  "format": "voltrus-device-template/1",
  "template_id": "endress-hauser-promag-400",
  "manufacturer": "Endress+Hauser",
  "model": "Proline Promag 400 Modbus RS485",
  "protocol": "modbus",
  "description": "Electromagnetic flowmeter transmitter from the Proline Promag 400 family with a Modbus RS485 interface. Registers cover volume and mass flow, conductivity, three totalizers, unit selections, diagnostics, device information and the Modbus communication settings. Register map: https://voltrus.id/registers/endress-hauser/promag-400/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from GP01045D/06/EN/02.21, 71538157, dated 2022-02-01, valid for device firmware 02.01.zz (https://bdih-download.endress.com/files/DLA/005056A500261EEC9FD771039688391B/GP01045DEN_0221-00.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 0-based addresses, the same as here.",
    "Word order from the manual: Low word first (CD AB).",
    "Float values use two registers. The Byte order parameter (register 4915) selects 0-1-2-3, 3-2-1-0, 2-3-0-1 or 1-0-3-2; the factory setting 1-0-3-2 sends the low-order word first with bytes in normal order (CD AB). The setting can be changed to match the host.",
    "The device speaks Modbus RS485 (RTU or ASCII). Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Bus address range 1 to 247. Baud rate options run from 1200 to 115200. Data transfer mode can be RTU or ASCII, with even, odd or no parity. The byte order parameter ships set to 1-0-3-2.",
    "Not included, because templates have no 64-bit integer or string type: NominalDiameter, DeviceTag, SerialNumber, FirmwareVersion, DeviceName, OrderCode."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "little",
  "registers": [
    {
      "name": "LockingStatus",
      "offset": 4918,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Locking status (manual address 4918)"
    },
    {
      "name": "DirectAccess",
      "offset": 3878,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Direct access code (manual address 3878)",
      "writable": true
    },
    {
      "name": "DeviceReset",
      "offset": 6817,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Device reset (manual address 6817)",
      "writable": true
    },
    {
      "name": "SoftwareOptionOverview",
      "offset": 2902,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Software option overview (manual address 2902)"
    },
    {
      "name": "VolumeFlow",
      "offset": 3874,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Volume flow (manual address 3874)"
    },
    {
      "name": "MassFlow",
      "offset": 3876,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Mass flow (manual address 3876)"
    },
    {
      "name": "Conductivity",
      "offset": 2013,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Conductivity (manual address 2013)"
    },
    {
      "name": "VolumeFlowUnit",
      "offset": 2103,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Volume flow unit code (manual address 2103)",
      "writable": true
    },
    {
      "name": "VolumeUnit",
      "offset": 2104,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Volume unit code (manual address 2104)",
      "writable": true
    },
    {
      "name": "ConductivityUnit",
      "offset": 2121,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Conductivity unit code (manual address 2121)",
      "writable": true
    },
    {
      "name": "TemperatureUnit",
      "offset": 2109,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Temperature unit code (manual address 2109)",
      "writable": true
    },
    {
      "name": "MassFlowUnit",
      "offset": 2101,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Mass flow unit code (manual address 2101)",
      "writable": true
    },
    {
      "name": "MassUnit",
      "offset": 2102,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Mass unit code (manual address 2102)",
      "writable": true
    },
    {
      "name": "DensityUnit",
      "offset": 2107,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Density unit code (manual address 2107)",
      "writable": true
    },
    {
      "name": "FilterOptions",
      "offset": 2273,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Filter option (manual address 2273)",
      "writable": true
    },
    {
      "name": "FlowDamping",
      "offset": 2274,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Flow damping (manual address 2274)",
      "writable": true
    },
    {
      "name": "FlowOverride",
      "offset": 5503,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Flow override (manual address 5503)",
      "writable": true
    },
    {
      "name": "ConductivityDamping",
      "offset": 5508,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Conductivity damping (manual address 5508)",
      "writable": true
    },
    {
      "name": "LowFlowCutoffAssign",
      "offset": 5101,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Low flow cut off, assigned process variable (manual address 5101)",
      "writable": true
    },
    {
      "name": "LowFlowCutoffOn",
      "offset": 5138,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Low flow cut off on value (manual address 5138)",
      "writable": true
    },
    {
      "name": "LowFlowCutoffOff",
      "offset": 5104,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Low flow cut off off value (manual address 5104)",
      "writable": true
    },
    {
      "name": "EmptyPipeDetection",
      "offset": 5106,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Empty pipe detection (manual address 5106)",
      "writable": true
    },
    {
      "name": "EmptyPipeSwitchPoint",
      "offset": 2890,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Empty pipe detection switch point (manual address 2890)",
      "writable": true
    },
    {
      "name": "EmptyPipeMeasuredValue",
      "offset": 2298,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Empty pipe detection measured value (manual address 2298)"
    },
    {
      "name": "ElectrodeCleaning",
      "offset": 2280,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Electrode cleaning circuit (manual address 2280)",
      "writable": true
    },
    {
      "name": "DensitySource",
      "offset": 2497,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Density source (manual address 2497)",
      "writable": true
    },
    {
      "name": "ExternalDensity",
      "offset": 2117,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "External density (manual address 2117)"
    },
    {
      "name": "FixedDensity",
      "offset": 2830,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Fixed density (manual address 2830)",
      "writable": true
    },
    {
      "name": "InstallationDirection",
      "offset": 5501,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Installation direction (manual address 5501)",
      "writable": true
    },
    {
      "name": "VolumeFlowOffset",
      "offset": 5521,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Volume flow offset (manual address 5521)",
      "writable": true
    },
    {
      "name": "VolumeFlowFactor",
      "offset": 5519,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Volume flow factor (manual address 5519)",
      "writable": true
    },
    {
      "name": "MassFlowOffset",
      "offset": 5525,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Mass flow offset (manual address 5525)",
      "writable": true
    },
    {
      "name": "MassFlowFactor",
      "offset": 5523,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Mass flow factor (manual address 5523)",
      "writable": true
    },
    {
      "name": "CalibrationFactor",
      "offset": 2313,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Calibration factor (manual address 2313)"
    },
    {
      "name": "ZeroPoint",
      "offset": 2870,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Zero point (manual address 2870)"
    },
    {
      "name": "BusAddress",
      "offset": 4910,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Modbus bus address (manual address 4910)",
      "writable": true
    },
    {
      "name": "Baudrate",
      "offset": 4912,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Baud rate code (manual address 4912)",
      "writable": true
    },
    {
      "name": "DataTransferMode",
      "offset": 4913,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Data transfer mode (manual address 4913)",
      "writable": true
    },
    {
      "name": "Parity",
      "offset": 4914,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Parity and stop bits (manual address 4914)",
      "writable": true
    },
    {
      "name": "ByteOrder",
      "offset": 4915,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Byte order (manual address 4915)",
      "writable": true
    },
    {
      "name": "TelegramDelay",
      "offset": 4916,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Telegram delay (manual address 4916)",
      "writable": true
    },
    {
      "name": "FailureMode",
      "offset": 4920,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Failure mode (manual address 4920)",
      "writable": true
    },
    {
      "name": "DeviceId",
      "offset": 2547,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Device ID (manual address 2547)"
    },
    {
      "name": "DeviceRevision",
      "offset": 4481,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Device revision (manual address 4481)"
    },
    {
      "name": "ScanListRegister0",
      "offset": 5001,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Modbus data map scan list entry 0 (manual address 5001)",
      "writable": true
    },
    {
      "name": "ResetAllTotalizers",
      "offset": 2609,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Reset all totalizers (manual address 2609)",
      "writable": true
    },
    {
      "name": "Totalizer1Assign",
      "offset": 2601,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 assigned process variable (manual address 2601)",
      "writable": true
    },
    {
      "name": "Totalizer1Unit",
      "offset": 4604,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 unit code (manual address 4604)",
      "writable": true
    },
    {
      "name": "Totalizer1Mode",
      "offset": 2605,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 operation mode (manual address 2605)",
      "writable": true
    },
    {
      "name": "Totalizer1Control",
      "offset": 2608,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 control (manual address 2608)",
      "writable": true
    },
    {
      "name": "Totalizer1Preset",
      "offset": 2590,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 preset value (manual address 2590)",
      "writable": true
    },
    {
      "name": "Totalizer1FailureMode",
      "offset": 2606,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 failure mode (manual address 2606)",
      "writable": true
    },
    {
      "name": "ActualDiagnostics",
      "offset": 2732,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Actual diagnostics (manual address 2732)"
    },
    {
      "name": "PreviousDiagnostics",
      "offset": 2734,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Previous diagnostics (manual address 2734)"
    },
    {
      "name": "ConfigurationCounter",
      "offset": 4818,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Configuration counter (manual address 4818)"
    },
    {
      "name": "ElectronicsTempMin",
      "offset": 2292,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Main electronics temperature, minimum (manual address 2292)"
    },
    {
      "name": "ElectronicsTempMax",
      "offset": 2294,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Main electronics temperature, maximum (manual address 2294)"
    },
    {
      "name": "DeviceAlarmSimulation",
      "offset": 6812,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Device alarm simulation (manual address 6812)",
      "writable": true
    },
    {
      "name": "SimulationAssign",
      "offset": 6813,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Simulation process variable (manual address 6813)",
      "writable": true
    },
    {
      "name": "SimulationValue",
      "offset": 6814,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Simulation process variable value (manual address 6814)",
      "writable": true
    },
    {
      "name": "Totalizer1Value",
      "offset": 2610,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 value (manual address 2610)"
    },
    {
      "name": "Totalizer1Overflow",
      "offset": 2612,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 1 overflow (manual address 2612)"
    },
    {
      "name": "Totalizer2Value",
      "offset": 2810,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 2 value (manual address 2810)"
    },
    {
      "name": "Totalizer2Overflow",
      "offset": 2812,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 2 overflow (manual address 2812)"
    },
    {
      "name": "Totalizer3Value",
      "offset": 3010,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 3 value (manual address 3010)"
    },
    {
      "name": "Totalizer3Overflow",
      "offset": 3012,
      "register_type": "float32",
      "register_area": "holding",
      "scale": 1,
      "description": "Totalizer 3 overflow (manual address 3012)"
    }
  ]
}