  "format": "voltrus-device-template/1",
  "template_id": "abb-acs355",
  "manufacturer": "ABB",
  "model": "ACS355",
  "protocol": "modbus",
  "description": "Compact ABB machinery drive for 0.37 to 22 kW motors. The embedded fieldbus interface speaks Modbus RTU and maps the control word, status word, two references, selectable actual values and every drive parameter to 4xxxx holding registers. Register map: https://voltrus.id/registers/abb/acs355/",
  "version": "1.0.0",
  "verified": false,
  "verified_notes": "Generated by voltrus.id from 3AUA0000066143 Rev E, effective 2020-11-02 (https://library.e.abb.com/public/805f31a82d524d8aa8a750011e2cd001/EN_ACS355_UM_E_A5.pdf), read 2026-10-24. Not checked against a real device; confirm a known value before relying on it.",
  "quirks": [
    "Offsets are 0-based wire addresses. The manual prints Modicon numbers such as 40001.",
    "The manual does not state the word order for 32 and 64-bit values; big (AB CD) is set. Check one known value and change it if it reads wrong.",
    "All rows listed here are single 16-bit registers, so no multi-register word order applies. The DCU profile 32-bit control and status words are split into separate low and high word registers.",
    "The device speaks Modbus RTU (embedded fieldbus, RS-232 or EIA-485). Voltrus SCADA polls Modbus TCP, so connect it through a Modbus RTU to TCP gateway: use the gateway's IP and port and the device's unit ID.",
    "Defaults from the manual: Station ID is set with parameter 5302 (range 0 to 247). The communication profile is chosen with parameter 5305 (ABB DRV LIM, ABB DRV FULL or DCU PROFILE). Parameter writes over Modbus are volatile; parameter 1607 saves them (p. 326)."
  ],
  "license": "CC-BY-4.0",
  "port": 502,
  "unit_id": 1,
  "interval_ms": 1000,
  "endianness": "big",
  "registers": [
    {
      "name": "ControlWord",
      "offset": 0,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Control word (manual address 40001)",
      "writable": true
    },
    {
      "name": "Reference1",
      "offset": 1,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "External reference REF1 (manual address 40002)",
      "writable": true
    },
    {
      "name": "Reference2",
      "offset": 2,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "External reference REF2 (manual address 40003)",
      "writable": true
    },
    {
      "name": "StatusWord",
      "offset": 3,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Status word (manual address 40004)"
    },
    {
      "name": "ActualValue1",
      "offset": 4,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Actual value 1 (manual address 40005)"
    },
    {
      "name": "ActualValue2",
      "offset": 5,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "description": "Actual value 2 (manual address 40006)"
    },
    {
      "name": "DCU_ControlWordLSW",
      "offset": 30,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "DCU profile control word, low word (manual address 40031)",
      "writable": true
    },
    {
      "name": "DCU_ControlWordMSW",
      "offset": 31,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "DCU profile control word, high word (manual address 40032)",
      "writable": true
    },
    {
      "name": "DCU_StatusWordLSW",
      "offset": 32,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "DCU profile status word, low word (manual address 40033)"
    },
    {
      "name": "DCU_StatusWordMSW",
      "offset": 33,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "DCU profile status word, high word (manual address 40034)"
    },
    {
      "name": "SpeedAndDirection",
      "offset": 100,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "rpm",
      "description": "Motor speed with direction (0101) (manual address 40101)"
    },
    {
      "name": "Speed",
      "offset": 101,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "rpm",
      "description": "Motor speed (0102) (manual address 40102)"
    },
    {
      "name": "OutputFrequency",
      "offset": 102,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "Hz",
      "description": "Output frequency (0103) (manual address 40103)"
    },
    {
      "name": "Current",
      "offset": 103,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "A",
      "description": "Motor current (0104) (manual address 40104)"
    },
    {
      "name": "Torque",
      "offset": 104,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Motor torque percent of nominal (0105) (manual address 40105)"
    },
    {
      "name": "Power",
      "offset": 105,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "kW",
      "description": "Motor power (0106) (manual address 40106)"
    },
    {
      "name": "DCBusVoltage",
      "offset": 106,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "DC bus voltage (0107) (manual address 40107)"
    },
    {
      "name": "OutputVoltage",
      "offset": 108,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "V",
      "description": "Output voltage (0109) (manual address 40109)"
    },
    {
      "name": "DriveTemperature",
      "offset": 109,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "°C",
      "description": "Drive IGBT temperature (0110) (manual address 40110)"
    },
    {
      "name": "ControlLocation",
      "offset": 112,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Active control location (0113) (manual address 40113)"
    },
    {
      "name": "RunTime",
      "offset": 113,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "h",
      "description": "Running time counter (0114) (manual address 40114)"
    },
    {
      "name": "kWhCounter",
      "offset": 114,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "kWh",
      "description": "Energy counter (0115) (manual address 40115)"
    },
    {
      "name": "AnalogInput1",
      "offset": 119,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Analog input AI1 relative value (0120) (manual address 40120)"
    },
    {
      "name": "AnalogInput2",
      "offset": 120,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Analog input AI2 relative value (0121) (manual address 40121)"
    },
    {
      "name": "AnalogOutput1",
      "offset": 123,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "mA",
      "description": "Analog output AO1 value (0124) (manual address 40124)"
    },
    {
      "name": "PID1Output",
      "offset": 125,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "%",
      "description": "Process PID1 output (0126) (manual address 40126)"
    },
    {
      "name": "FBCmdWord1",
      "offset": 300,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fieldbus command word 1 (0301) (manual address 40301)"
    },
    {
      "name": "FBCmdWord2",
      "offset": 301,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fieldbus command word 2 (0302) (manual address 40302)"
    },
    {
      "name": "FBStsWord1",
      "offset": 302,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fieldbus status word 1 (0303) (manual address 40303)"
    },
    {
      "name": "FBStsWord2",
      "offset": 303,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fieldbus status word 2 (0304) (manual address 40304)"
    },
    {
      "name": "FaultWord1",
      "offset": 304,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault word 1 (0305) (manual address 40305)"
    },
    {
      "name": "FaultWord2",
      "offset": 305,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault word 2 (0306) (manual address 40306)"
    },
    {
      "name": "FaultWord3",
      "offset": 306,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Fault word 3 (0307) (manual address 40307)"
    },
    {
      "name": "AlarmWord1",
      "offset": 307,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm word 1 (0308) (manual address 40308)"
    },
    {
      "name": "AlarmWord2",
      "offset": 308,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Alarm word 2 (0309) (manual address 40309)"
    },
    {
      "name": "LastFault",
      "offset": 400,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Code of the latest fault (0401) (manual address 40401)"
    },
    {
      "name": "SpeedAtFault",
      "offset": 403,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "rpm",
      "description": "Motor speed at latest fault (0404) (manual address 40404)"
    },
    {
      "name": "FreqAtFault",
      "offset": 404,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "Hz",
      "description": "Output frequency at latest fault (0405) (manual address 40405)"
    },
    {
      "name": "MinimumSpeed",
      "offset": 2000,
      "register_type": "int16",
      "register_area": "holding",
      "scale": 1,
      "unit": "rpm",
      "description": "Minimum speed (2001) (manual address 42001)",
      "writable": true
    },
    {
      "name": "MaximumSpeed",
      "offset": 2001,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "unit": "rpm",
      "description": "Maximum speed (2002) (manual address 42002)",
      "writable": true
    },
    {
      "name": "AccelTime1",
      "offset": 2201,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "s",
      "description": "Acceleration time 1 (2202) (manual address 42202)",
      "writable": true
    },
    {
      "name": "DecelTime1",
      "offset": 2202,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 0.1,
      "unit": "s",
      "description": "Deceleration time 1 (2203) (manual address 42203)",
      "writable": true
    },
    {
      "name": "EFB_StationId",
      "offset": 5301,
      "register_type": "uint16",
      "register_area": "holding",
      "scale": 1,
      "description": "Embedded fieldbus station ID (5302) (manual address 45302)",
      "writable": true
    }
  ]
}