  "format": "voltrus-device-template/1",
  "template_id": "deif-agc-150",
  "manufacturer": "DEIF",
  "model": "AGC 150",
  "protocol": "modbus",
  "description": "The DEIF AGC 150 is an advanced genset controller with a Modbus server. This map covers the GEN (genset) column of DEIF's AGC 150 Modbus server tables: generator voltage, current, power and energy, running hours and counters, engine communication values, alarm and mode bit words, control command words, remote command coils and status flags. The tables also cover BTB, mains, GEN-H, ENG and ATS controller types, and thousands of further addresses (power management, alarm strings, parameters by offset) that are not listed here. Register map: https://voltrus.id/registers/deif/agc-150/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from DEIF document 4189341212, AGC 150 Modbus server tables (Excel workbook), Revision Y, applicable to AGC 150 software version 1.38.0, DEIF A/S, vendor-hosted. Cited by sheet name and spreadsheet row number. Companion document: AGC 150 Modbus server User manual 4189341435-B EN, based on software version 1.37. (https://deif-cdn-umbraco.azureedge.net/media/f2hiadel/agc-150-modbus-server-tables-4189341212-uk.xlsx?rnd=134278173792730000&v=9), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints 0-based addresses, the same as here.",
    "Word order from the manual: High word first (AB CD).",
    "The user manual (section 3.4) states data format ABCD for 32-bit values, represented with HI16 on the lowest address and LO16 on the highest address. Values are scaled as actual value = register value times 10 to the power of minus scaling. The scale column in this file is the sheet scaling converted to a multiplier, for example scaling 2 becomes 0.01. Bit numbers in the bit words are as printed in the Bit column of the sheet.",
    "Defaults from the manual: RS-485 Modbus ID (parameters 7511 or 7521) range 1 to 247, default 3. RS-485 speed (7512 or 7522) 9600, 19200, 38400 or 115200 baud, default 9600. The TCP port and serial framing are not stated in the Modbus server user manual.",
    "Not included, because templates have no 64-bit integer or string type: Controller_Name."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "Application_Version",
      "offset": 500,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Application version (manual address 500)"
    },
    {
      "name": "Gen_Voltage_L1_L2",
      "offset": 501,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "V",
      "description": "Generator voltage L1-L2 (manual address 501)"
    },
    {
      "name": "Gen_Voltage_L2_L3",
      "offset": 502,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "V",
      "description": "Generator voltage L2-L3 (manual address 502)"
    },
    {
      "name": "Gen_Voltage_L3_L1",
      "offset": 503,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "V",
      "description": "Generator voltage L3-L1 (manual address 503)"
    },
    {
      "name": "Gen_Voltage_L1_N",
      "offset": 504,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "V",
      "description": "Generator voltage L1-N (manual address 504)"
    },
    {
      "name": "Gen_Voltage_L2_N",
      "offset": 505,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "V",
      "description": "Generator voltage L2-N (manual address 505)"
    },
    {
      "name": "Gen_Voltage_L3_N",
      "offset": 506,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "V",
      "description": "Generator voltage L3-N (manual address 506)"
    },
    {
      "name": "Gen_Frequency_L1",
      "offset": 507,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Generator frequency L1 (manual address 507)"
    },
    {
      "name": "Gen_Frequency_L2",
      "offset": 508,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Generator frequency L2 (manual address 508)"
    },
    {
      "name": "Gen_Frequency_L3",
      "offset": 509,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "Hz",
      "description": "Generator frequency L3 (manual address 509)"
    },
    {
      "name": "Gen_Phase_Angle_L1_L2",
      "offset": 510,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "deg",
      "description": "Generator voltage phase angle L1-L2 (manual address 510)"
    },
    {
      "name": "Gen_Phase_Angle_L2_L3",
      "offset": 511,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "deg",
      "description": "Generator voltage phase angle L2-L3 (manual address 511)"
    },
    {
      "name": "Gen_Phase_Angle_L3_L1",
      "offset": 512,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "deg",
      "description": "Generator voltage phase angle L3-L1 (manual address 512)"
    },
    {
      "name": "Gen_Current_L1",
      "offset": 513,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "A",
      "description": "Generator current L1 (manual address 513)"
    },
    {
      "name": "Gen_Current_L2",
      "offset": 514,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "A",
      "description": "Generator current L2 (manual address 514)"
    },
    {
      "name": "Gen_Current_L3",
      "offset": 515,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "A",
      "description": "Generator current L3 (manual address 515)"
    },
    {
      "name": "Gen_Power_L1",
      "offset": 516,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Generator active power L1 (manual address 516)"
    },
    {
      "name": "Gen_Power_L2",
      "offset": 517,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Generator active power L2 (manual address 517)"
    },
    {
      "name": "Gen_Power_L3",
      "offset": 518,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Generator active power L3 (manual address 518)"
    },
    {
      "name": "Gen_Power_Total",
      "offset": 519,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Generator active power total (manual address 519)"
    },
    {
      "name": "Gen_Reactive_Power_L1",
      "offset": 520,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVAr",
      "description": "Generator reactive power L1 (manual address 520)"
    },
    {
      "name": "Gen_Reactive_Power_L2",
      "offset": 521,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVAr",
      "description": "Generator reactive power L2 (manual address 521)"
    },
    {
      "name": "Gen_Reactive_Power_L3",
      "offset": 522,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVAr",
      "description": "Generator reactive power L3 (manual address 522)"
    },
    {
      "name": "Gen_Reactive_Power_Total",
      "offset": 523,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVAr",
      "description": "Generator reactive power total (manual address 523)"
    },
    {
      "name": "Gen_Apparent_Power_L1",
      "offset": 524,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVA",
      "description": "Generator apparent power L1 (manual address 524)"
    },
    {
      "name": "Gen_Apparent_Power_L2",
      "offset": 525,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVA",
      "description": "Generator apparent power L2 (manual address 525)"
    },
    {
      "name": "Gen_Apparent_Power_L3",
      "offset": 526,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVA",
      "description": "Generator apparent power L3 (manual address 526)"
    },
    {
      "name": "Gen_Apparent_Power_Total",
      "offset": 527,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kVA",
      "description": "Generator apparent power total (manual address 527)"
    },
    {
      "name": "Gen_Export_Reactive_Energy_Total",
      "offset": 528,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kVArh",
      "description": "Generator export reactive energy counter, total (manual address 528)"
    },
    {
      "name": "Gen_Export_Active_Energy_Day",
      "offset": 530,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kWh",
      "description": "Generator export active energy counter, day (manual address 530)"
    },
    {
      "name": "Gen_Export_Active_Energy_Week",
      "offset": 532,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kWh",
      "description": "Generator export active energy counter, week (manual address 532)"
    },
    {
      "name": "Gen_Export_Active_Energy_Month",
      "offset": 534,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kWh",
      "description": "Generator export active energy counter, month (manual address 534)"
    },
    {
      "name": "Gen_Export_Active_Energy_Total",
      "offset": 536,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kWh",
      "description": "Generator export active energy counter, total (manual address 536)"
    },
    {
      "name": "Gen_Power_Factor",
      "offset": 538,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "description": "Generator power factor (manual address 538)"
    },
    {
      "name": "Absolute_Running_Hours",
      "offset": 554,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "Absolute running hours (manual address 554)"
    },
    {
      "name": "Relative_Running_Hours",
      "offset": 556,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "description": "Relative running hours (manual address 556)"
    },
    {
      "name": "Alarm_Count",
      "offset": 558,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Number of alarms (manual address 558)"
    },
    {
      "name": "Unacknowledged_Alarm_Count",
      "offset": 559,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Number of unacknowledged alarms (manual address 559)"
    },
    {
      "name": "Active_Acknowledged_Alarm_Count",
      "offset": 560,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Number of active acknowledged alarms (manual address 560)"
    },
    {
      "name": "GB_Operations",
      "offset": 563,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Number of generator breaker operations (manual address 563)"
    },
    {
      "name": "MB_Operations",
      "offset": 564,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Number of mains breaker operations (manual address 564)"
    },
    {
      "name": "Start_Attempts",
      "offset": 566,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Start attempts (manual address 566)"
    },
    {
      "name": "DC_Supply_Voltage",
      "offset": 567,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "DC supply voltage, terminals 1 and 2 (manual address 567)"
    },
    {
      "name": "Service_Timer_1_Hours",
      "offset": 569,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Service timer 1 running hours (manual address 569)"
    },
    {
      "name": "Service_Timer_1_Days",
      "offset": 570,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Service timer 1 running days (manual address 570)"
    },
    {
      "name": "Service_Timer_2_Hours",
      "offset": 571,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Service timer 2 running hours (manual address 571)"
    },
    {
      "name": "Service_Timer_2_Days",
      "offset": 572,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Service timer 2 running days (manual address 572)"
    },
    {
      "name": "Cos_Phi",
      "offset": 573,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "description": "Cos phi (manual address 573)"
    },
    {
      "name": "Cos_Phi_Type",
      "offset": 574,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Cos phi inductive or capacitive (manual address 574)"
    },
    {
      "name": "Engine_RPM",
      "offset": 576,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "rpm",
      "description": "Engine speed (manual address 576)"
    },
    {
      "name": "Mains_Power",
      "offset": 592,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Mains power (single genset) or total mains power (power management) (manual address 592)"
    },
    {
      "name": "Power_Derate_Value",
      "offset": 689,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "%",
      "description": "Power derate value (manual address 689)"
    },
    {
      "name": "Gen_Power_Percent",
      "offset": 747,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Generator active power as percent (manual address 747)"
    },
    {
      "name": "Gen_Reactive_Power_Percent",
      "offset": 748,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Generator reactive power as percent (manual address 748)"
    },
    {
      "name": "Absolute_Running_Minutes",
      "offset": 760,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "min",
      "description": "Absolute running minutes (manual address 760)"
    },
    {
      "name": "Active_Power_Load",
      "offset": 765,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Active power load (manual address 765)"
    },
    {
      "name": "Reactive_Power_Load",
      "offset": 767,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Reactive power load (manual address 767)"
    },
    {
      "name": "EIC_Engine_Speed",
      "offset": 593,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "rpm",
      "description": "Engine communication: Engine Speed (manual address 593)"
    },
    {
      "name": "EIC_Coolant_Temperature",
      "offset": 594,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "Deg C/F",
      "description": "Engine communication: Engine Coolant Temperature (manual address 594)"
    },
    {
      "name": "EIC_Oil_Pressure",
      "offset": 595,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Engine Oil Pressure (manual address 595)"
    },
    {
      "name": "EIC_Active_Fault_Count",
      "offset": 596,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Engine communication: Number of Actual Faults (manual address 596)"
    },
    {
      "name": "EIC_Oil_Temperature",
      "offset": 597,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "Deg C/F",
      "description": "Engine communication: Engine Oil Temperature (manual address 597)"
    },
    {
      "name": "EIC_Fuel_Temperature",
      "offset": 598,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "Deg C/F",
      "description": "Engine communication: Fuel temperature (manual address 598)"
    },
    {
      "name": "EIC_Intake_Manifold_1_Pressure",
      "offset": 599,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Intake manifold #1 pressure (manual address 599)"
    },
    {
      "name": "EIC_Air_Inlet_Temperature",
      "offset": 600,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "Deg C/F",
      "description": "Engine communication: Air inlet temperature (manual address 600)"
    },
    {
      "name": "EIC_Coolant_Level",
      "offset": 601,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "%",
      "description": "Engine communication: Coolant level (manual address 601)"
    },
    {
      "name": "EIC_Fuel_Rate",
      "offset": 602,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "L/h",
      "description": "Engine communication: Fuel rate (manual address 602)"
    },
    {
      "name": "EIC_Charge_Air_Pressure",
      "offset": 603,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "bar/psi",
      "description": "Engine communication: Charge air pressure (manual address 603)"
    },
    {
      "name": "EIC_Intake_Manifold_1_Temperature",
      "offset": 604,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "Deg C/F",
      "description": "Engine communication: Intake manifold #1 temperature (manual address 604)"
    },
    {
      "name": "EIC_Drivers_Demand_Torque",
      "offset": 605,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Engine communication: Driver demand engine percent torque (manual address 605)"
    },
    {
      "name": "EIC_Actual_Torque",
      "offset": 606,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Engine communication: Actual engine percent torque (manual address 606)"
    },
    {
      "name": "EIC_Accelerator_Pedal_Position",
      "offset": 607,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Engine communication: Accelerator pedal position (manual address 607)"
    },
    {
      "name": "EIC_Load_At_Current_Speed",
      "offset": 608,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "%",
      "description": "Engine communication: Percent load at current speed (manual address 608)"
    },
    {
      "name": "EIC_Air_Inlet_Pressure",
      "offset": 609,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Air inlet pressure (manual address 609)"
    },
    {
      "name": "EIC_Exhaust_Gas_Temperature",
      "offset": 610,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "Deg C/F",
      "description": "Engine communication: Exhaust gas temperature (manual address 610)"
    },
    {
      "name": "EIC_Engine_Hours",
      "offset": 611,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "h",
      "description": "Engine communication: Engine hours (manual address 611)"
    },
    {
      "name": "EIC_Oil_Filter_Differential_Pressure",
      "offset": 612,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Engine oil filter differential pressure (manual address 612)"
    },
    {
      "name": "EIC_Keyswitch_Battery_Potential",
      "offset": 613,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "V",
      "description": "Engine communication: Keyswitch battery potential (manual address 613)"
    },
    {
      "name": "EIC_Fuel_Delivery_Pressure",
      "offset": 614,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Fuel delivery pressure (manual address 614)"
    },
    {
      "name": "EIC_Oil_Level",
      "offset": 615,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "%",
      "description": "Engine communication: Engine oil level (manual address 615)"
    },
    {
      "name": "EIC_Crankcase_Pressure",
      "offset": 616,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Crankcase pressure (manual address 616)"
    },
    {
      "name": "EIC_Coolant_Pressure",
      "offset": 617,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Coolant pressure (manual address 617)"
    },
    {
      "name": "EIC_Air_Filter_Differential_Pressure",
      "offset": 625,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.001,
      "unit": "bar/psi",
      "description": "Engine communication: Air filter differential pressure (manual address 625)"
    },
    {
      "name": "EIC_Atmospheric_Pressure",
      "offset": 627,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.01,
      "unit": "bar/psi",
      "description": "Engine communication: Atmospheric pressure (manual address 627)"
    },
    {
      "name": "EIC_Ambient_Air_Temperature",
      "offset": 628,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "Deg C/F",
      "description": "Engine communication: Ambient air temperature (manual address 628)"
    },
    {
      "name": "EIC_Trip_Fuel",
      "offset": 638,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "L",
      "description": "Engine communication: Engine trip fuel (manual address 638)"
    },
    {
      "name": "EIC_Total_Fuel_Used",
      "offset": 639,
      "register_type": "int16",
      "register_area": "input",
      "scale": 0.1,
      "unit": "kL",
      "description": "Engine communication: Engine total fuel used (manual address 639)"
    },
    {
      "name": "EIC_Engine_Operating_State",
      "offset": 854,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "description": "Engine communication: Engine Operating State (manual address 854)"
    },
    {
      "name": "EIC_Engine_Rated_Speed",
      "offset": 856,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "rpm",
      "description": "Engine communication: Engine Rated Speed (manual address 856)"
    },
    {
      "name": "EIC_Engine_Power",
      "offset": 908,
      "register_type": "int16",
      "register_area": "input",
      "scale": 1,
      "unit": "kW",
      "description": "Engine communication: Engine power (manual address 908)"
    },
    {
      "name": "EIC_Engine_Hours_Not_Scaled",
      "offset": 909,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "h",
      "description": "Engine communication: Engine Hours (not scaled) (manual address 909)"
    },
    {
      "name": "EIC_Trip_Fuel_Not_Scaled",
      "offset": 902,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "L",
      "description": "Engine communication: Engine Trip Fuel (not scaled) (manual address 902)"
    },
    {
      "name": "EIC_Total_Fuel_Used_Not_Scaled",
      "offset": 904,
      "register_type": "int32",
      "register_area": "input",
      "scale": 1,
      "unit": "L",
      "description": "Engine communication: Engine Total Fuel Used (not scaled) (manual address 904)"
    },
    {
      "name": "AC_Alarm_Word_1",
      "offset": 1000,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "AC alarm bits 1 (generator power, current, voltage) (manual address 1000)"
    },
    {
      "name": "AC_Alarm_Word_2",
      "offset": 1001,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "AC alarm bits 2 (generator frequency, busbar voltage and frequency) (manual address 1001)"
    },
    {
      "name": "AC_Alarm_Word_3",
      "offset": 1002,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "AC alarm bits 3 (busbar frequency, ROCOF, power, unbalance) (manual address 1002)"
    },
    {
      "name": "AC_Alarm_Word_4",
      "offset": 1003,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "AC alarm bits 4 (sequence components, directional overcurrent) (manual address 1003)"
    },
    {
      "name": "AC_Alarm_Word_5",
      "offset": 1004,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "AC alarm bits 5 (voltage and reactive power, external trips) (manual address 1004)"
    },
    {
      "name": "Alarm_Word_Sync_Breaker",
      "offset": 1005,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Synchronising and breaker alarm bits, phase sequence (manual address 1005)"
    },
    {
      "name": "Alarm_Word_Regulation",
      "offset": 1006,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Governor, deload and AVR regulation alarm bits (manual address 1006)"
    },
    {
      "name": "Alarm_Word_Engine_1",
      "offset": 1013,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Multi input and engine alarm bits 1 (manual address 1013)"
    },
    {
      "name": "Alarm_Word_Engine_2",
      "offset": 1014,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Engine and multi input alarm bits 2 (manual address 1014)"
    },
    {
      "name": "Alarm_Word_Service",
      "offset": 1015,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Service timer and other alarm bits (manual address 1015)"
    },
    {
      "name": "Relay_State_Word_1",
      "offset": 1016,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Relay state bits 1 (manual address 1016)"
    },
    {
      "name": "Relay_State_Word_2",
      "offset": 1017,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Relay state bits 2 (manual address 1017)"
    },
    {
      "name": "Plant_State_Word",
      "offset": 1018,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Plant logic state bits and dry mode bit (manual address 1018)"
    },
    {
      "name": "Mode_Word",
      "offset": 1019,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Operating mode bits (manual address 1019)"
    },
    {
      "name": "EIC_Alarm_Word_1",
      "offset": 1020,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Engine communication alarm bits 1 (manual address 1020)"
    },
    {
      "name": "DAVR_Alarm_Word",
      "offset": 1056,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Digital AVR alarm bits (manual address 1056)"
    },
    {
      "name": "Fail_Class_Word",
      "offset": 1057,
      "register_type": "uint16",
      "register_area": "input",
      "scale": 1,
      "description": "Fail class active bits (manual address 1057)"
    },
    {
      "name": "Cmd_Power_Setpoint",
      "offset": 0,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Power regulator setpoint (manual address 0)",
      "writable": true
    },
    {
      "name": "Cmd_CosPhi_Setpoint",
      "offset": 1,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "cos phi regulator setpoint (manual address 1)",
      "writable": true
    },
    {
      "name": "Cmd_Reactive_Power_Setpoint",
      "offset": 2,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Reactive power regulator setpoint (manual address 2)",
      "writable": true
    },
    {
      "name": "Cmd_Frequency_Setpoint",
      "offset": 3,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Frequency regulator setpoint (manual address 3)",
      "writable": true
    },
    {
      "name": "Cmd_Voltage_Setpoint",
      "offset": 4,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "%",
      "description": "Voltage regulator setpoint (manual address 4)",
      "writable": true
    },
    {
      "name": "Cmd_Word_1",
      "offset": 5,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 1 (manual address 5)",
      "writable": true
    },
    {
      "name": "Cmd_Word_2",
      "offset": 6,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 2 (modes) (manual address 6)",
      "writable": true
    },
    {
      "name": "Cmd_Word_3",
      "offset": 7,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 3 (manual address 7)",
      "writable": true
    },
    {
      "name": "Cmd_Word_4",
      "offset": 8,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 4 (virtual toggle events 1 to 15) (manual address 8)",
      "writable": true
    },
    {
      "name": "Cmd_Word_5",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 5 (virtual toggle events 16 to 30) (manual address 9)",
      "writable": true
    },
    {
      "name": "Cmd_Word_6",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 6 (manual address 10)",
      "writable": true
    },
    {
      "name": "Cmd_Word_7",
      "offset": 13,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control command word 7 (external control enable and disable) (manual address 13)",
      "writable": true
    },
    {
      "name": "Clock_Year",
      "offset": 58000,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: year (manual address 58000)",
      "writable": true
    },
    {
      "name": "Clock_Month",
      "offset": 58001,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: month (manual address 58001)",
      "writable": true
    },
    {
      "name": "Clock_Date",
      "offset": 58002,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: date (manual address 58002)",
      "writable": true
    },
    {
      "name": "Clock_Day",
      "offset": 58003,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: day of week (manual address 58003)",
      "writable": true
    },
    {
      "name": "Clock_Hour",
      "offset": 58004,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: hour (manual address 58004)",
      "writable": true
    },
    {
      "name": "Clock_Minute",
      "offset": 58005,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: minute (manual address 58005)",
      "writable": true
    },
    {
      "name": "Clock_Second",
      "offset": 58006,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Controller clock: second (manual address 58006)",
      "writable": true
    },
    {
      "name": "Coil_Remote_Start",
      "offset": 0,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Remote start (manual address 0)",
      "writable": true
    },
    {
      "name": "Coil_Remote_GB_On",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Remote GB ON (manual address 1)",
      "writable": true
    },
    {
      "name": "Coil_Remote_GB_Off",
      "offset": 2,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Remote GB OFF (manual address 2)",
      "writable": true
    },
    {
      "name": "Coil_Remote_Stop",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Remote stop (manual address 3)",
      "writable": true
    },
    {
      "name": "Coil_Alarm_Inhibit_1",
      "offset": 4,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Alarm inhibit 1 (manual address 4)",
      "writable": true
    },
    {
      "name": "Coil_Alarm_Inhibit_2",
      "offset": 5,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Alarm inhibit 2 (manual address 5)",
      "writable": true
    },
    {
      "name": "Coil_Alarm_Inhibit_3",
      "offset": 6,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Alarm inhibit 3 (manual address 6)",
      "writable": true
    },
    {
      "name": "Coil_Reset_Regulation_Output",
      "offset": 7,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Reset GOV/AVR regulation output to offset (manual address 7)",
      "writable": true
    },
    {
      "name": "Coil_Alarm_Acknowledge",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Alarm acknowledge (manual address 9)",
      "writable": true
    },
    {
      "name": "Coil_Nominal_Setting_1",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Nominal setting 1 (manual address 10)",
      "writable": true
    },
    {
      "name": "Coil_Nominal_Setting_2",
      "offset": 11,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Nominal setting 2 (manual address 11)",
      "writable": true
    },
    {
      "name": "Coil_Nominal_Setting_3",
      "offset": 12,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Nominal setting 3 (manual address 12)",
      "writable": true
    },
    {
      "name": "Coil_Nominal_Setting_4",
      "offset": 13,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Nominal setting 4 (manual address 13)",
      "writable": true
    },
    {
      "name": "Coil_Start_Sync_Manual",
      "offset": 14,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Start and synchronise (manual) (manual address 14)",
      "writable": true
    },
    {
      "name": "Coil_Deload_Stop_Manual",
      "offset": 15,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Deload and stop (manual) (manual address 15)",
      "writable": true
    },
    {
      "name": "Coil_Island_Mode",
      "offset": 16,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Island mode (manual address 16)",
      "writable": true
    },
    {
      "name": "Coil_AMF_Mode",
      "offset": 17,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Automatic mains failure (AMF) mode (manual address 17)",
      "writable": true
    },
    {
      "name": "Coil_Peak_Shaving_Mode",
      "offset": 18,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Peak shaving mode (manual address 18)",
      "writable": true
    },
    {
      "name": "Coil_Fixed_Power_Mode",
      "offset": 19,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Fixed power mode (manual address 19)",
      "writable": true
    },
    {
      "name": "Coil_Mains_Power_Export_Mode",
      "offset": 20,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Mains power export (MPE) mode (manual address 20)",
      "writable": true
    },
    {
      "name": "Coil_Load_Takeover_Mode",
      "offset": 21,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Load takeover (LTO) mode (manual address 21)",
      "writable": true
    },
    {
      "name": "Coil_MB_On",
      "offset": 24,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Mains breaker ON (manual address 24)",
      "writable": true
    },
    {
      "name": "Coil_MB_Off",
      "offset": 25,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Mains breaker OFF (manual address 25)",
      "writable": true
    },
    {
      "name": "Coil_Auto_Start_Stop",
      "offset": 26,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Auto start/stop (manual address 26)",
      "writable": true
    },
    {
      "name": "Coil_No_Regulation_Mode",
      "offset": 27,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "No regulation mode (manual address 27)",
      "writable": true
    },
    {
      "name": "Coil_Manual_Mode",
      "offset": 28,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "MANUAL mode (manual address 28)",
      "writable": true
    },
    {
      "name": "Coil_Auto_Mode",
      "offset": 29,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "AUTO mode (manual address 29)",
      "writable": true
    },
    {
      "name": "Coil_Test_Mode",
      "offset": 30,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "TEST mode (manual address 30)",
      "writable": true
    },
    {
      "name": "Coil_Reset_Horn",
      "offset": 135,
      "register_type": "uint16",
      "register_area": "coil",
      "scale": 1,
      "description": "Reset horn (manual address 135)",
      "writable": true
    },
    {
      "name": "DI_GB_Position_On",
      "offset": 0,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Generator breaker position ON (manual address 0)"
    },
    {
      "name": "DI_MB_Position_On",
      "offset": 1,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Mains breaker position ON (manual address 1)"
    },
    {
      "name": "DI_Running",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Running (manual address 3)"
    },
    {
      "name": "DI_Gen_Voltage_Frequency_OK",
      "offset": 4,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Generator voltage and frequency OK (manual address 4)"
    },
    {
      "name": "DI_Mains_Failure",
      "offset": 5,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Mains failure (single DG) (manual address 5)"
    },
    {
      "name": "DI_Block_Mode",
      "offset": 6,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "BLOCK mode (manual address 6)"
    },
    {
      "name": "DI_No_Regulation_Mode",
      "offset": 7,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "No regulation mode (manual address 7)"
    },
    {
      "name": "DI_Manual_Mode",
      "offset": 8,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "MANUAL mode (manual address 8)"
    },
    {
      "name": "DI_Auto_Mode",
      "offset": 9,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "AUTO mode (manual address 9)"
    },
    {
      "name": "DI_Test_Mode",
      "offset": 10,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "TEST mode (manual address 10)"
    },
    {
      "name": "DI_GB_Position_Off",
      "offset": 11,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Generator breaker position OFF (manual address 11)"
    },
    {
      "name": "DI_MB_Position_Off",
      "offset": 12,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Mains breaker position OFF (manual address 12)"
    },
    {
      "name": "DI_Island_Mode",
      "offset": 13,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Island mode (manual address 13)"
    },
    {
      "name": "DI_AMF_Mode",
      "offset": 14,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Automatic mains failure (AMF) mode (manual address 14)"
    },
    {
      "name": "DI_Peak_Shaving_Mode",
      "offset": 15,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Peak shaving mode (manual address 15)"
    },
    {
      "name": "DI_Fixed_Power_Mode",
      "offset": 16,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Fixed power mode (manual address 16)"
    },
    {
      "name": "DI_Mains_Power_Export_Mode",
      "offset": 17,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Mains power export (MPE) mode (manual address 17)"
    },
    {
      "name": "DI_Load_Takeover_Mode",
      "offset": 18,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Load takeover (LTO) mode (manual address 18)"
    },
    {
      "name": "DI_Power_Management",
      "offset": 19,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Power management (manual address 19)"
    },
    {
      "name": "DI_Battery_Test",
      "offset": 29,
      "register_type": "uint16",
      "register_area": "discrete",
      "scale": 1,
      "description": "Battery test (manual address 29)"
    }
  ]
}