  "format": "voltrus-device-template/1",
  "template_id": "siemens-sinamics-v20",
  "manufacturer": "Siemens",
  "model": "SINAMICS V20",
  "protocol": "modbus",
  "description": "Compact low-voltage inverter with a built-in RS485 port that can run as a Modbus RTU slave. The manual gives a fixed register table (40001 to 40559) for control, status, setpoints, ramp times, PID settings, fault codes and measured values, each linked to an inverter parameter. Register map: https://voltrus.id/registers/siemens/sinamics-v20/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from A5E34559884-006, 11/2016 (Siemens-hosted copy, chapter 7.2 MODBUS communication) (https://cache.industry.siemens.com/dl/files/991/109743991/att_906061/v1/V20_op_instr_1116_en-US.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints Modicon numbers such as 40001.",
    "The manual does not state the word order for 32 and 64-bit values; big (AB CD) is set. Check one known value and change it if it reads wrong.",
    "All table registers are single 16-bit values. The parameter value upper word and lower word registers (40554, 40555, 40558, 40559) are described only by name; the manual does not state how they combine.",
    "The device speaks Modbus RTU (RS485); function codes 3, 6 and 16 only. Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Select Modbus with P2023 = 2 (factory default 1, USS) and power cycle the inverter. Factory defaults printed: baud rate 9600 bit/s (P2010[0] = 6), Modbus address 1 (P2021, range 1 to 247), reply timeout 1000 ms (P2022), parity even (P2034 = 2; 0 none, 1 odd, 2 even), 1 stop bit (P2035 = 1; 1 or 2). The parameter list (p. 273 to 274) notes P2034 must be 0 when P2035 = 2 and P2035 must be 2 when P2034 = 0. Command source P0700 = 5 selects USS/MODBUS on RS485."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "Watchdog_Time",
      "offset": 0,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "ms",
      "description": "Watchdog time (manual address 40001)",
      "writable": true
    },
    {
      "name": "Watchdog_Action",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Watchdog action (manual address 40002)",
      "writable": true
    },
    {
      "name": "Frequency_Setpoint",
      "offset": 2,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Frequency setpoint, percent of reference frequency (manual address 40003)",
      "writable": true
    },
    {
      "name": "Run_Enable",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Run enable (manual address 40004)",
      "writable": true
    },
    {
      "name": "Forward_Reverse_Command",
      "offset": 4,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Forward/reverse command (manual address 40005)",
      "writable": true
    },
    {
      "name": "Start_Command",
      "offset": 5,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Start command (manual address 40006)",
      "writable": true
    },
    {
      "name": "Fault_Acknowledge",
      "offset": 6,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault acknowledgement (manual address 40007)",
      "writable": true
    },
    {
      "name": "PID_Setpoint_Reference",
      "offset": 7,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID setpoint reference (manual address 40008)",
      "writable": true
    },
    {
      "name": "PID_Enable",
      "offset": 8,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "PID enable (manual address 40009)",
      "writable": true
    },
    {
      "name": "Current_Limit",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Current limit (manual address 40010)",
      "writable": true
    },
    {
      "name": "Acceleration_Time",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "s",
      "description": "Acceleration time (manual address 40011)",
      "writable": true
    },
    {
      "name": "Deceleration_Time",
      "offset": 11,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "s",
      "description": "Deceleration time (manual address 40012)",
      "writable": true
    },
    {
      "name": "Digital_Output_1_Group1",
      "offset": 13,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital output 1 (manual address 40014)",
      "writable": true
    },
    {
      "name": "Digital_Output_2_Group1",
      "offset": 14,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital output 2 (manual address 40015)",
      "writable": true
    },
    {
      "name": "Reference_Frequency_Group1",
      "offset": 15,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Reference frequency (manual address 40016)",
      "writable": true
    },
    {
      "name": "PID_Upper_Limit_Group1",
      "offset": 16,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID upper limit (manual address 40017)",
      "writable": true
    },
    {
      "name": "PID_Lower_Limit_Group1",
      "offset": 17,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID lower limit (manual address 40018)",
      "writable": true
    },
    {
      "name": "Proportional_Gain_Group1",
      "offset": 18,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.001,
      "description": "PID proportional gain (manual address 40019)",
      "writable": true
    },
    {
      "name": "Integral_Gain_Group1",
      "offset": 19,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "PID integral gain (manual address 40020)",
      "writable": true
    },
    {
      "name": "Differential_Gain_Group1",
      "offset": 20,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "PID differential gain (manual address 40021)",
      "writable": true
    },
    {
      "name": "Feedback_Gain_Group1",
      "offset": 21,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID feedback gain (manual address 40022)",
      "writable": true
    },
    {
      "name": "Low_Pass_Group1",
      "offset": 22,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "description": "PID feedback low pass (manual address 40023)",
      "writable": true
    },
    {
      "name": "Frequency_Output_Group1",
      "offset": 23,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency (manual address 40024)"
    },
    {
      "name": "Speed_Group1",
      "offset": 24,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "RPM",
      "description": "Speed (manual address 40025)"
    },
    {
      "name": "Current_Group1",
      "offset": 25,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "A",
      "description": "Output current (manual address 40026)"
    },
    {
      "name": "Torque_Group1",
      "offset": 26,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Nm",
      "description": "Torque (manual address 40027)"
    },
    {
      "name": "Actual_Power_Group1",
      "offset": 27,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kW",
      "description": "Actual power (manual address 40028)"
    },
    {
      "name": "Total_kWh_Group1",
      "offset": 28,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "kWh",
      "description": "Total energy consumption (manual address 40029)"
    },
    {
      "name": "DC_Bus_Voltage_Group1",
      "offset": 29,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "DC bus voltage (manual address 40030)"
    },
    {
      "name": "Reference_Group1",
      "offset": 30,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency reference (manual address 40031)"
    },
    {
      "name": "Rated_Power_Group1",
      "offset": 31,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kW",
      "description": "Rated power (manual address 40032)"
    },
    {
      "name": "Voltage_Output_Group1",
      "offset": 32,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Output voltage (manual address 40033)"
    },
    {
      "name": "Forward_Reverse_State",
      "offset": 33,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Forward/reverse state (manual address 40034)"
    },
    {
      "name": "Stop_Run_State",
      "offset": 34,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Stop/run state (manual address 40035)"
    },
    {
      "name": "Run_At_Max_Frequency",
      "offset": 35,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Run at maximum frequency (manual address 40036)"
    },
    {
      "name": "Control_Mode",
      "offset": 36,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control mode (manual address 40037)"
    },
    {
      "name": "Enabled",
      "offset": 37,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Enabled (manual address 40038)"
    },
    {
      "name": "Ready_To_Run",
      "offset": 38,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Ready to run (manual address 40039)"
    },
    {
      "name": "Analog_Input_1_Group1",
      "offset": 39,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Analog input 1 (manual address 40040)"
    },
    {
      "name": "Analog_Input_2_Group1",
      "offset": 40,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Analog input 2 (manual address 40041)"
    },
    {
      "name": "Analog_Output_1_Group1",
      "offset": 41,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Analog output 1 (manual address 40042)"
    },
    {
      "name": "Actual_Frequency",
      "offset": 43,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Actual frequency, percent of reference frequency (manual address 40044)"
    },
    {
      "name": "PID_Setpoint_Output_Group1",
      "offset": 44,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID setpoint output (manual address 40045)"
    },
    {
      "name": "PID_Output_Group1",
      "offset": 45,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID output (manual address 40046)"
    },
    {
      "name": "PID_Feedback_Group1",
      "offset": 46,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID feedback (manual address 40047)"
    },
    {
      "name": "Digital_Input_1_Group1",
      "offset": 47,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 1 (manual address 40048)"
    },
    {
      "name": "Digital_Input_2_Group1",
      "offset": 48,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 2 (manual address 40049)"
    },
    {
      "name": "Digital_Input_3_Group1",
      "offset": 49,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 3 (manual address 40050)"
    },
    {
      "name": "Digital_Input_4_Group1",
      "offset": 50,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 4 (manual address 40051)"
    },
    {
      "name": "Fault_State",
      "offset": 53,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault (manual address 40054)"
    },
    {
      "name": "Last_Fault",
      "offset": 54,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Last fault code (manual address 40055)"
    },
    {
      "name": "Fault_1_Group1",
      "offset": 55,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 1 (manual address 40056)"
    },
    {
      "name": "Fault_2_Group1",
      "offset": 56,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 2 (manual address 40057)"
    },
    {
      "name": "Fault_3_Group1",
      "offset": 57,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 3 (manual address 40058)"
    },
    {
      "name": "Warning_State",
      "offset": 58,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Warning (manual address 40059)"
    },
    {
      "name": "Last_Warning",
      "offset": 59,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Last warning code (manual address 40060)"
    },
    {
      "name": "Inverter_Version_Group1",
      "offset": 60,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "description": "Inverter version (manual address 40061)"
    },
    {
      "name": "Inverter_Model_Group1",
      "offset": 61,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Inverter model (manual address 40062)"
    },
    {
      "name": "Control_Word",
      "offset": 99,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control word STW (process data 1) (manual address 40100)",
      "writable": true
    },
    {
      "name": "Speed_Setpoint",
      "offset": 100,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Speed setpoint HSW (process data 2) (manual address 40101)",
      "writable": true
    },
    {
      "name": "Status_Word",
      "offset": 109,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Status word ZSW (process data 1) (manual address 40110)"
    },
    {
      "name": "Actual_Speed",
      "offset": 110,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Actual speed HIW (process data 2) (manual address 40111)"
    },
    {
      "name": "Digital_Output_1",
      "offset": 199,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital output 1 (manual address 40200)",
      "writable": true
    },
    {
      "name": "Digital_Output_2",
      "offset": 200,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital output 2 (manual address 40201)",
      "writable": true
    },
    {
      "name": "Analog_Output_1",
      "offset": 219,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Analog output 1 (manual address 40220)"
    },
    {
      "name": "Digital_Input_1",
      "offset": 239,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 1 (manual address 40240)"
    },
    {
      "name": "Digital_Input_2",
      "offset": 240,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 2 (manual address 40241)"
    },
    {
      "name": "Digital_Input_3",
      "offset": 241,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 3 (manual address 40242)"
    },
    {
      "name": "Digital_Input_4",
      "offset": 242,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 4 (manual address 40243)"
    },
    {
      "name": "Analog_Input_1",
      "offset": 259,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Analog input 1 (manual address 40260)"
    },
    {
      "name": "Analog_Input_2",
      "offset": 260,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "Analog input 2 (manual address 40261)"
    },
    {
      "name": "Inverter_Model",
      "offset": 299,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Inverter model (manual address 40300)"
    },
    {
      "name": "Inverter_Version",
      "offset": 300,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "description": "Inverter version (manual address 40301)"
    },
    {
      "name": "Rated_Power",
      "offset": 319,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kW",
      "description": "Rated power (manual address 40320)"
    },
    {
      "name": "Current_Limit_Setting",
      "offset": 320,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Current limit (manual address 40321)",
      "writable": true
    },
    {
      "name": "Acceleration_Time_Setting",
      "offset": 321,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "s",
      "description": "Acceleration time (manual address 40322)",
      "writable": true
    },
    {
      "name": "Deceleration_Time_Setting",
      "offset": 322,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "s",
      "description": "Deceleration time (manual address 40323)",
      "writable": true
    },
    {
      "name": "Reference_Frequency",
      "offset": 323,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Reference frequency (manual address 40324)",
      "writable": true
    },
    {
      "name": "Reference",
      "offset": 339,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency reference (manual address 40340)"
    },
    {
      "name": "Speed",
      "offset": 340,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "RPM",
      "description": "Speed (manual address 40341)"
    },
    {
      "name": "Frequency_Output",
      "offset": 341,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency (manual address 40342)"
    },
    {
      "name": "Voltage_Output",
      "offset": 342,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Output voltage (manual address 40343)"
    },
    {
      "name": "DC_Bus_Voltage",
      "offset": 343,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "DC bus voltage (manual address 40344)"
    },
    {
      "name": "Current",
      "offset": 344,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "A",
      "description": "Output current (manual address 40345)"
    },
    {
      "name": "Torque",
      "offset": 345,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Nm",
      "description": "Torque (manual address 40346)"
    },
    {
      "name": "Actual_Power",
      "offset": 346,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kW",
      "description": "Actual power (manual address 40347)"
    },
    {
      "name": "Total_kWh",
      "offset": 347,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "kWh",
      "description": "Total energy consumption (manual address 40348)"
    },
    {
      "name": "Hand_Auto",
      "offset": 348,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Hand/auto (manual address 40349)"
    },
    {
      "name": "Fault_1",
      "offset": 399,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 1 (manual address 40400)"
    },
    {
      "name": "Fault_2",
      "offset": 400,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 2 (manual address 40401)"
    },
    {
      "name": "Fault_3",
      "offset": 401,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 3 (manual address 40402)"
    },
    {
      "name": "Fault_4",
      "offset": 402,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 4 (manual address 40403)"
    },
    {
      "name": "Fault_5",
      "offset": 403,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 5 (manual address 40404)"
    },
    {
      "name": "Fault_6",
      "offset": 404,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 6 (manual address 40405)"
    },
    {
      "name": "Fault_7",
      "offset": 405,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 7 (manual address 40406)"
    },
    {
      "name": "Fault_8",
      "offset": 406,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault code 8 (manual address 40407)"
    },
    {
      "name": "Warning",
      "offset": 407,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Warning code (manual address 40408)"
    },
    {
      "name": "Parameter_Error_Code",
      "offset": 498,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter error code (manual address 40499)"
    },
    {
      "name": "PID_Enable_Setting",
      "offset": 499,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "PID enable (manual address 40500)",
      "writable": true
    },
    {
      "name": "PID_Setpoint_Reference_Setting",
      "offset": 500,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID setpoint reference (manual address 40501)",
      "writable": true
    },
    {
      "name": "PID_Low_Pass",
      "offset": 509,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "description": "PID feedback low pass (manual address 40510)",
      "writable": true
    },
    {
      "name": "PID_Feedback_Gain",
      "offset": 510,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID feedback gain (manual address 40511)",
      "writable": true
    },
    {
      "name": "PID_Proportional_Gain",
      "offset": 511,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.001,
      "description": "PID proportional gain (manual address 40512)",
      "writable": true
    },
    {
      "name": "PID_Integral_Gain",
      "offset": 512,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "PID integral gain (manual address 40513)",
      "writable": true
    },
    {
      "name": "PID_Differential_Gain",
      "offset": 513,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "PID differential gain (manual address 40514)",
      "writable": true
    },
    {
      "name": "PID_Upper_Limit",
      "offset": 514,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID upper limit (manual address 40515)",
      "writable": true
    },
    {
      "name": "PID_Lower_Limit",
      "offset": 515,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID lower limit (manual address 40516)",
      "writable": true
    },
    {
      "name": "PID_Setpoint_Output",
      "offset": 519,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID setpoint output (manual address 40520)"
    },
    {
      "name": "PID_Feedback",
      "offset": 520,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID feedback (manual address 40521)"
    },
    {
      "name": "PID_Output",
      "offset": 521,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "%",
      "description": "PID output (manual address 40522)"
    },
    {
      "name": "Parameter_Number",
      "offset": 549,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter number for indirect parameter access (manual address 40550)",
      "writable": true
    },
    {
      "name": "Parameter_Index",
      "offset": 550,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter index for indirect parameter access (manual address 40551)",
      "writable": true
    },
    {
      "name": "Parameter_Value_Upper_Word_RW",
      "offset": 553,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter value upper word (RW) (manual address 40554)",
      "writable": true
    },
    {
      "name": "Parameter_Value_Lower_Word_RW",
      "offset": 554,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter value lower word (RW) (manual address 40555)",
      "writable": true
    },
    {
      "name": "Parameter_Value_Upper_Word_RO",
      "offset": 557,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter value upper word (RO) (manual address 40558)"
    },
    {
      "name": "Parameter_Value_Lower_Word_RO",
      "offset": 558,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parameter value lower word (RO) (manual address 40559)"
    }
  ]
}