  "format": "voltrus-device-template/1",
  "template_id": "solax-power-energy-storage-inverter",
  "manufacturer": "SolaX Power",
  "model": "X1 and X3 energy storage inverters",
  "protocol": "modbus",
  "description": "One Modbus register map from SolaX for its single-phase (X1) and three-phase (X3) energy storage inverters. The document lists the inverters that share the map by name and inverter ID. It covers firmware and serial data, status and fault words, PV, grid, meter, battery and energy history values, and the common operating settings. The inverter reports its own type code, and some registers apply only to X1 or only to X3. This file is a selection of the document, not every register: battery serial numbers, time of use and charge period tables, generator, VPP, parallel and other settings are left out. Register map: https://voltrus.id/registers/solax-power/energy-storage-inverter/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from Version V001.02, revision dated 2026/2/10, SolaX Power Network Technology (Zhejiang) Co., Ltd. (copy hosted by a third party; a vendor-hosted copy could not be fetched, and the SolaX knowledge base tells integrators to ask SolaX for the document) (https://community.symcon.de/uploads/short-url/ecxNpsZsby8yDD7kHPxv4Gz6ENS.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 0-based addresses, the same as here.",
    "Word order from the manual: Low word first (CD AB).",
    "For 32-bit values the tables label the first register address LSB and the second MSB (for example 0x0052 LSB, 0x0053 MSB for Etotal_Togrid), so the low word comes first. The VPP example on p. 76 confirms this: ACActivePower of -1000 W is sent as 0xFC18 then 0xFFFF. Bytes inside each register are big endian (p. 3). The document does not define its Gain column (the changelog only says the attribute was added to all tables in V001.00),",
    "so the meaning is inferred: a raw register value equals the physical value times Gain, and scale here is 1 divided by Gain (gain 10 gives scale 0.1, gain 100 gives 0.01, gain 1000 gives 0.001). This is the only reading that fits the document's own ranges: the cell voltage gain of 1000 on a V unit only makes sense for millivolt counts, and the export power limit (Table 3.5.2) prints gain X1: 1 and X3: 0.1 with ranges 0 to 60000 W (X1) and 0 to 30000 W (X3) in a 16-bit register,",
    "which fits only if an X3 count is 10 W. The document gives no worked example for a register with a gain other than 1.",
    "Defaults from the manual: Slave address 1 (default), allowed 1 to 247. RS485: 19200 baud (default), 8 data bits, 1 stop bit, no parity (p. 2). Modbus TCP via the monitoring module: port 502, unit ID 0x01 by default (p. 3). The document asks for at least 1 s between two instructions and a response timeout of 1 s (p. 4).",
    "26 unsigned 32-bit registers are read as int32: exact up to a raw value of 2,147,483,647.",
    "Not included, because templates have no 64-bit integer or string type: Inverter_SN, Factory_Name, Inverter_Name, Module_SN."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "little",
  "registers": [
    {
      "name": "Inverter_Type",
      "offset": 21,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Inverter type code (manual address 21)"
    },
    {
      "name": "Bat_Port_Num",
      "offset": 89,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Total battery port number (manual address 89)"
    },
    {
      "name": "Firmware_Version_DSP",
      "offset": 123,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Full DSP firmware version (manual address 123)"
    },
    {
      "name": "Firmware_Version_ARM",
      "offset": 124,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Full ARM firmware version (manual address 124)"
    },
    {
      "name": "Firmware_Version_DSP_Minor",
      "offset": 125,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Minor DSP software version (manual address 125)"
    },
    {
      "name": "Hardware_Version",
      "offset": 126,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Hardware version (manual address 126)"
    },
    {
      "name": "Firmware_Version_DSP_Major",
      "offset": 127,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Major DSP software version (manual address 127)"
    },
    {
      "name": "Firmware_Version_ARM_Major",
      "offset": 128,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Major ARM software version (manual address 128)"
    },
    {
      "name": "Firmware_Version_Modbus",
      "offset": 130,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Modbus protocol document version supported by the firmware (manual address 130)"
    },
    {
      "name": "Firmware_Version_ARM_Minor",
      "offset": 131,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Minor ARM software version (manual address 131)"
    },
    {
      "name": "Firmware_Version_ARM_Boot",
      "offset": 132,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "ARM bootloader version (manual address 132)"
    },
    {
      "name": "RTC_Seconds",
      "offset": 133,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Real time clock, seconds (manual address 133)"
    },
    {
      "name": "RTC_Minutes",
      "offset": 134,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Real time clock, minutes (manual address 134)"
    },
    {
      "name": "RTC_Hours",
      "offset": 135,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Real time clock, hours (manual address 135)"
    },
    {
      "name": "RTC_Days",
      "offset": 136,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Real time clock, days (manual address 136)"
    },
    {
      "name": "RTC_Months",
      "offset": 137,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Real time clock, months (manual address 137)"
    },
    {
      "name": "RTC_Years",
      "offset": 138,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Real time clock, years (manual address 138)"
    },
    {
      "name": "Rated_Output_Power",
      "offset": 186,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "W",
      "description": "Inverter rated AC output power (manual address 186)"
    },
    {
      "name": "Inverter_Run_Mode",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Inverter working mode code (manual address 9)"
    },
    {
      "name": "Inverter_Lock_State",
      "offset": 84,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Parameter unlock status (manual address 84)"
    },
    {
      "name": "Inverter_Fault_Message",
      "offset": 64,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "Inverter fault bit field (manual address 64)"
    },
    {
      "name": "Inv_Fault_Message_Extend",
      "offset": 94,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "Inverter fault bit field, extended (manual address 94)"
    },
    {
      "name": "Manager_Fault_Message",
      "offset": 67,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Manager fault bit field (manual address 67)"
    },
    {
      "name": "BMS1_Fault_Message",
      "offset": 68,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "BMS1 fault bit field (manual address 68)"
    },
    {
      "name": "BMS1_Fault_Message_Extend",
      "offset": 214,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "BMS1 fault bit field, extended (manual address 214)"
    },
    {
      "name": "BMS2_Fault_Message",
      "offset": 298,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "BMS2 fault bit field (manual address 298)"
    },
    {
      "name": "BMS2_Fault_Message_Extend",
      "offset": 775,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "BMS2 fault bit field, extended (manual address 775)"
    },
    {
      "name": "Pv_Power_Sum",
      "offset": 50,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Sum of all PV power (manual address 50)"
    },
    {
      "name": "On_Grid_Power_Sum",
      "offset": 52,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "On-grid total active power of the inverter (manual address 52)"
    },
    {
      "name": "Off_Grid_Power_Sum",
      "offset": 54,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Off-grid total active power of the inverter (manual address 54)"
    },
    {
      "name": "Bat_Power_Sum",
      "offset": 56,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Total power of the battery system (manual address 56)"
    },
    {
      "name": "Bat_Sys_Installed_Capacity",
      "offset": 58,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Wh",
      "description": "Total capacity of the battery system (manual address 58)"
    },
    {
      "name": "Bat_System_SOC",
      "offset": 60,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Total SOC of the battery system (manual address 60)"
    },
    {
      "name": "Bat_System_SOH",
      "offset": 61,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Total SOH of the battery system (manual address 61)"
    },
    {
      "name": "MPPT_Count",
      "offset": 27,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Total number of PV strings (manual address 27)"
    },
    {
      "name": "Pv_Voltage1",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "PV1 voltage (manual address 3)"
    },
    {
      "name": "Pv_Current1",
      "offset": 5,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "PV1 current (manual address 5)"
    },
    {
      "name": "Pv_Power1",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "PV1 power (manual address 10)"
    },
    {
      "name": "Pv_Voltage2",
      "offset": 4,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "PV2 voltage (manual address 4)"
    },
    {
      "name": "Pv_Current2",
      "offset": 6,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "PV2 current (manual address 6)"
    },
    {
      "name": "Pv_Power2",
      "offset": 11,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "PV2 power (manual address 11)"
    },
    {
      "name": "Pv_Voltage3",
      "offset": 290,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "PV3 voltage (manual address 290)"
    },
    {
      "name": "Pv_Current3",
      "offset": 291,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "PV3 current (manual address 291)"
    },
    {
      "name": "Pv_Power3",
      "offset": 292,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "PV3 power (manual address 292)"
    },
    {
      "name": "Pv_Voltage4",
      "offset": 40,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "PV4 voltage (manual address 40)"
    },
    {
      "name": "Pv_Current4",
      "offset": 43,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "PV4 current (manual address 43)"
    },
    {
      "name": "Pv_Power4",
      "offset": 46,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "PV4 power (manual address 46)"
    },
    {
      "name": "Pv_Voltage5",
      "offset": 41,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "PV5 voltage (manual address 41)"
    },
    {
      "name": "Pv_Current5",
      "offset": 44,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "PV5 current (manual address 44)"
    },
    {
      "name": "Pv_Power5",
      "offset": 47,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "PV5 power (manual address 47)"
    },
    {
      "name": "Pv_Voltage6",
      "offset": 42,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "PV6 voltage (manual address 42)"
    },
    {
      "name": "Pv_Current6",
      "offset": 45,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "PV6 current (manual address 45)"
    },
    {
      "name": "Pv_Power6",
      "offset": 48,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "PV6 power (manual address 48)"
    },
    {
      "name": "Grid_Status",
      "offset": 26,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Grid status (manual address 26)"
    },
    {
      "name": "Grid_Voltage_X1",
      "offset": 0,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "On-grid voltage, single-phase inverter (manual address 0)"
    },
    {
      "name": "Grid_Current_X1",
      "offset": 1,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "On-grid current, single-phase inverter (manual address 1)"
    },
    {
      "name": "Grid_Power_X1",
      "offset": 2,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "On-grid active power, single-phase inverter (manual address 2)"
    },
    {
      "name": "Grid_Frequency_X1",
      "offset": 7,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "On-grid frequency, single-phase inverter (manual address 7)"
    },
    {
      "name": "Grid_Voltage_R_X3",
      "offset": 106,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "R-phase on-grid voltage, three-phase inverter (manual address 106)"
    },
    {
      "name": "Grid_Current_R_X3",
      "offset": 107,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "R-phase on-grid current, three-phase inverter (manual address 107)"
    },
    {
      "name": "Grid_Power_R_X3",
      "offset": 108,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "R-phase on-grid active power, three-phase inverter (manual address 108)"
    },
    {
      "name": "Grid_Frequency_R_X3",
      "offset": 109,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "R-phase on-grid frequency, three-phase inverter (manual address 109)"
    },
    {
      "name": "Grid_Voltage_S_X3",
      "offset": 110,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "S-phase on-grid voltage, three-phase inverter (manual address 110)"
    },
    {
      "name": "Grid_Current_S_X3",
      "offset": 111,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "S-phase on-grid current, three-phase inverter (manual address 111)"
    },
    {
      "name": "Grid_Power_S_X3",
      "offset": 112,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "S-phase on-grid active power, three-phase inverter (manual address 112)"
    },
    {
      "name": "Grid_Frequency_S_X3",
      "offset": 113,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "S-phase on-grid frequency, three-phase inverter (manual address 113)"
    },
    {
      "name": "Grid_Voltage_T_X3",
      "offset": 114,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "T-phase on-grid voltage, three-phase inverter (manual address 114)"
    },
    {
      "name": "Grid_Current_T_X3",
      "offset": 115,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "T-phase on-grid current, three-phase inverter (manual address 115)"
    },
    {
      "name": "Grid_Power_T_X3",
      "offset": 116,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "T-phase on-grid active power, three-phase inverter (manual address 116)"
    },
    {
      "name": "Grid_Frequency_T_X3",
      "offset": 117,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "T-phase on-grid frequency, three-phase inverter (manual address 117)"
    },
    {
      "name": "Grid_Reactive_Power_Sum",
      "offset": 96,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "On-grid total reactive power of the inverter (manual address 96)"
    },
    {
      "name": "Grid_Apparent_Power_Sum",
      "offset": 98,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "On-grid total apparent power of the inverter (manual address 98)"
    },
    {
      "name": "Grid_Reactive_Power_R",
      "offset": 100,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "R-phase on-grid reactive power (manual address 100)"
    },
    {
      "name": "Grid_Reactive_Power_S",
      "offset": 101,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "S-phase on-grid reactive power (manual address 101)"
    },
    {
      "name": "Grid_Reactive_Power_T",
      "offset": 102,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "T-phase on-grid reactive power (manual address 102)"
    },
    {
      "name": "Grid_Apparent_Power_R",
      "offset": 103,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "R-phase on-grid apparent power (manual address 103)"
    },
    {
      "name": "Grid_Apparent_Power_S",
      "offset": 104,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "S-phase on-grid apparent power (manual address 104)"
    },
    {
      "name": "Grid_Apparent_Power_T",
      "offset": 105,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "T-phase on-grid apparent power (manual address 105)"
    },
    {
      "name": "On_Grid_Run_Time",
      "offset": 136,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "h",
      "description": "On-grid run time (manual address 136)"
    },
    {
      "name": "Off_Grid_Voltage_X1",
      "offset": 76,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "Off-grid voltage, single-phase inverter (manual address 76)"
    },
    {
      "name": "Off_Grid_Current_X1",
      "offset": 77,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "Off-grid current, single-phase inverter (manual address 77)"
    },
    {
      "name": "Off_Grid_Power_X1",
      "offset": 78,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "Off-grid power, single-phase inverter (manual address 78)"
    },
    {
      "name": "Off_Grid_Frequency",
      "offset": 79,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Off-grid frequency (manual address 79)"
    },
    {
      "name": "Off_Grid_Volt_R_X3",
      "offset": 118,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "R-phase off-grid voltage, three-phase inverter (manual address 118)"
    },
    {
      "name": "Off_Grid_Current_R_X3",
      "offset": 119,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "R-phase off-grid current, three-phase inverter (manual address 119)"
    },
    {
      "name": "Off_Grid_Power_R_X3",
      "offset": 120,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "R-phase off-grid active power, three-phase inverter (manual address 120)"
    },
    {
      "name": "Off_Grid_Power_Apparent_R_X3",
      "offset": 121,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "R-phase off-grid apparent power, three-phase inverter (manual address 121)"
    },
    {
      "name": "Off_Grid_Volt_S_X3",
      "offset": 122,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "S-phase off-grid voltage, three-phase inverter (manual address 122)"
    },
    {
      "name": "Off_Grid_Current_S_X3",
      "offset": 123,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "S-phase off-grid current, three-phase inverter (manual address 123)"
    },
    {
      "name": "Off_Grid_Power_S_X3",
      "offset": 124,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "S-phase off-grid active power, three-phase inverter (manual address 124)"
    },
    {
      "name": "Off_Grid_Power_Apparent_S_X3",
      "offset": 125,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "S-phase off-grid apparent power, three-phase inverter (manual address 125)"
    },
    {
      "name": "Off_Grid_Volt_T_X3",
      "offset": 126,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "T-phase off-grid voltage, three-phase inverter (manual address 126)"
    },
    {
      "name": "Off_Grid_Current_T_X3",
      "offset": 127,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "T-phase off-grid current, three-phase inverter (manual address 127)"
    },
    {
      "name": "Off_Grid_Power_T_X3",
      "offset": 128,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "T-phase off-grid active power, three-phase inverter (manual address 128)"
    },
    {
      "name": "Off_Grid_Power_Apparent_T_X3",
      "offset": 129,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "VA",
      "description": "T-phase off-grid apparent power, three-phase inverter (manual address 129)"
    },
    {
      "name": "Off_Grid_Run_Time",
      "offset": 138,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "h",
      "description": "Off-grid run time (manual address 138)"
    },
    {
      "name": "Feedin_Power",
      "offset": 70,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Power at the grid connection point measured by meter or CT (manual address 70)"
    },
    {
      "name": "Feedin_Power_R_Phase_X3",
      "offset": 130,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "R-phase feed-in power (meter or CT), three-phase inverter (manual address 130)"
    },
    {
      "name": "Feedin_Power_S_Phase_X3",
      "offset": 132,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "S-phase feed-in power (meter or CT), three-phase inverter (manual address 132)"
    },
    {
      "name": "Feedin_Power_T_Phase_X3",
      "offset": 134,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "T-phase feed-in power (meter or CT), three-phase inverter (manual address 134)"
    },
    {
      "name": "Grid_Reactive_Power_Total_Meter",
      "offset": 210,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "Total reactive power (meter or CT) (manual address 210)"
    },
    {
      "name": "Grid_Reactive_Power_R_Meter",
      "offset": 222,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "R-phase reactive power (meter or CT) (manual address 222)"
    },
    {
      "name": "Grid_Reactive_Power_S_Meter",
      "offset": 224,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "S-phase reactive power (meter or CT) (manual address 224)"
    },
    {
      "name": "Grid_Reactive_Power_T_Meter",
      "offset": 212,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Var",
      "description": "T-phase reactive power (meter or CT) (manual address 212)"
    },
    {
      "name": "Grid_Power_Factor_Total_Meter",
      "offset": 196,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Total grid power factor (meter or CT) (manual address 196)"
    },
    {
      "name": "Grid_Power_Factor_R_Meter",
      "offset": 197,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "R-phase grid power factor (meter or CT) (manual address 197)"
    },
    {
      "name": "Grid_Power_Factor_S_Meter",
      "offset": 198,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "S-phase grid power factor (meter or CT) (manual address 198)"
    },
    {
      "name": "Grid_Power_Factor_T_Meter",
      "offset": 199,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "T-phase grid power factor (meter or CT) (manual address 199)"
    },
    {
      "name": "Grid_Frequency_Meter",
      "offset": 200,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Grid frequency (meter or CT) (manual address 200)"
    },
    {
      "name": "Grid_Voltage_Total_Meter",
      "offset": 201,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "Total grid voltage (meter or CT) (manual address 201)"
    },
    {
      "name": "Grid_Voltage_R_Meter",
      "offset": 202,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "R-phase grid voltage (meter or CT) (manual address 202)"
    },
    {
      "name": "Grid_Voltage_S_Meter",
      "offset": 203,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "S-phase grid voltage (meter or CT) (manual address 203)"
    },
    {
      "name": "Grid_Voltage_T_Meter",
      "offset": 204,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "T-phase grid voltage (meter or CT) (manual address 204)"
    },
    {
      "name": "Grid_Current_Total_Meter",
      "offset": 205,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "Total grid current (meter or CT) (manual address 205)"
    },
    {
      "name": "Grid_Current_R_Meter",
      "offset": 206,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "R-phase grid current (meter or CT) (manual address 206)"
    },
    {
      "name": "Grid_Current_S_Meter",
      "offset": 207,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "S-phase grid current (meter or CT) (manual address 207)"
    },
    {
      "name": "Grid_Current_T_Meter",
      "offset": 208,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "T-phase grid current (meter or CT) (manual address 208)"
    },
    {
      "name": "Meter1_Communication_State",
      "offset": 184,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Communication state of meter 1 (manual address 184)"
    },
    {
      "name": "Meter2_Communication_State",
      "offset": 185,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Communication state of meter 2 (manual address 185)"
    },
    {
      "name": "Feedin_Power_Meter2",
      "offset": 168,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Power value of meter 2 or CT2 (manual address 168)"
    },
    {
      "name": "Feedin_Power_R_Phase_Meter2",
      "offset": 178,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "R-phase power of meter 2 or CT2 (manual address 178)"
    },
    {
      "name": "Feedin_Power_S_Phase_Meter2",
      "offset": 180,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "S-phase power of meter 2 or CT2 (manual address 180)"
    },
    {
      "name": "Feedin_Power_T_Phase_Meter2",
      "offset": 182,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "T-phase power of meter 2 or CT2 (manual address 182)"
    },
    {
      "name": "BMS1_Connect_State",
      "offset": 23,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "BMS1 connection state (manual address 23)"
    },
    {
      "name": "BMS2_Connect_State",
      "offset": 31,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "BMS2 connection state (manual address 31)"
    },
    {
      "name": "Bat1_Temperature",
      "offset": 24,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "degC",
      "description": "BMS1 ambient temperature (manual address 24)"
    },
    {
      "name": "Bat2_Temperature",
      "offset": 305,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "degC",
      "description": "BMS2 ambient temperature (manual address 305)"
    },
    {
      "name": "Bat_Voltage_Charge1",
      "offset": 20,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "BMS1 voltage (manual address 20)"
    },
    {
      "name": "Bat_Current_Charge1",
      "offset": 21,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "BMS1 current (manual address 21)"
    },
    {
      "name": "Bat_Power_Charge1",
      "offset": 22,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "BMS1 power (manual address 22)"
    },
    {
      "name": "Bat_Voltage_Charge2",
      "offset": 295,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "BMS2 voltage (manual address 295)"
    },
    {
      "name": "Bat_Current_Charge2",
      "offset": 296,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "BMS2 current (manual address 296)"
    },
    {
      "name": "Bat_Power_Charge2",
      "offset": 297,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "BMS2 power (manual address 297)"
    },
    {
      "name": "BDC_Status",
      "offset": 25,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "BMS charging and discharging status (manual address 25)"
    },
    {
      "name": "Battery1_Capacity",
      "offset": 28,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "BMS1 SOC (manual address 28)"
    },
    {
      "name": "Battery2_Capacity",
      "offset": 301,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "BMS2 SOC (manual address 301)"
    },
    {
      "name": "BMS1_SOH",
      "offset": 191,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "BMS1 SOH (manual address 191)"
    },
    {
      "name": "BMS2_SOH",
      "offset": 785,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "BMS2 SOH (manual address 785)"
    },
    {
      "name": "BMS1_Charge_Max_Current",
      "offset": 36,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "BMS1 maximum charge current (manual address 36)"
    },
    {
      "name": "BMS1_Discharge_Max_Current",
      "offset": 37,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "BMS1 maximum discharge current (manual address 37)"
    },
    {
      "name": "BMS1_Battery_Capacity",
      "offset": 38,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "Wh",
      "description": "BMS1 battery capacity (manual address 38)"
    },
    {
      "name": "BMS1_Cell_Temp_High",
      "offset": 186,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "degC",
      "description": "BMS1 cell high temperature (manual address 186)"
    },
    {
      "name": "BMS1_Cell_Temp_Low",
      "offset": 187,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "degC",
      "description": "BMS1 cell low temperature (manual address 187)"
    },
    {
      "name": "BMS1_Cell_Voltage_High",
      "offset": 188,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.001,
      "unit": "V",
      "description": "BMS1 cell high voltage (manual address 188)"
    },
    {
      "name": "BMS1_Cell_Voltage_Low",
      "offset": 189,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.001,
      "unit": "V",
      "description": "BMS1 cell low voltage (manual address 189)"
    },
    {
      "name": "BMS2_Charge_Max_Current",
      "offset": 777,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "BMS2 maximum charge current (manual address 777)"
    },
    {
      "name": "BMS2_Discharge_Max_Current",
      "offset": 778,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "A",
      "description": "BMS2 maximum discharge current (manual address 778)"
    },
    {
      "name": "Battery2_Temp_High",
      "offset": 768,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "degC",
      "description": "BMS2 cell high temperature (manual address 768)"
    },
    {
      "name": "Battery2_Temp_Low",
      "offset": 769,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "degC",
      "description": "BMS2 cell low temperature (manual address 769)"
    },
    {
      "name": "Bat2_Cell_Voltage_High",
      "offset": 770,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.001,
      "unit": "V",
      "description": "BMS2 cell high voltage (manual address 770)"
    },
    {
      "name": "Bat2_Cell_Voltage_Low",
      "offset": 771,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.001,
      "unit": "V",
      "description": "BMS2 cell low voltage (manual address 771)"
    },
    {
      "name": "Bat_Max_Allowed_Chg_Power",
      "offset": 162,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Battery maximum allowed charge power (manual address 162)"
    },
    {
      "name": "Bat_Max_Allowed_Dischg_Power",
      "offset": 164,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "W",
      "description": "Battery maximum allowed discharge power (manual address 164)"
    },
    {
      "name": "Etoday_Togrid",
      "offset": 80,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Today's on-grid output energy (inverter grid port) (manual address 80)"
    },
    {
      "name": "Etotal_Togrid",
      "offset": 82,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Total on-grid output energy (inverter grid port) (manual address 82)"
    },
    {
      "name": "Echarge_Today",
      "offset": 145,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Today's on-grid input energy (inverter grid port) (manual address 145)"
    },
    {
      "name": "Echarge_Total",
      "offset": 146,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Total on-grid input energy (inverter grid port) (manual address 146)"
    },
    {
      "name": "Off_Grid_Yield_Today",
      "offset": 144,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Off-grid yield (register named Today), inverter EPS port (manual address 144)"
    },
    {
      "name": "Off_Grid_Yield_Total",
      "offset": 142,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Off-grid yield (register named Total), inverter EPS port (manual address 142)"
    },
    {
      "name": "Feedin_Energy_Today",
      "offset": 152,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Today's output energy (meter 1 or CT1) (manual address 152)"
    },
    {
      "name": "Feedin_Energy_Total",
      "offset": 72,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Total output energy (meter 1 or CT1) (manual address 72)"
    },
    {
      "name": "Consum_Energy_Today",
      "offset": 154,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Today's input energy (meter 1 or CT1) (manual address 154)"
    },
    {
      "name": "Consum_Energy_Total",
      "offset": 74,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Total input energy (meter 1 or CT1) (manual address 74)"
    },
    {
      "name": "Consum_Energy_Today_Meter2",
      "offset": 176,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Today's input energy (meter 2 or CT2) (manual address 176)"
    },
    {
      "name": "Consum_Energy_Total_Meter2",
      "offset": 172,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Total input energy (meter 2 or CT2) (manual address 172)"
    },
    {
      "name": "Feedin_Energy_Today_Meter2",
      "offset": 174,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Today's output energy (meter 2 or CT2) (manual address 174)"
    },
    {
      "name": "Feedin_Energy_Total_Meter2",
      "offset": 170,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Total output energy (meter 2 or CT2) (manual address 170)"
    },
    {
      "name": "Solar_Energy_Total",
      "offset": 148,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Total PV energy (inverter PV port) (manual address 148)"
    },
    {
      "name": "Solar_Energy_Today",
      "offset": 150,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Today's PV energy (inverter PV port) (manual address 150)"
    },
    {
      "name": "Bat_Discharge_Energy_Total",
      "offset": 29,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Total battery discharge energy (inverter battery port) (manual address 29)"
    },
    {
      "name": "Bat_Discharge_Energy_Today",
      "offset": 32,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Today's battery discharge energy (inverter battery port) (manual address 32)"
    },
    {
      "name": "Bat_Charge_Energy_Total",
      "offset": 33,
      "register_type": "int32",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Total battery charge energy (inverter battery port) (manual address 33)"
    },
    {
      "name": "Bat_Charge_Energy_Today",
      "offset": 35,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kWh",
      "description": "Today's battery charge energy (inverter battery port) (manual address 35)"
    },
    {
      "name": "Inverter_Output_Switch",
      "offset": 218,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "System on or off (manual address 218)",
      "writable": true
    },
    {
      "name": "Safety_Code",
      "offset": 29,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Safety code (manual address 29)",
      "writable": true
    },
    {
      "name": "Inverter_Work_Mode",
      "offset": 139,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Inverter work mode (manual address 139)",
      "writable": true
    },
    {
      "name": "SelfUse_Min_SOC_And_Grid_Charge",
      "offset": 147,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Self use mode: discharge cut-off SOC (high byte) and charge from grid enable (low byte) (manual address 147)",
      "writable": true
    },
    {
      "name": "SelfUse_Charge_Upper_SOC",
      "offset": 148,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Self use mode: charge upper SOC (manual address 148)",
      "writable": true
    },
    {
      "name": "Feedin_Soc_Limits",
      "offset": 149,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Feed-in mode: charging cut-off SOC (high byte) and discharging cut-off SOC (low byte) (manual address 149)",
      "writable": true
    },
    {
      "name": "BackUp_Soc_Limits",
      "offset": 150,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Backup mode: charging cut-off SOC (high byte) and discharging cut-off SOC (low byte) (manual address 150)",
      "writable": true
    },
    {
      "name": "Manual_Mode",
      "offset": 140,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Manual mode command (manual address 140)",
      "writable": true
    },
    {
      "name": "Export_Power_Percentage",
      "offset": 37,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Export power control limit percentage (inverter grid port) (manual address 37)",
      "writable": true
    },
    {
      "name": "Main_Breaker_Current_Limit",
      "offset": 215,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Main breaker current limit (manual address 215)",
      "writable": true
    },
    {
      "name": "Inv_Max_Set_Bat_Cur",
      "offset": 92,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "A",
      "description": "Inverter maximum battery current setting (manual address 92)"
    },
    {
      "name": "Bat_Charge_Max_Current",
      "offset": 144,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "A",
      "description": "Battery charge maximum current (manual address 144)",
      "writable": true
    },
    {
      "name": "Bat_Discharge_Max_Current",
      "offset": 145,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "A",
      "description": "Battery discharge maximum current (manual address 145)",
      "writable": true
    },
    {
      "name": "Bat_Charge_Max_SOC",
      "offset": 270,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Lithium battery charger upper limit (manual address 270)",
      "writable": true
    },
    {
      "name": "Meter_CT_Select",
      "offset": 277,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Meter or CT selection (manual address 277)",
      "writable": true
    },
    {
      "name": "Meter1_ID",
      "offset": 265,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Meter 1 ID (manual address 265)",
      "writable": true
    },
    {
      "name": "Meter2_ID",
      "offset": 266,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Meter 2 ID (manual address 266)",
      "writable": true
    },
    {
      "name": "Direction_Meter_CT1",
      "offset": 267,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Meter or CT 1 direction (manual address 267)",
      "writable": true
    },
    {
      "name": "Direction_Meter_CT2",
      "offset": 268,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Meter or CT 2 direction (manual address 268)",
      "writable": true
    },
    {
      "name": "EPS_Frequency",
      "offset": 185,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Output frequency in EPS (off-grid) mode (manual address 185)",
      "writable": true
    },
    {
      "name": "EPS_Restart_Soc",
      "offset": 160,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "SOC to charge to before restoring EPS (off-grid) mode (manual address 160)",
      "writable": true
    }
  ]
}