  "format": "voltrus-device-template/1",
  "template_id": "mitsubishi-electric-fr-d700",
  "manufacturer": "Mitsubishi Electric",
  "model": "FR-D700",
  "protocol": "modbus",
  "description": "Small general-purpose inverter series with an RS-485 port on the PU connector that can run Modbus RTU as a slave. The Modbus map covers run and speed commands, live monitor values, the fault history and every inverter parameter. Register map: https://voltrus.id/registers/mitsubishi-electric/fr-d700/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from IB(NA)-0600366ENG-H (1806), printed June 2018 (https://www.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600366eng/ib0600366engh.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints Modicon numbers such as 40001.",
    "The manual does not state the word order for 32 and 64-bit values; big (AB CD) is set. Check one known value and change it if it reads wrong.",
    "Every row is a single 16-bit register.",
    "The device speaks Modbus RTU. Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Per the manual: Modbus RTU is off until Pr. 549 is set to 1. Initial station number 0 (no reply), 19200 bps (Pr. 118 = 192), even parity with 1 stop bit (Pr. 120 = 2), 8 data bits. The PU connector must be the network command source (Pr. 551 = 2) and the inverter in network mode."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "InverterReset",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Inverter reset command (manual address 40002)",
      "writable": true
    },
    {
      "name": "StatusControlWord",
      "offset": 8,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Inverter status (read) or control input command (write) (manual address 40009)",
      "writable": true
    },
    {
      "name": "OperationMode",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Operation mode (read) or mode setting (write) (manual address 40010)",
      "writable": true
    },
    {
      "name": "RunningFrequencyRAM",
      "offset": 13,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Running frequency command, RAM value (manual address 40014)",
      "writable": true
    },
    {
      "name": "RunningFrequencyEEPROM",
      "offset": 14,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Running frequency command, EEPROM value (manual address 40015)",
      "writable": true
    },
    {
      "name": "OutputFrequency",
      "offset": 200,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency or speed (manual address 40201)"
    },
    {
      "name": "OutputCurrent",
      "offset": 201,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "A",
      "description": "Output current (manual address 40202)"
    },
    {
      "name": "OutputVoltage",
      "offset": 202,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "Output voltage (manual address 40203)"
    },
    {
      "name": "FrequencySetting",
      "offset": 204,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency setting or speed setting (manual address 40205)"
    },
    {
      "name": "ConverterOutputVoltage",
      "offset": 207,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "Converter output (DC bus) voltage (manual address 40208)"
    },
    {
      "name": "RegenBrakeDuty",
      "offset": 208,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Regenerative brake duty (manual address 40209)"
    },
    {
      "name": "ElectronicThermalLoad",
      "offset": 209,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Electronic thermal relay load factor (manual address 40210)"
    },
    {
      "name": "OutputCurrentPeak",
      "offset": 210,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "A",
      "description": "Output current peak value (manual address 40211)"
    },
    {
      "name": "ConverterVoltagePeak",
      "offset": 211,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "Converter output voltage peak value (manual address 40212)"
    },
    {
      "name": "OutputPower",
      "offset": 213,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kW",
      "description": "Output power (manual address 40214)"
    },
    {
      "name": "InputTerminalStatus",
      "offset": 214,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Input terminal states (manual address 40215)"
    },
    {
      "name": "OutputTerminalStatus",
      "offset": 215,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Output terminal states (manual address 40216)"
    },
    {
      "name": "CumulativeEnergizationTime",
      "offset": 219,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Cumulative energization time (manual address 40220)"
    },
    {
      "name": "ActualOperationTime",
      "offset": 222,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Actual operation time (manual address 40223)"
    },
    {
      "name": "MotorLoadFactor",
      "offset": 223,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Motor load factor (manual address 40224)"
    },
    {
      "name": "CumulativePower",
      "offset": 224,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "kWh",
      "description": "Cumulative power (manual address 40225)"
    },
    {
      "name": "PIDSetPoint",
      "offset": 251,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID set point (manual address 40252)"
    },
    {
      "name": "PIDMeasuredValue",
      "offset": 252,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID measured value (manual address 40253)"
    },
    {
      "name": "PIDDeviation",
      "offset": 253,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "PID deviation (manual address 40254)"
    },
    {
      "name": "MotorThermalLoad",
      "offset": 260,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Motor thermal load factor (manual address 40261)"
    },
    {
      "name": "InverterThermalLoad",
      "offset": 261,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Inverter thermal load factor (manual address 40262)"
    },
    {
      "name": "CumulativePower2",
      "offset": 262,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kWh",
      "description": "Cumulative power 2 (manual address 40263)"
    },
    {
      "name": "PTCThermistorResistance",
      "offset": 263,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "kΩ",
      "description": "PTC thermistor resistance (manual address 40264)"
    },
    {
      "name": "FaultRecord1",
      "offset": 500,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Most recent fault record (manual address 40501)",
      "writable": true
    },
    {
      "name": "FaultRecord2",
      "offset": 501,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 2 (older) (manual address 40502)"
    },
    {
      "name": "FaultRecord3",
      "offset": 502,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 3 (older) (manual address 40503)"
    },
    {
      "name": "FaultRecord4",
      "offset": 503,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 4 (older) (manual address 40504)"
    },
    {
      "name": "FaultRecord5",
      "offset": 504,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 5 (older) (manual address 40505)"
    },
    {
      "name": "FaultRecord6",
      "offset": 505,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 6 (older) (manual address 40506)"
    },
    {
      "name": "FaultRecord7",
      "offset": 506,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 7 (older) (manual address 40507)"
    },
    {
      "name": "FaultRecord8",
      "offset": 507,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault record 8 (older) (manual address 40508)"
    },
    {
      "name": "Pr7_AccelerationTime",
      "offset": 1006,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "s",
      "description": "Pr. 7 acceleration time (manual address 41007)",
      "writable": true
    },
    {
      "name": "Pr8_DecelerationTime",
      "offset": 1007,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "s",
      "description": "Pr. 8 deceleration time (manual address 41008)",
      "writable": true
    },
    {
      "name": "Pr79_OperationModeSelection",
      "offset": 1078,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 79 operation mode selection (manual address 41079)",
      "writable": true
    },
    {
      "name": "Pr117_StationNumber",
      "offset": 1116,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 117 PU communication station number (Modbus slave address) (manual address 41117)",
      "writable": true
    },
    {
      "name": "Pr118_CommSpeed",
      "offset": 1117,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 118 PU communication speed (manual address 41118)",
      "writable": true
    },
    {
      "name": "Pr120_ParityCheck",
      "offset": 1119,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 120 PU communication parity and stop bits (manual address 41120)",
      "writable": true
    },
    {
      "name": "Pr343_CommErrorCount",
      "offset": 1342,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 343 Modbus RTU communication error count (manual address 41343)"
    },
    {
      "name": "Pr502_CommErrorStopMode",
      "offset": 1501,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 502 stop mode at communication error (manual address 41502)",
      "writable": true
    },
    {
      "name": "Pr549_ProtocolSelection",
      "offset": 1548,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr. 549 protocol selection (manual address 41549)",
      "writable": true
    }
  ]
}