  "format": "voltrus-device-template/1",
  "template_id": "schneider-electric-pm3255",
  "manufacturer": "Schneider Electric",
  "model": "PM3255",
  "protocol": "modbus",
  "description": "DIN-rail power and energy meter that measures through 1 A or 5 A current transformers and can also be connected through voltage transformers. It reports current, voltage, power, power factor, frequency, harmonic distortion, demand and four-quadrant energy, and adds two digital inputs, two digital outputs and an RS-485 Modbus RTU port. Register map: https://voltrus.id/registers/schneider-electric/pm3255/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from DOCA0006EN-09, 07/2026 (https://productinfo.se.com/pm3200/pm3200-user-manual/PM3200%20User%20Manual/English/DOCA0006EN-09.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 1-based numbers (offset = number minus 1).",
    "The manual does not state the word order for 32 and 64-bit values; big (AB CD) is set. Check one known value and change it if it reads wrong.",
    "The manual does not say how 32-bit floats and 64-bit values are laid out across registers.",
    "The device speaks Modbus RTU. Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: RS-485 Modbus RTU (p. 49). Baud rate 9600, 19200 or 38400 (register 6502 codes), parity odd, even or none, one stop bit, address 1 to 247. Supported functions: 03 read holding registers, 16 write multiple registers, 43/14 read device identification, 20 read file record.",
    "1 unsigned 32-bit registers are read as int32: exact up to a raw value of 2,147,483,647.",
    "Not included, because templates have no 64-bit integer or string type: Meter_Name, Meter_Model, Manufacturer, Hardware_Revision, Total_Active_Energy_Import, Total_Active_Energy_Export, Total_Reactive_Energy_Import, Total_Reactive_Energy_Export, Total_Apparent_Energy_Import, Total_Apparent_Energy_Export, Partial_Active_Energy_Import, Partial_Reactive_Energy_Import, Active_Energy_Import_L1, Active_Energy_Import_L2, Active_Energy_Import_L3, Rate1_Active_Energy_Import, Rate2_Active_Energy_Import,",
    "Rate3_Active_Energy_Import, Rate4_Active_Energy_Import."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "Serial_Number",
      "offset": 129,
      "register_type": "int32",
      "register_area": "holding",
      "scale": 1,
      "description": "Serial number (manual address 130)"
    },
    {
      "name": "Firmware_Version",
      "offset": 1636,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Present firmware version (manual address 1637)"
    },
    {
      "name": "Energy_Pulse_Duration",
      "offset": 2128,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "ms",
      "description": "Energy pulse duration (manual address 2129)",
      "writable": true
    },
    {
      "name": "Active_Pulse_Output_Association",
      "offset": 2130,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital output association for active energy pulse (manual address 2131)",
      "writable": true
    },
    {
      "name": "Active_Pulse_Weight",
      "offset": 2131,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "pulse/kWh",
      "description": "Active energy pulse frequency (manual address 2132)",
      "writable": true
    },
    {
      "name": "Command_Requested",
      "offset": 5249,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Requested command number (manual address 5250)",
      "writable": true
    },
    {
      "name": "Command_Status",
      "offset": 5374,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Command status (manual address 5375)"
    },
    {
      "name": "Command_Result",
      "offset": 5375,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Command result code (manual address 5376)"
    },
    {
      "name": "Comm_Protocol",
      "offset": 6499,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Communication protocol (manual address 6500)"
    },
    {
      "name": "Modbus_Address",
      "offset": 6500,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Modbus slave address (manual address 6501)",
      "writable": true
    },
    {
      "name": "Baud_Rate",
      "offset": 6501,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Baud rate code (manual address 6502)",
      "writable": true
    },
    {
      "name": "Parity",
      "offset": 6502,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parity code (manual address 6503)",
      "writable": true
    },
    {
      "name": "DI1_Control_Mode",
      "offset": 7273,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital input 1 control mode (manual address 7274)"
    },
    {
      "name": "DO1_Control_Mode",
      "offset": 9672,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Digital output 1 control mode status (manual address 9673)"
    },
    {
      "name": "Current_I1",
      "offset": 2999,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Phase 1 current (manual address 3000)"
    },
    {
      "name": "Current_I2",
      "offset": 3001,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Phase 2 current (manual address 3002)"
    },
    {
      "name": "Current_I3",
      "offset": 3003,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Phase 3 current (manual address 3004)"
    },
    {
      "name": "Current_In",
      "offset": 3005,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Neutral current (manual address 3006)"
    },
    {
      "name": "Current_Avg",
      "offset": 3009,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Average current (manual address 3010)"
    },
    {
      "name": "Current_Unbalance_Worst",
      "offset": 3017,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Worst current unbalance (manual address 3018)"
    },
    {
      "name": "Voltage_L1_L2",
      "offset": 3019,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Voltage L1 to L2 (manual address 3020)"
    },
    {
      "name": "Voltage_L2_L3",
      "offset": 3021,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Voltage L2 to L3 (manual address 3022)"
    },
    {
      "name": "Voltage_L3_L1",
      "offset": 3023,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Voltage L3 to L1 (manual address 3024)"
    },
    {
      "name": "Voltage_LL_Avg",
      "offset": 3025,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Average line to line voltage (manual address 3026)"
    },
    {
      "name": "Voltage_L1_N",
      "offset": 3027,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Voltage L1 to neutral (manual address 3028)"
    },
    {
      "name": "Voltage_L2_N",
      "offset": 3029,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Voltage L2 to neutral (manual address 3030)"
    },
    {
      "name": "Voltage_L3_N",
      "offset": 3031,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Voltage L3 to neutral (manual address 3032)"
    },
    {
      "name": "Voltage_LN_Avg",
      "offset": 3035,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Average line to neutral voltage (manual address 3036)"
    },
    {
      "name": "Voltage_Unbalance_LL_Worst",
      "offset": 3043,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Worst line to line voltage unbalance (manual address 3044)"
    },
    {
      "name": "Voltage_Unbalance_LN_Worst",
      "offset": 3051,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Worst line to neutral voltage unbalance (manual address 3052)"
    },
    {
      "name": "Active_Power_L1",
      "offset": 3053,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kW",
      "description": "Phase 1 active power (manual address 3054)"
    },
    {
      "name": "Active_Power_L2",
      "offset": 3055,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kW",
      "description": "Phase 2 active power (manual address 3056)"
    },
    {
      "name": "Active_Power_L3",
      "offset": 3057,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kW",
      "description": "Phase 3 active power (manual address 3058)"
    },
    {
      "name": "Active_Power_Total",
      "offset": 3059,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kW",
      "description": "Total active power (manual address 3060)"
    },
    {
      "name": "Reactive_Power_L1",
      "offset": 3061,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVAR",
      "description": "Phase 1 reactive power (manual address 3062)"
    },
    {
      "name": "Reactive_Power_L2",
      "offset": 3063,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVAR",
      "description": "Phase 2 reactive power (manual address 3064)"
    },
    {
      "name": "Reactive_Power_L3",
      "offset": 3065,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVAR",
      "description": "Phase 3 reactive power (manual address 3066)"
    },
    {
      "name": "Reactive_Power_Total",
      "offset": 3067,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVAR",
      "description": "Total reactive power (manual address 3068)"
    },
    {
      "name": "Apparent_Power_L1",
      "offset": 3069,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVA",
      "description": "Phase 1 apparent power (manual address 3070)"
    },
    {
      "name": "Apparent_Power_L2",
      "offset": 3071,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVA",
      "description": "Phase 2 apparent power (manual address 3072)"
    },
    {
      "name": "Apparent_Power_L3",
      "offset": 3073,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVA",
      "description": "Phase 3 apparent power (manual address 3074)"
    },
    {
      "name": "Apparent_Power_Total",
      "offset": 3075,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVA",
      "description": "Total apparent power (manual address 3076)"
    },
    {
      "name": "Power_Factor_L1",
      "offset": 3077,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Phase 1 power factor (manual address 3078)"
    },
    {
      "name": "Power_Factor_L2",
      "offset": 3079,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Phase 2 power factor (manual address 3080)"
    },
    {
      "name": "Power_Factor_L3",
      "offset": 3081,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Phase 3 power factor (manual address 3082)"
    },
    {
      "name": "Power_Factor_Total",
      "offset": 3083,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Total power factor (manual address 3084)"
    },
    {
      "name": "Tangent_Phi_Total",
      "offset": 3107,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Total tangent phi (reactive factor) (manual address 3108)"
    },
    {
      "name": "Frequency",
      "offset": 3109,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "Frequency (manual address 3110)"
    },
    {
      "name": "Temperature",
      "offset": 3131,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "°C",
      "description": "Meter temperature (manual address 3132)"
    },
    {
      "name": "THD_Current_I1",
      "offset": 45099,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Current THD phase 1 (manual address 45100)"
    },
    {
      "name": "THD_Current_I2",
      "offset": 45101,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Current THD phase 2 (manual address 45102)"
    },
    {
      "name": "THD_Current_I3",
      "offset": 45103,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Current THD phase 3 (manual address 45104)"
    },
    {
      "name": "THD_Voltage_LL_Avg",
      "offset": 45115,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Average line to line voltage THD (manual address 45116)"
    },
    {
      "name": "THD_Voltage_LN_Avg",
      "offset": 45125,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Average line to neutral voltage THD (manual address 45126)"
    },
    {
      "name": "Active_Tariff",
      "offset": 4190,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Active tariff rate (manual address 4191)",
      "writable": true
    },
    {
      "name": "Total_Active_Energy_Import_F",
      "offset": 45165,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "Wh",
      "description": "Total active energy import (float) (manual address 45166)"
    },
    {
      "name": "Total_Active_Energy_Export_F",
      "offset": 45167,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "Wh",
      "description": "Total active energy export (float) (manual address 45168)"
    },
    {
      "name": "Total_Reactive_Energy_Import_F",
      "offset": 45169,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "VARh",
      "description": "Total reactive energy import (float) (manual address 45170)"
    },
    {
      "name": "Total_Reactive_Energy_Export_F",
      "offset": 45171,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "VARh",
      "description": "Total reactive energy export (float) (manual address 45172)"
    },
    {
      "name": "Total_Apparent_Energy_Import_F",
      "offset": 45173,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "VAh",
      "description": "Total apparent energy import (float) (manual address 45174)"
    },
    {
      "name": "Total_Apparent_Energy_Export_F",
      "offset": 45175,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "VAh",
      "description": "Total apparent energy export (float) (manual address 45176)"
    },
    {
      "name": "Demand_Method",
      "offset": 3700,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Demand method (manual address 3701)",
      "writable": true
    },
    {
      "name": "Demand_Interval",
      "offset": 3701,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "min",
      "description": "Demand interval duration (manual address 3702)",
      "writable": true
    },
    {
      "name": "Active_Power_Demand",
      "offset": 3765,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kW",
      "description": "Active power present demand (manual address 3766)"
    },
    {
      "name": "Active_Power_Peak_Demand",
      "offset": 3769,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kW",
      "description": "Active power peak demand (manual address 3770)"
    },
    {
      "name": "Reactive_Power_Demand",
      "offset": 3781,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVAR",
      "description": "Reactive power present demand (manual address 3782)"
    },
    {
      "name": "Reactive_Power_Peak_Demand",
      "offset": 3785,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVAR",
      "description": "Reactive power peak demand (manual address 3786)"
    },
    {
      "name": "Apparent_Power_Demand",
      "offset": 3797,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVA",
      "description": "Apparent power present demand (manual address 3798)"
    },
    {
      "name": "Apparent_Power_Peak_Demand",
      "offset": 3801,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "unit": "kVA",
      "description": "Apparent power peak demand (manual address 3802)"
    }
  ]
}