicationsErrorLog",
      "offset": 61,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Communications error log (manual address 61)"
    },
    {
      "name": "OutputFrequencyRpm",
      "offset": 62,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "r/min",
      "description": "Output frequency in r/min (manual address 62)"
    },
    {
      "name": "OutputFrequencyPercent",
      "offset": 63,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Output frequency in percent (manual address 63)"
    },
    {
      "name": "U1_04_ControlMode",
      "offset": 67,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U1-04 control mode (manual address 67)"
    },
    {
      "name": "DriveStatusU1_12",
      "offset": 75,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive status (U1-12) (manual address 75)"
    },
    {
      "name": "U1_25_SoftwareNumberFlash",
      "offset": 77,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U1-25 software number (Flash) (manual address 77)"
    },
    {
      "name": "U1_26_SoftwareNumberRom",
      "offset": 91,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U1-26 software number (ROM) (manual address 91)"
    },
    {
      "name": "AlarmCode",
      "offset": 127,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm code (manual address 127)"
    },
    {
      "name": "U2_01_CurrentFault",
      "offset": 128,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U2-01 current fault (manual address 128)"
    },
    {
      "name": "U2_02_PreviousFault",
      "offset": 129,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U2-02 previous fault (manual address 129)"
    },
    {
      "name": "U3_01_MostRecentFault",
      "offset": 144,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U3-01 most recent fault (manual address 144)"
    },
    {
      "name": "U3_02_SecondMostRecentFault",
      "offset": 145,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U3-02 second most recent fault (manual address 145)"
    },
    {
      "name": "U3_03_ThirdMostRecentFault",
      "offset": 146,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U3-03 third most recent fault (manual address 146)"
    },
    {
      "name": "U3_04_FourthMostRecentFault",
      "offset": 147,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "U3-04 fourth most recent fault (manual address 147)"
    },
    {
      "name": "U4_01_AccumulatedOperationTime",
      "offset": 152,
      "register_type": "int32",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "U4-01 accumulated operation time (manual address 152)"
    },
    {
      "name": "U4_03_CoolingFanOperationTime",
      "offset": 154,
      "register_type": "int32",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "U4-03 cooling fan operation time (manual address 154)"
    },
    {
      "name": "DriveRatedCurrent",
      "offset": 171,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Drive rated current (manual address 171)"
    },
    {
      "name": "OptionCode",
      "offset": 176,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Option code (manual address 176)"
    },
    {
      "name": "OpeErrorNumber",
      "offset": 191,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "oPE error number (manual address 191)"
    },
    {
      "name": "FaultContents3",
      "offset": 192,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 3 (manual address 192)"
    },
    {
      "name": "FaultContents4",
      "offset": 193,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 4 (manual address 193)"
    },
    {
      "name": "FaultContents5",
      "offset": 194,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 5 (manual address 194)"
    },
    {
      "name": "FaultContents6",
      "offset": 195,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 6 (manual address 195)"
    },
    {
      "name": "FaultContents7",
      "offset": 196,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents 7 (manual address 196)"
    },
    {
      "name": "AlarmContents2",
      "offset": 200,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm contents 2 (manual address 200)"
    },
    {
      "name": "AlarmContents3",
      "offset": 201,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm contents 3 (manual address 201)"
    },
    {
      "name": "AlarmContents4",
      "offset": 202,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm contents 4 (manual address 202)"
    },
    {
      "name": "AlarmContents5",
      "offset": 203,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm contents 5 (manual address 203)"
    },
    {
      "name": "CpfContents1",
      "offset": 208,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "CPF contents 1 (manual address 208)"
    },
    {
      "name": "CpfContents2",
      "offset": 209,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "CPF contents 2 (manual address 209)"
    },
    {
      "name": "OptionCardFaultContents",
      "offset": 216,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Option card fault contents (manual address 216)"
    },
    {
      "name": "b1_01_FrequencyReferenceSelection1",
      "offset": 384,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-01 frequency reference selection 1 (manual address 384)",
      "writable": true
    },
    {
      "name": "b1_02_RunCommandSelection1",
      "offset": 385,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-02 run command selection 1 (manual address 385)",
      "writable": true
    },
    {
      "name": "b1_03_StoppingMethodSelection",
      "offset": 386,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-03 stopping method selection (manual address 386)",
      "writable": true
    },
    {
      "name": "b1_04_ReverseOperationSelection",
      "offset": 387,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-04 reverse operation selection (manual address 387)",
      "writable": true
    },
    {
      "name": "C1_01_AccelerationTime1",
      "offset": 512,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "C1-01 acceleration time 1 (manual address 512)",
      "writable": true
    },
    {
      "name": "C1_02_DecelerationTime1",
      "offset": 513,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "C1-02 deceleration time 1 (manual address 513)",
      "writable": true
    },
    {
      "name": "C1_03_AccelerationTime2",
      "offset": 514,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "C1-03 acceleration time 2 (manual address 514)",
      "writable": true
    },
    {
      "name": "C1_04_DecelerationTime2",
      "offset": 515,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "C1-04 deceleration time 2 (manual address 515)",
      "writable": true
    },
    {
      "name": "C1_10_AccelDecelTimeUnits",
      "offset": 521,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "C1-10 accel/decel time setting units (manual address 521)",
      "writable": true
    },
    {
      "name": "d1_01_FrequencyReference1",
      "offset": 640,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "d1-01 frequency reference 1 (manual address 640)",
      "writable": true
    },
    {
      "name": "d1_02_FrequencyReference2",
      "offset": 641,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "d1-02 frequency reference 2 (manual address 641)",
      "writable": true
    },
    {
      "name": "d1_03_FrequencyReference3",
      "offset": 642,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "d1-03 frequency reference 3 (manual address 642)",
      "writable": true
    },
    {
      "name": "d1_04_FrequencyReference4",
      "offset": 643,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "d1-04 frequency reference 4 (manual address 643)",
      "writable": true
    },
    {
      "name": "d2_01_FrequencyReferenceUpperLimit",
      "offset": 649,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "d2-01 frequency reference upper limit (manual address 649)",
      "writable": true
    },
    {
      "name": "d2_02_FrequencyReferenceLowerLimit",
      "offset": 650,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "d2-02 frequency reference lower limit (manual address 650)",
      "writable": true
    },
    {
      "name": "E1_04_MaxOutputFrequency",
      "offset": 771,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "E1-04 maximum output frequency (manual address 771)",
      "writable": true
    },
    {
      "name": "E1_05_MaxOutputVoltage",
      "offset": 772,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "E1-05 maximum output voltage (manual address 772)",
      "writable": true
    },
    {
      "name": "E1_06_BaseFrequency",
      "offset": 773,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "E1-06 base frequency (manual address 773)",
      "writable": true
    },
    {
      "name": "E1_09_MinOutputFrequency",
      "offset": 776,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "E1-09 minimum output frequency (manual address 776)",
      "writable": true
    },
    {
      "name": "E2_01_MotorRatedCurrent",
      "offset": 782,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "E2-01 motor rated current (manual address 782)",
      "writable": true
    },
    {
      "name": "E2_04_NumberOfMotorPoles",
      "offset": 785,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "E2-04 number of motor poles (manual address 785)",
      "writable": true
    },
    {
      "name": "H5_01_DriveNodeAddress",
      "offset": 1061,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-01 drive node address (manual address 1061)",
      "writable": true
    },
    {
      "name": "H5_02_CommunicationSpeedSelection",
      "offset": 1062,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-02 communication speed selection (manual address 1062)",
      "writable": true
    },
    {
      "name": "H5_03_CommunicationParitySelection",
      "offset": 1063,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-03 communication parity selection (manual address 1063)",
      "writable": true
    },
    {
      "name": "H5_04_StoppingMethodAfterCommError",
      "offset": 1064,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-04 stopping method after communication error (manual address 1064)",
      "writable": true
    },
    {
      "name": "H5_05_CommunicationFaultDetection",
      "offset": 1065,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-05 communication fault detection selection (manual address 1065)",
      "writable": true
    },
    {
      "name": "H5_06_DriveTransmitWaitTime",
      "offset": 1066,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "ms",
      "description": "H5-06 drive transmit wait time (manual address 1066)",
      "writable": true
    },
    {
      "name": "H5_07_RtsControlSelection",
      "offset": 1067,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-07 RTS control selection (manual address 1067)",
      "writable": true
    },
    {
      "name": "H5_09_CeDetectionTime",
      "offset": 1077,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "H5-09 CE detection time (manual address 1077)",
      "writable": true
    },
    {
      "name": "H5_10_UnitSelectionRegister0025H",
      "offset": 1078,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-10 unit selection for MEMOBUS/Modbus register 0025H (manual address 1078)",
      "writable": true
    },
    {
      "name": "H5_11_EnterFunctionSelection",
      "offset": 1084,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-11 communications Enter function selection (manual address 1084)",
      "writable": true
    },
    {
      "name": "H5_12_RunCommandMethodSelection",
      "offset": 1085,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-12 run command method selection (manual address 1085)",
      "writable": true
    },
    {
      "name": "L1_01_MotorOverloadProtectionSelection",
      "offset": 1152,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "L1-01 motor overload protection selection (manual address 1152)",
      "writable": true
    },
    {
      "name": "o1_03_DigitalOperatorDisplaySelection",
      "offset": 1282,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "o1-03 digital operator display selection (manual address 1282)",
      "writable": true
    },
    {
      "name": "EnterCommandSaveToEeprom",
      "offset": 2304,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Enter command: write data to EEPROM and enable it in RAM (manual address 2304)",
      "writable": true
    },
    {
      "name": "EnterCommandRamOnly",
      "offset": 2320,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Enter command: write data to RAM only (manual address 2320)",
      "writable": true
    }
  ]
}