  "format": "voltrus-device-template/1",
  "template_id": "yaskawa-ga500",
  "manufacturer": "Yaskawa",
  "model": "GA500",
  "protocol": "modbus",
  "description": "Compact AC micro drive with a built-in RS-485 MEMOBUS/Modbus RTU slave port. The map covers the run and frequency command registers, live monitor and fault bit words, and parameter registers including the communication settings. Register map: https://voltrus.id/registers/yaskawa/ga500/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from SIEPC71061753B, revision 1 (December 2019). Yaskawa PDF as hosted by the distributor TME (https://www.tme.eu/Document/79d9547dcea8e1be4406f2eedcb830c7/GA500-EN-INS-FULL.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 0-based addresses, the same as here.",
    "The manual does not state the word order for 32 and 64-bit values; big (AB CD) is set. Check one known value and change it if it reads wrong.",
    "Every row is a single 16-bit register. Long counters such as operation time are split across two registers by the drive, see the notes.",
    "The device speaks Modbus RTU. Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Per the parameter list: node address 1FH (H5-01), 9600 bps (H5-02 = 3), no parity (H5-03 = 0). The drive does not answer while H5-01 is 0. Control over Modbus needs b1-01 = 2 and b1-02 = 2.",
    "Not included, because templates have no 64-bit integer or string type: ProductCode1, ProductCode2."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "CommandWord",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Run command and multi-function input command word (manual address 1)",
      "writable": true
    },
    {
      "name": "FrequencyReference",
      "offset": 2,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency reference (manual address 2)",
      "writable": true
    },
    {
      "name": "OutputVoltageGain",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Output voltage gain (manual address 3)",
      "writable": true
    },
    {
      "name": "TorqueLimit",
      "offset": 4,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Torque limit (manual address 4)",
      "writable": true
    },
    {
      "name": "TorqueCompensation",
      "offset": 5,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Torque compensation (manual address 5)",
      "writable": true
    },
    {
      "name": "PIDSetpoint",
      "offset": 6,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID setpoint (manual address 6)",
      "writable": true
    },
    {
      "name": "AnalogMonitorOutputAM",
      "offset": 7,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Setting for multi-function analog monitor output AM (manual address 7)",
      "writable": true
    },
    {
      "name": "MFDOSetting",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Multi-function digital output setting (manual address 9)",
      "writable": true
    },
    {
      "name": "PulseTrainOutput",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "Pulse train output frequency (manual address 10)",
      "writable": true
    },
    {
      "name": "CommandSelection",
      "offset": 15,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Command selection setting (manual address 15)",
      "writable": true
    },
    {
      "name": "DriveStatus1",
      "offset": 32,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive status word 1 (manual address 32)"
    },
    {
      "name": "FaultDescription1",
      "offset": 33,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault description word 1 (manual address 33)"
    },
    {
      "name": "FaultContents",
      "offset": 34,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault contents (data write status) (manual address 34)"
    },
    {
      "name": "FrequencyReferenceMonitor",
      "offset": 35,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency reference monitor (U1-01) (manual address 35)"
    },
    {
      "name": "OutputFrequencyMonitor",
      "offset": 36,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency (U1-02) (manual address 36)"
    },
    {
      "name": "OutputVoltageReference",
      "offset": 37,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "Output voltage reference (U1-06) (manual address 37)"
    },
    {
      "name": "OutputCurrent",
      "offset": 38,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "A",
      "description": "Output current (U1-03) (manual address 38)"
    },
    {
      "name": "OutputPower",
      "offset": 39,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Output power (U1-08) (manual address 39)"
    },
    {
      "name": "TorqueReference",
      "offset": 40,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Torque reference (U1-09) (manual address 40)"
    },
    {
      "name": "FaultDescription2",
      "offset": 41,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault description word 2 (manual address 41)"
    },
    {
      "name": "MinorFaultDescription1",
      "offset": 42,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Minor fault (alarm) description word 1 (manual address 42)"
    },
    {
      "name": "InputTerminalStatus",
      "offset": 43,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Input terminal status (U1-10) (manual address 43)"
    },
    {
      "name": "DriveStatus2",
      "offset": 44,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive status word 2 (manual address 44)"
    },
    {
      "name": "OutputTerminalStatus",
      "offset": 45,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Output terminal status (U1-11) (manual address 45)"
    },
    {
      "name": "DCBusVoltage",
      "offset": 49,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "DC bus voltage (U1-07) (manual address 49)"
    },
    {
      "name": "TorqueReference1Pct",
      "offset": 50,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Torque reference (U1-09), 1 percent units (manual address 50)"
    },
    {
      "name": "PIDFeedback",
      "offset": 56,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID feedback (manual address 56)"
    },
    {
      "name": "PIDInput",
      "offset": 57,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID input (manual address 57)"
    },
    {
      "name": "PIDOutput",
      "offset": 58,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID output (manual address 58)"
    },
    {
      "name": "CommErrorDescription",
      "offset": 61,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Communication error description (manual address 61)"
    },
    {
      "name": "OutputFrequencyRPM",
      "offset": 62,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "r/min",
      "description": "Output frequency in r/min (manual address 62)"
    },
    {
      "name": "OutputFrequencyPercent",
      "offset": 63,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Output frequency in 0.01 percent units (manual address 63)"
    },
    {
      "name": "OutputCurrentRated",
      "offset": 66,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Output current (U1-03), rated-current scale (manual address 66)"
    },
    {
      "name": "ControlMethod",
      "offset": 67,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control method in use (U1-04) (manual address 67)"
    },
    {
      "name": "DriveStatusU1_12",
      "offset": 75,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive status (U1-12) (manual address 75)"
    },
    {
      "name": "MinorFaultCode",
      "offset": 127,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Minor fault code (manual address 127)"
    },
    {
      "name": "ElapsedTimeHigh",
      "offset": 152,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Cumulative operation time (U4-01), upper part (manual address 152)"
    },
    {
      "name": "ElapsedTimeLow",
      "offset": 153,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Cumulative operation time (U4-01), last digit (manual address 153)"
    },
    {
      "name": "FanTimeHigh",
      "offset": 154,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Cooling fan operation time (U4-03), upper part (manual address 154)"
    },
    {
      "name": "FanTimeLow",
      "offset": 155,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Cooling fan operation time (U4-03), last digit (manual address 155)"
    },
    {
      "name": "DriveRatedCurrent",
      "offset": 171,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Drive rated current (manual address 171)"
    },
    {
      "name": "MotorSpeedRPM",
      "offset": 172,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "r/min",
      "description": "Motor speed (U1-05) in r/min (manual address 172)"
    },
    {
      "name": "MotorSpeedPercent",
      "offset": 173,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Motor speed (U1-05) in 0.01 percent units (manual address 173)"
    },
    {
      "name": "b1_01_FrequencyReferenceSelection1",
      "offset": 384,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-01 frequency reference source (manual address 384)",
      "writable": true
    },
    {
      "name": "b1_02_RunCommandSelection1",
      "offset": 385,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-02 run command source (manual address 385)",
      "writable": true
    },
    {
      "name": "b1_03_StoppingMethod",
      "offset": 386,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "b1-03 stopping method (manual address 386)",
      "writable": true
    },
    {
      "name": "C1_01_AccelerationTime1",
      "offset": 512,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "C1-01 acceleration time 1 (manual address 512)",
      "writable": true
    },
    {
      "name": "C1_02_DecelerationTime1",
      "offset": 513,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "C1-02 deceleration time 1 (manual address 513)",
      "writable": true
    },
    {
      "name": "d1_01_Reference1",
      "offset": 640,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "d1-01 preset frequency reference 1 (manual address 640)",
      "writable": true
    },
    {
      "name": "E1_04_MaxOutputFrequency",
      "offset": 771,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "E1-04 maximum output frequency (manual address 771)",
      "writable": true
    },
    {
      "name": "E1_05_MaxOutputVoltage",
      "offset": 772,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "E1-05 maximum output voltage (manual address 772)",
      "writable": true
    },
    {
      "name": "E1_06_BaseFrequency",
      "offset": 773,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "E1-06 base frequency (manual address 773)",
      "writable": true
    },
    {
      "name": "E2_01_MotorRatedCurrent",
      "offset": 782,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "E2-01 motor rated current (FLA) (manual address 782)",
      "writable": true
    },
    {
      "name": "H5_01_DriveNodeAddress",
      "offset": 1061,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-01 drive node address (manual address 1061)",
      "writable": true
    },
    {
      "name": "H5_02_CommSpeedSelection",
      "offset": 1062,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-02 communication speed selection (manual address 1062)",
      "writable": true
    },
    {
      "name": "H5_03_CommParitySelection",
      "offset": 1063,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-03 communication parity selection (manual address 1063)",
      "writable": true
    },
    {
      "name": "H5_04_CommErrorStopMethod",
      "offset": 1064,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-04 stop method on communication error (manual address 1064)",
      "writable": true
    },
    {
      "name": "H5_05_CommFaultDetection",
      "offset": 1065,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-05 communication fault detection (manual address 1065)",
      "writable": true
    },
    {
      "name": "H5_06_TransmitWaitTime",
      "offset": 1066,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "ms",
      "description": "H5-06 drive transmit wait time (manual address 1066)",
      "writable": true
    },
    {
      "name": "H5_09_CEDetectionTime",
      "offset": 1077,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-09 communication error detection time (manual address 1077)",
      "writable": true
    },
    {
      "name": "H5_10_Register0025Unit",
      "offset": 1078,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-10 unit for register 0025H (manual address 1078)",
      "writable": true
    },
    {
      "name": "H5_11_EnterCommandMode",
      "offset": 1084,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-11 Enter command mode (manual address 1084)",
      "writable": true
    },
    {
      "name": "H5_12_RunCommandMethod",
      "offset": 1085,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "H5-12 run command method (manual address 1085)",
      "writable": true
    },
    {
      "name": "o1_03_FrequencyDisplayUnit",
      "offset": 1282,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "o1-03 frequency display unit (manual address 1282)",
      "writable": true
    },
    {
      "name": "EnterCommandEEPROM",
      "offset": 2304,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Enter command, save to EEPROM and enable (manual address 2304)",
      "writable": true
    },
    {
      "name": "EnterCommandRAM",
      "offset": 2320,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Enter command, enable in RAM only (manual address 2320)",
      "writable": true
    }
  ]
}