  "format": "voltrus-device-template/1",
  "template_id": "delta-vfd-e",
  "manufacturer": "Delta Electronics",
  "model": "VFD-E",
  "protocol": "modbus",
  "description": "General purpose AC motor drive with a built-in RS-485 serial port (RJ-45) for Modbus ASCII and RTU. The address list gives a command word, a frequency command, an error code, status and live monitor values, and every drive parameter at an address built from its group and number. This file lists the fixed command and status area plus the main communication and basic parameters; the full parameter list is in the manual. Register map: https://voltrus.id/registers/delta/vfd-e/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14. Delta Electronics user manual as hosted by the distributor Delta AC Drives; vendor-hosted copy could not be fetched. (https://deltaacdrives.com/Delta-VFD-E-User-Manual.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 0-based addresses, the same as here.",
    "The manual does not state the word order for 32 and 64-bit values; big (AB CD) is set. Check one known value and change it if it reads wrong.",
    "Every row is a single 16-bit register. The user defined display (Pr.00.04) is split into a low word at 2116H and a high word at 2117H, but the manual describes the 2117H bytes as decimal places and an ASCII code rather than a 32-bit value, so they are listed separately.",
    "The device speaks Modbus RTU (also Modbus ASCII). Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Per the parameter summary: address 1 (Pr.09.00), 9600 bps (Pr.09.01 = 1), protocol 0 = Modbus ASCII 7,N,2 (Pr.09.04), so an RTU master needs Pr.09.04 set to 3 to 8. Pr.02.00 = 3 and Pr.02.01 = 3 or 4 hand frequency and run control to RS-485/USB."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "Pr00_00_IdentityCode",
      "offset": 0,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.00.00 identity code of the AC motor drive (manual address 0)"
    },
    {
      "name": "Pr00_01_RatedCurrentDisplay",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "A",
      "description": "Pr.00.01 rated current display of the AC motor drive (manual address 1)"
    },
    {
      "name": "Pr00_02_ParameterReset",
      "offset": 2,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.00.02 parameter reset (manual address 2)",
      "writable": true
    },
    {
      "name": "Pr01_00_MaxOutputFrequency",
      "offset": 256,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Pr.01.00 maximum output frequency (Fmax) (manual address 256)",
      "writable": true
    },
    {
      "name": "Pr01_01_MaxVoltageFrequency",
      "offset": 257,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "Hz",
      "description": "Pr.01.01 maximum voltage frequency (Fbase), motor 0 (manual address 257)",
      "writable": true
    },
    {
      "name": "Pr01_09_AccelTime1",
      "offset": 265,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "Pr.01.09 acceleration time 1 (manual address 265)",
      "writable": true
    },
    {
      "name": "Pr01_10_DecelTime1",
      "offset": 266,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "Pr.01.10 deceleration time 1 (manual address 266)",
      "writable": true
    },
    {
      "name": "Pr01_11_AccelTime2",
      "offset": 267,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "Pr.01.11 acceleration time 2 (manual address 267)",
      "writable": true
    },
    {
      "name": "Pr01_12_DecelTime2",
      "offset": 268,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "Pr.01.12 deceleration time 2 (manual address 268)",
      "writable": true
    },
    {
      "name": "Pr01_19_AccelDecelTimeUnit",
      "offset": 275,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.01.19 accel/decel time unit (manual address 275)",
      "writable": true
    },
    {
      "name": "Pr02_00_MasterFrequencySource",
      "offset": 512,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.02.00 source of first master frequency command (manual address 512)",
      "writable": true
    },
    {
      "name": "Pr02_01_OperationCommandSource",
      "offset": 513,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.02.01 source of first operation command (manual address 513)",
      "writable": true
    },
    {
      "name": "Pr09_00_CommunicationAddress",
      "offset": 2304,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.09.00 communication address (manual address 2304)",
      "writable": true
    },
    {
      "name": "Pr09_01_TransmissionSpeed",
      "offset": 2305,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.09.01 transmission speed (manual address 2305)",
      "writable": true
    },
    {
      "name": "Pr09_02_TransmissionFaultTreatment",
      "offset": 2306,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.09.02 transmission fault treatment (manual address 2306)",
      "writable": true
    },
    {
      "name": "Pr09_03_TimeoutDetection",
      "offset": 2307,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "s",
      "description": "Pr.09.03 time-out detection (manual address 2307)",
      "writable": true
    },
    {
      "name": "Pr09_04_CommunicationProtocol",
      "offset": 2308,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Pr.09.04 communication protocol (manual address 2308)",
      "writable": true
    },
    {
      "name": "Pr09_07_ResponseDelayTime",
      "offset": 2311,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 2,
      "unit": "ms",
      "description": "Pr.09.07 response delay time (manual address 2311)",
      "writable": true
    },
    {
      "name": "CommandWord",
      "offset": 8192,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Command word (run, direction, accel/decel set) (manual address 8192)",
      "writable": true
    },
    {
      "name": "FrequencyCommand",
      "offset": 8193,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency command (manual address 8193)",
      "writable": true
    },
    {
      "name": "ControlCommand2",
      "offset": 8194,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "External fault and reset bits (manual address 8194)",
      "writable": true
    },
    {
      "name": "ErrorCode",
      "offset": 8448,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Error code (manual address 8448)"
    },
    {
      "name": "DriveStatus",
      "offset": 8449,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Status of the AC drive (manual address 8449)"
    },
    {
      "name": "FrequencyCommandMonitor",
      "offset": 8450,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Frequency command (F) (manual address 8450)"
    },
    {
      "name": "OutputFrequency",
      "offset": 8451,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Output frequency (H) (manual address 8451)"
    },
    {
      "name": "OutputCurrent",
      "offset": 8452,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "A",
      "description": "Output current (AXXX.X) (manual address 8452)"
    },
    {
      "name": "DcBusVoltage",
      "offset": 8456,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "DC-BUS voltage (UXXX.X) (manual address 8456)"
    },
    {
      "name": "OutputVoltage",
      "offset": 8457,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "V",
      "description": "Output voltage (EXXX.X) (manual address 8457)"
    },
    {
      "name": "IgbtTemperature",
      "offset": 8458,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "degC",
      "description": "Display temperature of IGBT (manual address 8458)"
    },
    {
      "name": "UserDefinedLowWord",
      "offset": 8470,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "User defined display (low word) (manual address 8470)"
    },
    {
      "name": "UserDefinedHighWord",
      "offset": 8471,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "User defined display (high word) (manual address 8471)"
    }
  ]
}